The Model 208A & 208D Line Voltage & Phase Sequence Detectors are designed to quickly determine phase sequence (ABC or CBA) and detect missing phases in a 3-phase circuit. Available in 50/60Hz and 400Hz versions, these detectors illuminate specific lamps to indicate phase presence and sequence.

Specifications
  • Model 208A-208/240V and 208A-480V operate at 50/60Hz, while Model 208D-208/240V operates at 400Hz.
  • Continuous connection time with fly leads.
  • Weight: 3.2 oz.
  • Enclosure made of ABS plastic.

Connection Procedure
Connect the detector to a 3-phase power source. Apply AC power and observe the illuminated lamp to determine phase sequence. If incorrect, swap any two leads. Ensure all phases are present; if not, check for voltage loss.

3-Phase Power Basics
In a 3-phase system, phases are typically labeled A-B-C, with phase B lagging A by 120 degrees and phase C lagging A by 240 degrees. Correct phase sequence is crucial for proper equipment operation.

Warranty
The product is warranted against defects in materials and workmanship for one year from the date of manufacture. For warranty details, refer to the Time Mark catalog or contact them directly.

Safety Instructions
Ensure all electrical power is removed when connecting or disconnecting wiring. Installation and servicing should be performed by qualified personnel due to potentially hazardous voltages.
See more

Catalog excerpts

MODEL 208-1

The Model 208A & 208D Line Voltage & Phase Sequence Detectors allows quick and easy determination of phase sequence (either ABC or CBA). Available in 50/60Hz and 400Hz versions, this unit can also show that all phases are present, or if one or more phases are lost, it indicates which of the phases are missing. To use, connect the Detector to any 3-phase circuit, Wye or Delta. In proper phase sequence, and with all phases present, the ABC lamp, and the three line voltage lamps will illuminate. An open phase condition will illuminate both rotation lamps and only two line voltage lamps. See the Condition Chart. E-mail: [email protected] Internet: http://www.time-mark.com 1 1440 East Pine Street Tulsa, Oklahoma 7411 6 11/2011 © 2011 TIME MARK CORPORATION TIME MARK is a division of

 Open the catalog to page 1
MODEL 208-2

Line Voltage & Phase Sequence Detectors READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE. KEEP THIS DATA SHEET FOR FUTURE REFERENCE. GENERAL SAFETY POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODELS 208A OR D DETECTORS. ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. THIS DEVICE AND WIRING SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL. OPERATOR INSTRUCTIONS CONNECTION Connect the three leads to the 3-phase power source. Apply AC power. One of the detector lamps should illuminate indicating the phase sequence...

 Open the catalog to page 2

All Time Mark catalogs and technical brochures

  1. MODEL 108C

    2  Pages

  2. MODEL 108B

    2  Pages

  3. MODEL 108A

    2  Pages

  4. Relay

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.