iRTU

iRTU

iRTU

Product catalog summary
Highlights
  • Adaptable and modular Remote Telecontrol Units (RTUs) suitable for diverse environments.
  • Supports a full range of communication protocols including DNP3.0, IEC 61850, and IEC 60870-5.
  • Embedded Ethernet switch with redundancy features and multiple port options.
Overview

The iRTU is a scalable solution for substation automation, capable of handling both legacy and modern protocols across various network types. It simplifies automation by integrating functions typically requiring multiple devices, such as data acquisition and protocol conversion, into a single compact unit.

Standards and Compliance

The iRTU complies with numerous standards, including IEC61850-3 and IEC60255-26, ensuring reliability in harsh environments. It incorporates IEC 61131-3 for PLC automation, allowing for flexible programming and control.

Communication Ports

Equipped with multiple Ethernet and serial ports, the iRTU supports various configurations, including optional internal modems for wireless communication. It ensures robust network synchronization with multiple time management protocols.

Inputs and Outputs

The iRTU features internal I/O modules with high isolation and accuracy, supporting various input voltage levels and providing configurable debounce and decluttering filters.

Communication Protocols & IP Networking

Designed to handle numerous protocols, the iRTU facilitates complex IP network control through transparent TCP bridging and configurable IP routing. It is certified for IEC 61850 capabilities.

iGWlite Device

A compact gateway device for protocol conversion, the iGWlite supports TASE 2.0 and offers various port configurations, making it suitable for smaller generation plants.

Series and Configurations

The iRTU is available in various series (B0, S, M) with different port and modem configurations, allowing for tailored solutions to specific needs.

Time Synchronization and RTC

Features a real-time clock with high accuracy and supports multiple synchronization protocols to ensure network reliability.

Configuration & Maintenance

Offers easy configuration through the iConf tool and supports real-time monitoring and maintenance via web server or local/remote access.

See more

Catalog excerpts

iRTU-1

iRTU One compact device, designed to solve any network challenge Highlights • Adaptable and modular Remote Telecontrol Units suitable for all environments • Full range of protocols (DNP3.0, IEC 61850, IEC 60870-5... ) to communicate with all devices and control centers • Embedded Ethernet switch with (2) 10/100 BaseTx, (2) FX100 fiber optics and RSTP/ PRP/ HSR redundancy • Up to 4 Ethernet ports, 4 serial ports, and optional, internal 4G, 3G and GPRS modems Overview Our scalable RTUs can simultaneously handle older and newer protocols on serial, wireless and Ethernet networks making substation automation less complex and more affordable. Remote telecontrol units (RTUs) for SCADAs are frequently employed as bay controllers for data acquisition in substations, often requiring further devices for gateway and more advanced functionalities like load shedding or microsecond timestamping. Our modular iRTUs are powerful controllers with embedded ethernet switches, state-ofthe-art features and internal I/Os, allowing you to do it all with one small device. They can map serial servers to IEC 61850 logical nodes, collect and process data from old and new IEDs, report directly to the cotrol center with any standard protocol (e.g. IEC 60970-5-104, DNP3) and handle all common protocol conversions:. An architecture based on iRTUs is open and scalable: you can easily integrate future generations of devices (IEDs, sensors, routers etc.) and adapt to any present and future needs, such as changing network topology or communication m

 Open the catalog to page 1
iRTU-2

Communication Ports The iRTU comes with 2 independent 10/100 BaseTX Ethernet ports (two different MAC addresses, RJ45 connector) and an internal Ethernet switch with (2) 10/100BaseTX, (2) fiber optic FX100 sensors with ST, SC o SFP connectors, and RSTP/PRP/ HSR redundancy. The diverse backgrounds of our partners and clients from all over the world have helped us gather state-of-the-art knowhow and firsthand experience in a great variety of energy applications. This joint knowledge is the foundation of our optimized iRTU family, which has a proven track record of being particularly effective and...

 Open the catalog to page 2
iRTU-3

(4) Software configurable serial ports with LEDs: (1) Full RS-232/ RS-422/ RS-485 serial port (2) Basic RS-232/ RS-422/ RS-485 serial ports (1) RS-422/ RS-485 serial port (EXP-422 port*) (2) 10/100BaseTX Ethernet ports (RJ45 connector) (1) USB port to connect peripheral devices (1) MGMT port (MiniUSB connector) for local maintenance The M series replaces one of the serial ports with an internal modem: M0 (GPRS), M1 (3G + GPRS) and M2 (4G/LTE + GPRS) Internal I/O Configurations iGW S/M/B Series: no I/Os, same ports as iRTUs C1 – (8) digital inputs, (4) relay outputs, and (2) DC current analog...

 Open the catalog to page 3
iRTU-4

Protocol Stack General Characteristics Power supply W : wide range, 32 - 250Vdc / 80 - 250Vac (2.5kVrms isolation) 24 : 19.5-60Vdc (2.5kVrms isolation) Master/Slave Modbus TCP/UDP and JBUS (master) Master/Slave ModbusRTU Master DLMS Master Spabus, Mlink, Procome Environmental Operating temperature : -25ºC to +70ºC IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-3, IEC 60068-2-14, IEC 60068-2-30, IEC 60068-2-38 SNMP Agent/Manager Vibration & shock test IEC 60068-2-6, IEC 60068-2-7 Physical External dimensions: 173 x 78.4 x 137 mm (HxWxD) IP30 enclosure with DIN Rail mounting MTBF 177,000h (one hundred...

 Open the catalog to page 4

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.