video corpo

TEOS 300

TEOS 300

TEOS 300

Product catalog summary
General Specifications
The TEOS 300 series offers a range of UPS systems with capacities from 10kVA to 80kVA, featuring DSP technology for high performance and an output power factor of 1.0. It supports dual inputs, active power factor correction, and can operate in ECO mode for energy savings. The system includes an emergency power off function and adjustable charging current, with optional parallel operation and a 4.3” touch LCD.

Technical Specifications
The models (Teos 310 to Teos 380) are 3-phase in/out systems with capacities ranging from 10kVA/10kW to 80kVA/80kW. They support parallel operation of up to 4 units. Input voltage ranges from 190-520VAC at 50% load and 305-478VAC at 100% load, with a frequency range of 46~54Hz or 56~64Hz. The output voltage is 3 x 360/380/400/415 VAC with AC voltage regulation of ±1% in battery mode. The systems have a crest factor of 3:1 and harmonic distortion of ≤2% THD for linear loads.

Efficiency and Battery
The UPS operates at 95.5% efficiency in AC mode, 98.5% in ECO mode, and 94.5% in battery mode. Battery configurations are adjustable, with a maximum charge current of ±136.5 VDC or ±218 VDC.

Physical and Environmental
Dimensions and weight vary by model, with operating temperatures from 0ºC to 40ºC and humidity below 95%. Acoustic noise levels range from <62dBA to <75dBA depending on the model.

Management
The system supports smart RS-232/USB connections and is compatible with various operating systems. Optional SNMP allows power management via SNMP manager and web browser.
See more

Catalog excerpts

TEOS 300-1

DATA CENTER HOME & OFFICE MALLS & FACILITIES TEOS 300 10-80kVA Output Power Factor (PF) 1.0 DSP Technology Split By-pass SERVICE / TECH. SUPPORT G E N E R A L S P E C I F I C AT I O N S • DSP technology guarantees high performance • Adjustable charging current • Output power factor 1.0 • Very powerful charger • Active power factor correction in all phases • Optional parallel operation with common battery • Dual Inputs • High overload capability • 50Hz/60Hz frequency converter mode • Adjustable battery design • ECO mode operation for energy saving • Emergency power off function (E

 Open the catalog to page 1
TEOS 300-2

Parallel capability INPUT Nominal voltage Input voltage range Frequency range Power factor OUTPUT Voltage Frequency range (synchronized range) Frequency range (batt. mode) Frequency tolerance Crest factor Harmonic distortion Transfer time ≤ 2 % THD (Linear Load) ≤ 5 % THD (Non-linear load) AC mode to batt. mode Waveform (batt. mode) Overload Pure sinewave Battery mode Battery mode BATTERIES Battery type Number of batteries Charge current (max.) Depends on the application 20 pcs internal 32 pcs (can be extended with external cabinet) UPS status, Load level, Battery level, Input/Output voltage,...

 Open the catalog to page 2

All Tescom catalogs and technical brochures

  1. XT100

    2  Pages

  2. ACCESSORIES

    4  Pages

  3. TEOS RT

    2  Pages

  4. TEOS 200

    2  Pages

  5. XT200

    2  Pages

  6. DS POWER X

    2  Pages

  7. DS POWER XL

    2  Pages

  8. DS POWER

    2  Pages

  9. DS POWER SH

    2  Pages

  10. XT300

    2  Pages

  11. STS 2000

    2  Pages

  12. STS 4000

    2  Pages

  13. TVR 11 SERIES

    2  Pages

  14. TVR 33 SERIES

    2  Pages

  15. TVR 33 SERIES

    2  Pages

  16. SD SERIES

    2  Pages

  17. TEOS+ 100

    2  Pages

  18. TEOS100

    2  Pages

  19. Leo

    2  Pages

  20. TEOS100xl

    2  Pages

  21. Leo+

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.