1. Catalogs
  2. Tongdy Control Technology
  3. F06-DP series of Dew-proof thermostat | Tongdy®

F06-DP series of Dew-proof thermostat | Tongdy®
1 /3Pages

F06-DP series of Dew-proof thermostat | Tongdy®

F06-DP series of Dew-proof thermostat | Tongdy®
1 /3Pages

Catalog excerpts

F06-DP series of Dew-proof thermostat | Tongdy®-1

Dew-Proof Thermostat- DATASHEET Model: F06-DP For floor cooling/heating radiant AC systems with dew-proof control of the floor Features Special design for cooling/heating AC systems of floor hydronic radiant with dew-proof control of the floor temperature sensor. Room temperature &humidity and floor temperature can be pre-set by users. Provides a more comfortable living environment with Used in the hydronic radiant heating system, it will be a saving energy. room thermostat with humidity control and floor over Attractive turn-cover design, most frequently used keys are located next to the LCD for quick and easy access to operation. setup keys are located on the interior to heating protection. 2 or 3xon/off outputs to control the water valve/humidifier/ dehumidifier separately. Two control modes selectable by users in cooling to eliminate accident setting changes. Large white backlit LCD with enough messages for quick control the water valve. One mode is controlled by either and easy readability and operation. Like, real-time room temperature or humidity. The another mode is detected room temperature, humidity, and pre-set room controlled by either floor temperature or room humidity. temperature, working state of water valve, etc. Celsius degree or Fahrenheit degree display selectable. Smart thermostat& hygrostat with room temperature control and floor dew–proof control in cooling. Room thermostat with maximum limit of temperature for floor in heating Used in the hydronic radiant cooling system with auto Both temperature differential and humidity differential can be pre-set in order to maintain an optimal control of your hydronic radiant AC systems. Special design of pressure signal input to control the water valve. Humidify or dehumidify mode selectable All pre-set settings can be remembered even energized again after a power failure. calculating the dew point temperature by real-time Infrared remote control optional. detecting room temperature and humidity. RS485 communication interface optional. Floor temperature is be detected by the external cooling/heating mode humidify/dehumidify switch humidify/ dehumidify switch mode control mode switch

 Open the catalog to page 1
F06-DP series of Dew-proof thermostat | Tongdy®-2

Specifications Power Supply Electrical rating 1 amp rated switch current/per terminal Temperature: NTC sensor ; Humidity: Capacitance sensor Temperature measuring range Temperature setting range Temperature accuracy Humidity measuring range Humidity setting range Humidity accuracy Mounting standard Mounting on the wall, 2“×4“or 65mm×65mm wire box PC/ABS plastic fireproof material DESCRIPTION Dew-proof thermostat for hydronic radiant floor cooling/heating AC systems. White backlit LCD. 2xon/off outputs to a water valve and a humidity device (humidifier or dehumidifier). 1Xexternal on/off or analog...

 Open the catalog to page 2
F06-DP series of Dew-proof thermostat | Tongdy®-3

Mounting and Wiring Diagram Line Voltage 24VAC Common water valve 24VAC Transformer 24VAC Transformer 24VAC Common 24VAC Common water valve 24VAC Transformer 24VAC Transformer 24VAC Transformer 24VAC Common 24VAC Common 24VAC Common water valve water valve water valve Line Line Voltage Voltage water valve humidity devvice humidity devvice o C o C dehumidifier 24VAC Transformer humidity devvice Transformer dehumidifier Transformer o humidifier C o humidifier C o Cexternal senser external senser external senser A outside singnal input(analog/on-off) A RS-485 RS-485 B B external senser external...

 Open the catalog to page 3

All Tongdy Control Technology catalogs and technical brochures

  1. MSD

    6  Pages

  2. TSP-16

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.