Features
  • Real-time CO2 level detection using NDIR infrared technology.
  • Self-Calibration Algorithm with a sensor lifespan of over 10 years.
  • Wall-mountable design suitable for HVAC and ventilation systems.
  • Provides one analog output with options for 0~10VDC or 0~10VDC/4~20mA.
  • Optional Modbus RS485 communication interface.
  • CE-Approved.
Specifications
  • Gas Detected: Carbon Dioxide (CO2).
  • Sensing Element: Non-Dispersive Infrared Detector (NDIR).
  • Accuracy: ±70ppm + 3% of reading at 25℃ (77℉).
  • Stability: Less than 2% of full scale over the sensor's life (10 years typical).
  • Response Time: Less than 2 minutes for 90% step change.
  • Warm-up Time: 10 minutes initially, 30 seconds during operation.
  • CO2 Measuring Range: 0 to 2,000ppm.
  • Power Supply: 24VAC/24VDC with a consumption of 3.6 W max, 2.4 W avg.
  • Analog Outputs: 1X0~10VDC linear output or selectable 1X0~10VDC/4~20mA.
  • Modbus Interface: RS485 with various baud rates.
  • Operating Conditions: 0~50℃ (32~122℉); 0~95% RH, non-condensing.
  • Storage Conditions: 0~50℃ (32~122℉).
  • Net Weight: 160g.
  • Dimensions: 100mm x 80mm x 28mm.
  • Installation Standard: 65mm x 65mm or 2” x 4” wire box.
  • Approval: CE-Approved.
Models Guide
  • F12-S8100: 1X0~10VDC output, CO2 range: 0~2,000ppm.
  • F12-S8200: 1X0~10VDC/4~20mA output (selectable by jumpers), CO2 range: 0~2,000ppm.
  • F12-S8201: 1X0~10VDC/4~20mA output (selectable by jumpers), with Modbus RS485 communication.
Wiring Diagram

Includes connections for 24VAC, 24VDC, RS-485, 0-10VDC, and 4-20mA outputs.

Mounting

Details not specified in the document.

Shipping Information
  • Individual Carton Dimensions: 115mm x 95mm x 45mm.
  • Master Carton Quantity: 80 units.
  • Master Carton Dimensions: 45cm (L) x 34cm (W) x 34cm (H).
  • Master Carton Weight: 16KG.
See more

Catalog excerpts

CARBON DIOXIDE DETECTOR  Model: F12-S8100/8201-1

Tongdy Sensing Technology Corporation www.tongdy.com CARBON DIOXIDE DETECTOR Model: F12-S8100/8201 ♦ Real-time detecting CO2 level. ♦ NDIR infrared CO2 module inside ♦ CO2 sensor has Self-Calibration Algorithm and more than 10 years lifetime ♦ Wall-mounting ♦ Providing one analog output ♦ Only 0~10VDC output or 0~10VDC/4~20mA selectable ♦ Design for basic application in HVAC, ventilation systems applications ♦ Modbus RS485 communication interface optional ♦ CE-Approval Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China Tel: (86 10) 59738930/31/32 Fax: (86 10) 59738935 E-Mail: [email protected]

 Open the catalog to page 1
CARBON DIOXIDE DETECTOR  Model: F12-S8100/8201-2

Tongdy Sensing Technology Corporation www.tongdy.com Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China Tel: (86 10) 59738930/31/32 Fax: (86 10) 59738935 E-Mail: info@tongdy com

 Open the catalog to page 2

All Tongdy Control Technology catalogs and technical brochures

  1. MSD

    6  Pages

  2. TSP-16

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.