Technical Specifications:
The TPS HV 80 E energy storage system is available in two configurations: 10 battery modules with 80 kWh energy content and 7 battery modules with 56 kWh. The nominal voltage for these configurations is 810 V and 567 V, respectively. The system supports a maximum charging/discharging current of 100 A and a maximum C-Rate of 0.6C for the 80 kWh configuration and 0.9C for the 56 kWh configuration. The battery cells are Lithium NMC prismatic from Samsung SDI, with a DynamiX Battery Optimizer for cell balancing. The expected cycle life is 6,000 cycles at 1C/1C and 8,000 cycles at 0.5C/0.5C, both at 100% DoD and 70% SoH at 23°C ±5°C. The system efficiency can reach up to 98%, with a standby self-consumption of 5 W without a battery inverter. The operating temperature range is 0°C to 50°C, and the system can be installed at altitudes below 2,000 m above sea level.

Certifications and Standards:
The system complies with several standards, including IEC 62619, UL 1642, UN 38.3 for cells, and additional standards for battery modules and products. It offers a 10-year performance guarantee and a 5-year system guarantee. Recycling is supported through a free take-back scheme in Germany.

Technical Data STPS X 50:
The STPS X 50 has a nominal power of 50 kVA, with an AC voltage range of 340 V to 477 V and a grid frequency range of 44 Hz to 66 Hz. The DC voltage range is 200 V to 980 V. It features a maximum efficiency of 98% and a European efficiency of 97.2%. The operating temperature range is -25°C to 60°C, with a noise emission of 69 dB(A). The protection class is IP 65 | NEMA 4X, and it supports communication via Modbus, SMA Speedwire, and Webconnect.

Container Specifications:
The containers are available in 10 ft and 20 ft sizes, with a maximum energy content of 640 kWh and 1,280 kWh, respectively. They include a rack system, AC subdistribution, air conditioning, and a fire alarm system. Optional features include CSC certification, extended operating temperature range, and enhanced corrosion protection.

System Configurations:
The system can be configured with up to 16 systems for both 80 kWh and 56 kWh configurations, with varying energy outputs and container sizes. The configurations are project-specific for 20 ft variants and all 56 kWh per battery string variants.
See more

Catalog excerpts

TPS HV 80 E-1

TECHNICAL DATA SHEET TPS HV 80 E TECHNICAL DATA ENERGY STORAGE Length of battery string (number of battery modules) Energy content Nominal voltage Minimum operating voltage Maximum operating voltage Maximum charging/discharging current Maximum C-Rate 0,9C Lithium NMC prismatic (Samsung SDI) Cell balancing Cycles expected @ 100% DoD | 70% SoH | 23°C +/-5°C 1C/1C Cycles expected @ 100% DoD | 70% SoH | 23°C +/-5°C 0.5C/0.5C Efficiency (battery) Self-consumption (standby) DynamiX Battery Optimizer 6,000 8,000 up to 98 % 5 W (without battery inverter) Cooling concept passive via fins and active via fans Altitude of installation site Operating temperature Ambient temperature Weight battery module Weight battery magament system (APU) Certificates/standards 13 kg Cell Battery module Product 10-year performance guarantee, 5-year system guarantee TESVOLT offers a free take-back scheme for batteries from Germany Protection class battery module Degree of protection battery module Battery specification as per IEC 62620:2014 TECHNICAL DATA STPS X 50 Nominal power AC voltage range Grid frequency range DC voltage range Dimensions (H x W x D) Max. efficiency/European efficiency Self-consumption (standby) Operating temperature Noise emission (typical) Weight Protection class Communication Topology/cooling principle Guarantee Certificates 50 kVA 340 V to 477 V 44 Hz to 66 Hz 200 V ⎓ to 980 V ⎓ 837.3 mm × 772 mm × 443.8 mm 98%/97.2% 25 W -25 to 60°C (with derating) 69 dB (A) 104 kg IP 65 | NEMA 4X Modbus (SMA, Sunspec), SMA Speedwire, Webconnect Three-phase/active 5 years standard SMA guarantee (optional: 10 years) see SMA website for more: https:

 Open the catalog to page 1
TPS HV 80 E-2

Corrosion protection (paint) Ambient temperature (air conditioning) Altitude of installation site Sizes [ft] Dimensions (as delivered) H x W x D [mm] Dimensions (after installation) H x W x D [mm] Max. Number of storage systems Max. energy content [kWh] Included in standard scope of delivery Special equipment (optional) Extended ambient temperature (air conditioning) (optional) Rack system, AC subdistribution, air conditioning, fire alarm system according to DIN 14675, rupture disk CSC certification, available in other RAL colors, extended operating temperature range, corrosion protection up...