Overview
The TMI-Orion VACQ xFlat 2.8 Radio and VACQ xFlat 4.8 Radio are autonomous data loggers designed for real-time temperature measurement in thermal process control. The 2.8 model supports 16 thermocouple connectors, while the 4.8 model supports 32 connectors. Both models can operate with an AC adapter or in battery mode for greater temperature range autonomy.

Specifications
  • Thermocouple Channels: 16 for 2.8 model, 32 for 4.8 model.
  • Operating Range: 0°C to +60°C with AC adapter; -55°C to +140°C with batteries.
  • Measurement Range: Varies by thermocouple type (e.g., Type K: 0°C to +1300°C).
  • Resolution: <± 0.1°C.
  • Calibration Uncertainties: ± 0.2°C from 0°C to +140°C.
  • Material: Anodized aluminum.
  • Dimensions: 150 mm x 20 mm x 80 mm for 2.8 model; 150 mm x 40 mm x 80 mm for 4.8 model.
  • Memory Capacity: 13,700 acquisitions per channel for 2.8 model; 13,443 for 4.8 model.
  • Connectivity: 2.4 GHz radio transceiver and USB interface.

Functions
The devices support 2.4 GHz radio communication, immediate or delayed start setup, real-time or post-process data transmission, and battery level alerts via Qlever software. They operate on the 2.4 GHz ISM band and can manage multiple devices in a star configuration.

Autonomy
Powered by an AC adapter or two 015S batteries, the autonomy varies based on environmental and operational conditions. Users are advised to determine battery life based on their specific process conditions.

Radio-Frequency Communication
The devices use TMI-Orion's 2.4 GHz radio protocol based on the IEEE 802.15.4 standard, offering 14 RF channels and a maximum radiated power of +5 dBm.

Deliverables
The package includes the data logger, calibration certificate, configuration file, and optional accessories like a radio transceiver and Qlever software platform.

Software and Related Products
The Qlever software platform facilitates data acquisition and management, compatible with Windows Vista/7/8/10. The VACQ xFlat family also includes models with non-interchangeable power supplies for remote real-time wireless setup and data reading.
See more

Catalog excerpts

VACQ xFlat 2.8 and 4.8 Radio-1

DATA SHEET VACQ xFlat 2.8 Radio and VACQ xFlat 4.8 Radio Real time temperature measurement at various points for thermal process control. The VACQ xFlat 2.8 Radio is an autonomous data logger equipped with 16 thermocouple connectors. The VACQ xFlat 4.8 Radio is an autonomous data logger equipped with 32 thermocouple connectors. The use of the logger with power adapter frees the user from battery lifetime concerns. When required by the application, it is possible to switch to battery mode so the logger is fully autonomous and offers a greater operating range in temperature. It must be protected by a thermal shield when the temperature exceeds +140°C. The Radio function allows real time visualization and/or recording of data. Each logger can be calibrated and adjusted at the temperature points corresponding to the user’s needs. *The specified uncertainties correspond to two standard deviations. The uncertainties are calculated taking into account the various significant error sources, including the calibration probes, the equipment, the environmental conditions, the influence of the logger, repeatability, etc... TMI-Orion VACQ xFlat 2.8 Radio an

 Open the catalog to page 1
VACQ xFlat 2.8 and 4.8 Radio-2

• 2.4 GHz radio communication • Time stamped measurement data • Start set up: immediate or delayed • Battery level alert with Qlever software • Real time or after the process radio data transmission • Interchangeable power supply (*) A preliminary test Is recommended to validate the hertztan transmission In the user’s application. TMI-Orion VACQ xFlat 2.8 Radio and VACQ xFlat 4.8 Radio

 Open the catalog to page 2
VACQ xFlat 2.8 and 4.8 Radio-3

VACQ xFlat 2.8 Radio with AC adapter VACQ xFlat 2.8 Radio with batteries VACQ xFlat 4.8 Radio with AC adapter VACQ xFlat 4.8 Radio with batteries RADIO-FREQUENCY COMMUNICATION • 2.4 GHz ISM band (frequency range 2.405 GHz to 2.475 GHz) / Can be used without license / Universal band for industrial, scientific and medical devices with low radio transmission power / Maximum radiated power +5 dBm (3,2 mW). Radio transmission range depends on the environment. TMI-Orion 2.4 GHz radio protocol, based on IEEE 802.15.4 standard / 14 RF channels for the user / Able to manage several pieces of equipment...

 Open the catalog to page 3
VACQ xFlat 2.8 and 4.8 Radio-4

SOFTWARE AND RELATED PRODUCTS VACQ xFlat 2.8 Radio and VACQ xFlat 4.8 Radio are used with Qlever software platform and a TMI-Orion radio transceiver. Qlever software platform: data acquisition, management and visualization of data from TMI-Orion data loggers. Qlever is installed on a PC and operates under Windows® Vista/7/8/10. Depending on the use of VACQ xFlat 2.8 Radio and VACQ xFlat 4.8 Radio, data transmission and visualization is done in real time or after the process. TMI-Orion radio transceiver: this transmitting device connects to the PC in order to ensure radio link with the VACQ xFlat...

 Open the catalog to page 4

All TMI-ORION catalogs and technical brochures

  1. VACQ3000

    2  Pages

  2. NanoVACQ HT

    4  Pages

  3. NanoVACQ Ex

    3  Pages

  4. NanoVACQ Ad

    3  Pages

  5. MiniVACQ

    2  Pages

  6. High-T-Dry

    3  Pages

  7. CeriDry

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.