TemPower 2 ACB Catalogue

TemPower 2 ACB Catalogue
1 / 80 PagesView full catalog

TemPower 2 ACB Catalogue

Product catalog summary
Introduction
Terasaki's TemPower2 Air Circuit Breaker (ACB) is designed for switchboard builders, consultants, and end users, featuring a compact size and the innovative "Double Break" system for enhanced operational capability and space efficiency.
Specifications and Standards
The TemPower2 ACB complies with international standards such as JIS C 8201-2-1, IEC60947-2, and others, certified by organizations like ASTA, NK, LR, ABS, GL, and BV.
Innovations and Features
Models range from 800A to 6300A, featuring a "Double Break" contact system for fast interruption and reduced wear. The design supports easy maintenance and contact replacement.
Technical Specifications
The ACBs offer a short time withstand rating equal to the service short-circuit breaking capacity, ensuring full selectivity up to the system fault level and high mechanical endurance.
Protection and Safety Features
Advanced protection features include RMS sensing over-current release, reverse power trip, ground fault trip, and phase rotation protection, with remote communication via Modbus.
Maintenance and Accessibility
Designed for easy installation and maintenance, the ACBs allow vertical stacking without extra arc space, reducing switchboard height and costs.
Advanced Features
Options for double neutrals and TemCurve Selectivity Analysis Software are available, maintaining performance even when tripped by an external relay.
Conclusion
The TemPower2 ACBs offer compact, efficient circuit protection with a focus on reliability, maintenance ease, and advanced safety features.
Overview
The document details technical specifications and features of the TemPower2 ACBs, including design, functionality, communication capabilities, and configurations for diverse applications.
Specifications
Designed for high packing density, the ACBs offer true RMS protection, reverse power protection, and load shedding relay capabilities, compliant with IEC 60255-3 standards.
Communication and Monitoring
Equipped with a communication interface for Modbus network data exchange, supporting up to 31 units per network over 1.2 km.
Protection Features
Includes ground fault protection, LSI characteristic curves, self-checking protection relays, contact temperature monitoring, and fault diagnosis.
Maintenance and Operation
Field-changeable terminal connections and accessories, with main contacts changeable in 15 minutes per pole. Tripping coil monitoring and alarm features included.
Ratings and Configurations
Lists models with various ampere ratings, operational voltages, and breaking capacities, detailing life cycles, weight, and dimensions for fixed and draw-out types.
Mounting Types
Available in draw-out and fixed types, with terminal arrangements affecting maximum rated current.
Specifications and Procedures
Outlines specifications and procedures for reverse power protection and trip pickup times, with specific equipment requirements.
Accessories
Includes power cable, AC adaptor, signal cable, and operation manual.
Ratings and Specifications
Details the ANU-2 OCR test interface unit for reverse power protection checks, with power supply requirements.
Measurement Outputs
Measures trip pickup currents and times for various protection functions.
Current Transformer Specifications
Details for current transformers for neutral lines, including rated currents.
Auxiliary Switches and Trip Indicators
Describes auxiliary switch operations and trip indicator functions.
Interlocking and Safety Features
Describes key locks, interlocks, and safety features for unauthorized operation prevention.
Environmental Conditions
Specifies operating environment conditions and special treatments for different climates.
Discrimination in Circuit Breakers
Explains discrimination to ensure only downstream breakers open during faults, with total and partial discrimination definitions.
Reading Discrimination Tables
Tables indicate total discrimination with 'T', following IEC 60947-2 standards.
Worked Example
Example of total discrimination for a 1600A ACB feeding a 400A MCCB with a 65kA fault level.
Discrimination Table
Lists combinations of upstream ACBs and downstream MCCBs, indicating total selectivity.
TemTransfer Automatic Changeover Controller
Monitors AC mains supply, switching to a generator if limits are exceeded, compatible with TemPower2 ACBs and other devices.
Order Form and Accessories
Includes an order form for TemPower2 ACBs, detailing mounting options and accessories.
See more

Catalog excerpts

TemPower 2 ACB Catalogue-1

Innovators in Protection Technology Double Breaker

 Open the catalog to page 1
TemPower 2 ACB Catalogue-2

Terasaki’s TemPower2 A.C.B is the result of an intensive market r e s e a rch p ro g r a m which took into account the requirements of switchboard builders, consultants and end users. TemPower2 Air Circuit Breaker is one of the smallest in the market with a 1 second rating (Icw). öBased Standards Innovations ¡The product range of the world's smallest ACBs, TemPower2 broadens with new 5000A and 6300A models. ¡A TemPower2 model with a frame size of 4000A is downsized.

 Open the catalog to page 2
TemPower 2 ACB Catalogue-4

1 Features The ultimate in compactness and operational capability Icw,1s = Ics for all TemPower2 ACBs. TemPower2 TemPower2 is the world’s first “Double Break” ACB, having two breaking contacts per phase. The unique pole structure means that the short time withstand rating (Icw, 1sec) is equal to the service short-circuit breaking capacity (Ics) for all models. Full selectivity is guaranteed up to the full system fault level. TemPower2 ACBs have the world’s smallest depth resulting in space saving in switchboards. Saved space More than twenty design patents have been registered for the TemPower2...

 Open the catalog to page 4
TemPower 2 ACB Catalogue-5

Increased accessibility from the front It enhances ease of installation, operation, and maintenance. Connection to the main circuit (for front connections) Connection to the control circuit Accessory fitting (Removing the front cover enables replacement of internal parts.) Manual operation The double insulated design ensures that most accessories can be safely and easily, installed by the user. Control, auxiliary and position switch terminals are mounted at the front on the ACB body for easy access. Horizontal, vertical and front terminal connections, can also be changed by the user for any last...

 Open the catalog to page 5
TemPower 2 ACB Catalogue-6

1 Features A high performance and reliability Very fast interruption by “DoubleBreak” system¶ The unique “DoubleBreak” main contact system ensures extremely fast interruption of short circuit currents and substantially reduces main contact wear. The internally symmetrical “DoubleBreak” structure means the moving contact is isolated from the supply voltage even when the ACB is reverse connected. The neutral pole of all TemPower2 ACBs are of early make/late break design. This eliminates the risk of abnormal line to neutral voltages, which may damage sensitive electronic equipment. “DoubleBreak”...

 Open the catalog to page 6
TemPower 2 ACB Catalogue-7

Enhanced selectivity Long time delay Short time delay At Terasaki our protection relays have ‘LSI’ characteristics as standard. This provides an adjustable time delay on overload (L) and also the l2t ramp characteristic (S). As shown, these are essential to provide selectivity when grading with other protective devices such as downstream fuses and upstream relays. The standard ‘LSI’ curve provides more than five million combinations of unique time current characteristics. Zone selective interlocking is available to provide zero time delay selectivity. As the rated breaking capacity is identical...

 Open the catalog to page 7
TemPower 2 ACB Catalogue-8

TemP<mer2 provides positive protection lor electric power systems. The TemPower2 series is equipped with an RMS sensing over-current release (OCR) having a wide range of protection functions and capabilities. OVER-CURRENT RELEASE OVER-CURRENT RELEASE OVER-CURRENT RELEASE Standard OCR with adjustment dial Standard OCR with LCD-'Ammeter' Enhanced OCR with LCD- 'Analyser' Overload protection Adjustable from 40-100% of rated current. True r.m.s detec- tion up to the 19th harmonic, a distant vision for the competi- tion who rarely see past the 7th. Neutral protection for all those Triple-N harmonics,...

 Open the catalog to page 8
TemPower 2 ACB Catalogue-9

For general feeder circuits (L-characteristic) For general feeder circuits (R-characteristic) For generator protection (S-characteristic) FOR FULL DETAILS REFER TO THE FEATURES TABLE PAGE 28-29 Two channel pre-trip alarm function (optional) Advanced L.C.D. display, Over Current Relay This function can be used to monitor and switch on additional The AGR-31B OCR comes standard with the backlit LCD dis- power backup to feed critical circuits. For example, the function play. It can monitor and indicate phase currents, voltages, power, can be set so that when a pre-trip alarm is activated, an emer-...

 Open the catalog to page 9
TemPower 2 ACB Catalogue-10

1 Features Optimum protective coordination Why use a separate panel mounted protection relay when you can have all the benefits of I.D.M.T. protection integral to the ACB? TemPower2 is available with a choice of flexible protection curves to assist in selectivity applications. S.I. Standard Inverse V.I. Very Inverse E.I. Extremely Inverse All these curves are user definable and comply with IEC 60255-3. Standard transformer and generator protection characteristics are also available. AGR-L Industrial & transformer protection AGR-S Generator protection AGR-R Characteristics to IEC 60255-3 Zone...

 Open the catalog to page 10
TemPower 2 ACB Catalogue-11

Double opening and closing coils Double Opening and Closing Coils provides extended control system redundancy to an ACB. Double coils allow designers to implement back-up tripping and closing systems. It provides the end user with ultimate reliability on critical UPS circuits connected to critical loads. Earthing Device The unique design of TemPower2 ACBs allows for the earthing of either the busbar (line) or the circuit (load) of a low voltage system. Thus allowing system flexibility. Some other manufactures only offer one option either, busbar or circuit earthing. For full details refer to...

 Open the catalog to page 11
TemPower 2 ACB Catalogue-12

1 Features Double Neutrals System harmonics, in the face of increasing triple-N harmonic currents Terasaki have launched a range of ACBs with double neutrals from 800 – 6300Amps – The ‘AR-DN’. Terasaki have the widest range of double rated neutral ACBs on the global market. TemCurve TemCurve Selectivity Analysis Software is shaped around the extensive range of Terasaki circuit breakers, but also includes a large number of complimentary protective devices such as High and Low Voltage Fuses to BS88/IEC60269, IDMT Relays to BS142/IEC60255. As a result, TemCurve can assist in protection device grading...

 Open the catalog to page 12

All Terasaki (Europe) Circuit Breaker catalogs and technical brochures

  1. Contactors

    16  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.