Product catalog summary
Overview: The BACnet Commercial Thermostat F08-PSB-21/22 Series is designed for use in FCU air conditioning systems, controlling a 3-speed fan and one or two water valves. It is compatible with BACnet MS/TP networks and includes a PIC statement for easy integration and mapping to graphical user interfaces.
Features: The thermostat features an LCD display showing room temperature, set point, and fan speed, with user-friendly setting buttons. It offers a large set point range with user-defined temperature limits, low temperature protection, and selectable Celsius or Fahrenheit display. Optional features include infrared remote control and a blue backlight.
Specifications: The thermostat operates on a 24VAC/VDC±10% power supply. It includes 3 relay outputs for the fan and 2 Triac outputs for water valves. The BACnet interface supports adjustable baud rates. The temperature sensor is NTC 5K, with a control range of 5-35℃ (41℉-95℉) and an accuracy of ±0.5℃ (±1℉) at 25℃. The device weighs 280g and measures 130mm x 90mm x 32mm.
Models: Two models are available: F08-PSB-21 for 2-pipe FCU systems with one water valve output, and F08-PSB-22 for 4-pipe systems with two water valve outputs. Both models support auto or manual fan speed adjustment and cooling/heating mode selection.
Options: Optional features include a blue backlight (EL) and infrared remote control (R).
Shipping Information: Individual carton dimensions are 135mm x 95mm x 55mm. Master cartons contain 40 units, measuring 44cm x 34cm x 32cm and weighing 14kg.
See more

Catalog excerpts

BACnet thermostat for FCU: F08-PSB | Tongdy®-1

BACnet Commercial Thermostat F08-PSB-21/22 Series 3-Speed Fan and One or Two Water Valves Control Features LCD displays working status such as room Typical used in FCU air conditioning systems, with temperature, set point, fan speed, etc. Makes reading control a 3-speed fan and one or two water valves and operating easy and accurate. Designed for BACnet MS/TP network with a PIC All models feature user-friendly setting buttons statement to further facilitate integration. Large set point range, the min. and max. limit of A PIC statement is supplied to be easily mapped temperature presetting by end users back to a graphical user interface. Self configuring / adjustable baud-rate senses the Celsius or Fahrenheit degree selectable communication conditions of the current MS/TP Infrared Remote Control (optional) network and match them. Blue backlight (optional) Buttons and LCD Description room temp. or set point air speed locking mode turn on/off mode switch Specifications Power supply 3 relay outputs with each 5A for 3-speed fan 2XTriac outputs with each 1A for one or two water valves BACnet interface BACnet MS/TP with adjustable baud-rate Temperature Sensor Temperature Control Range

 Open the catalog to page 1
BACnet thermostat for FCU: F08-PSB | Tongdy®-2

Mounting Standard Mounting on or inside the wall, 2“×4“/ 65mm×65mm box Models Types BACnet thermostat for 2-pipes FCU systems Power supply: -(F): 24VAC BACnet thermostat for 4-pipes FCU systems Power supply: -(F): 24VAC 3-speed fan auto or manual adjustment, 1X on/off output to one 2-wire water valve 3-speed fan auto or manual adjustment, 2X on/off outputs to two 2-wire water valves for 4 pipes systems. Cooling/heating auto change over or manual switch selectable Remote Control-R Infrared remote control Shipping Information Wiring Diagrams VA-Heat VA-Cool MS/TP MS/TP + open close VA-Heat VA-Cool...

 Open the catalog to page 2
BACnet thermostat for FCU: F08-PSB | Tongdy®-3

ggy Tongdy Control Technology Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China

 Open the catalog to page 3

All Tongdy Control Technology catalogs and technical brochures

  1. MSD

    6  Pages

  2. TSP-16

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.