Overview: The FT8250 Cooling Tower is part of the FT Series Fiberglass Cooling Towers, designed for industrial environments with a focus on durability and efficiency.
Standard Features:
  • Fiberglass Construction: Offers corrosion resistance and durability in harsh conditions.
  • Direct Drive Fan Motor: Features a direct drive motor with permanently sealed bearings, eliminating the need for maintenance on motor bearings, belts, pulleys, and gearboxes.
  • Stainless Steel Fasteners: Provides additional strength and corrosion resistance.
  • PVC Fill and Internal Piping: Ensures optimal efficiency and longevity with minimal maintenance.
  • Fiberglass Inlet Louvers: Prevents debris and animals from entering the basin.
  • Pressurized Water Distribution System: Utilizes a nonferrous rotating sprinkler head and PVC piping for reliable operation.
  • Factory Assembled: Delivered fully assembled, except for the motor and fan, to prevent shipping damage and facilitate easy installation.
Warranty:
  • 10-year parts warranty on the fiberglass shell.
  • 1-year parts warranty on the complete cooling tower.
Model Specifications:
  • Cooling Capacity: 60 tons.
  • Fan Motor: 2 hp, 5 FLA @ 460/3/60.
  • Nominal Flow: 180 gpm.
  • Inlet Pressure Required: 5 psi.
  • Operating Range: 90 to 340 gpm.
  • Shipping Weight: 750 lbs.
  • Operating Weight: 2,100 lbs.
Dimensions:
  • Inlet/Outlet Sizes: 4" inlet and outlet.
  • Height: 84".
  • Width: 92".
Additional Information: Thermal Care is ISO-9001 Certified, and the manufacturer reserves the right to change specifications or designs without notification.
See more

Catalog excerpts

FT Series Fiberglass Cooling Tower-1

FT Series Fiberglass Cooling Tower Direct Drive Fan Motor Direct drive motor with permanently sealed bearing connected direct to fan to eliminate motor bearing, belt, pulley, and gear box maintenance. Stainless Steel Fasteners Stainless steel fasteners provide added strength and corrosion resistance for long life and durability in severe environmental conditions. PVC Fill and Internal Piping Optimal efficiency and long life with low maintenance and no concern of rust or corrosion typical of galvanized steel towers. Fiberglass Inlet Louvers Air inlet louvers kept unwanted debris and animals out of the basin and ensure water splashes in the basin stay in the tower. Pressurized Water Distribution System Pressurized, nonferrous rotating sprinkler head with large non-clogging openings and PVC distribution piping for trouble-free operation. Factory Assembled Fully assembled with motor and fan removed to prevent shipping damage makes installation quick and easy. Standard Features Fiberglass Construction Corrosion resistant rugged fiberglass withstands harsh weather and industrial manufacturing environments. Warranty 10 year parts on fiberglass shell 1 year parts on complete cooling tower Inlet Pressure Required (psi)

 Open the catalog to page 1
FT Series Fiberglass Cooling Tower-2

FT Series Fiberglass Cooling Tower 5680 W. Jarvis Ave • Niles, IL 60714 847-966-2260 • [email protected] www.thermalcare.com Thermal Care is ISO-9001 Certified Manufacturer reserve the right to change specification or design without notification or obligation FT Specification 0

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.