Moulded Case Circuit Breakers New TemBreak2
68Pages

{{requestButtons}}

Catalog excerpts

Moulded Case Circuit Breakers New TemBreak2 - 1

| Innovators in Protection Technology

Open the catalog to page 1
Moulded Case Circuit Breakers New TemBreak2 - 3

Molded Case Circuit Breakers 3. Ratings and operation data of auxiliary and (2) Breaker-mounted (field installable)(HB) (3) Door-mounted (depth adjustable) (HS) standard type •••3-16 (2) CR for rear-connected and plug-in breakers 4. Characteristics and Outline Dimensions

Open the catalog to page 3
Moulded Case Circuit Breakers New TemBreak2 - 4

FEATURES Saving space and saving money ! No.4 No.1 No.6 Compact size: W75 H130 D68; Operation in pollution degree 3 to IEC standard IP20 protection for the terminals and high breaking capacity: 40kA and IP30 protection for the front cover 415V (S160-SF/SJ) with toggle (with terminal covers) No.9 No.7 Two alarm Unique accessory switches can be cover opens with easily installed only one screw No.8 No.5 Practical internal Suitable for isolation accessories can with positive contact be installed with indication one touch • ayxiliary switch • alarm switch No.2 • shunt trip • undervoltage Huge...

Open the catalog to page 4
Moulded Case Circuit Breakers New TemBreak2 - 6

1 Ratings and Specifications Molded Case Circuit Breakers zFixed thermal and fixed magnetic MCCBs 100 DC 690V 500V 440V 415V 380V 240V 250V 125V 160 250 S160-SCF S160-SF E250-SF 3 1 2 3 4 2 10 15 20 30 40 AC 160 E160-SF 2 center pole omitted Rated insulation voltage Ui V Rated impulse withstand voltage U imp kV Utilization Category Rated breaking capacity, kA IEC60947-2 AC Icu/Ics(sym) 160 E100-SF Frame size (A) Type Number of poles Ratings Rated current, A Calibrated at 40°C 50 60 75 100 16 63 20 80 25 100 32 125 40 50 (45°C only) 15 20 30 40 50 60 15 20 30 40 50 60 75 100 125 160 125 150...

Open the catalog to page 6
Moulded Case Circuit Breakers New TemBreak2 - 7

1 Ratings and Specifications Molded Case Circuit Breakers xAdjustable thermal and adjustable magnetic MCCBs 160 160 S160-SJ E250-SJ 3 3 3 250 250 S160-SCJ Frame size (A) Type Number of poles Ratings Rated current, A Calibrated at 45°C 4 4 S250-SJ 4 3 Rated insulation voltage Ui V Rated impulse withstand voltage U imp kV Utilization Category Rated breaking capacity, kA IEC60947-2 AC Icu/Ics(sym) DC AC 690V 500V 440V 415V 380V 240V 250V 125V 25 40 63 80 100 125 160 100 125 160 200 250 690 8 A 690 8 A 800 8 A 800 8 A 7.5/4 15/7.5 25/13 25/13 35/18 20/10 30/15 6/3 10/7.5 25/13 40/20 40/20 50/25...

Open the catalog to page 7
Moulded Case Circuit Breakers New TemBreak2 - 8

1 Ratings and Specifications Molded Case Circuit Breakers cSwitch-disconnectors 160 V d b S250-SN 3 Rated short circuit making capacity, kA peak Rated short time withstand current, kA Rated impulse withstand voltage U imp kV Performance Utilization category AC IEC 60947-3 DC Upstream breaker (OCPD) @9 External dimensions, mm a 250 S160-SN Frame size (A) Type Number of poles Ratings Rated current, A Rated insulation voltage Ui Rated operational voltage V c AC AC DC 690V 250V a b c d 160 690 690 250 2.8 2 0.3sec 8 250 690 690 250 6 3 0.3sec 8 AC-23A DC-22A S160-SF AC-23A DC-22A S250-SF 75 130...

Open the catalog to page 8
Moulded Case Circuit Breakers New TemBreak2 - 10

2 Mounting and Connection Molded Case Circuit Breakers zType of connections and mountings List of connecting types Front-connected (FC) Connecting types (Abbreviation) For compression terminals / flat bars With extension bars Rear-connected (RC) With cable clamps Flat bar studs Stud can be turned 45° or 90° Outer view Breaker E100-SF ' E160-SF ' S160-SCF S160-SF ' S160-SCJ S160-SJ S160-SN ' E250-SF S250-SF E250-SJ S250-SJ S250-SN ' • Extension bars are attached • Connect compression to breaker terminals. terminals or flat bars directly Connect compression to breaker terminals. terminals or...

Open the catalog to page 10
Moulded Case Circuit Breakers New TemBreak2 - 12

Molded Case Circuit Breakers Front connected type (without extension bar) Front connected type (with extension bar) (D. Commercially made compression terminals can be used (refer to I JST : Made by Japan Solderless Terminal Manufacturing Co., Ltd. NTK : Made by Nippon Tanshi Co., Ltd. NTM : Made by Nichifu Terminal Industries Co., Ltd. MELEC : Made by Shanghai JiaMeng Electrical Equipment Co., Ltd. (D. Compression terminals in i i box cells are made by us at Terasaki. They are available from us or our authorized agents. (f). Compression terminals enclosed in parentheses are to be used as...

Open the catalog to page 12
Moulded Case Circuit Breakers New TemBreak2 - 13

Connection (two terminals) If a shortage of insulating occurs between the mounting plate and a terminal, use a recommended taping or insulator. 2 When a single terminal is connected Terasaki made compression terminals are used (refer to 60-2BA 80-3BA box) 100-3BA 18.0 22 2.6 2.3 2.0 Nominal size engraved If a shortage of insulating occurs, use a recommended taping or insulator. 22.3 +0.7 –0.5 If a shortage of insulating occurs, use a recommended typing or insulator. ➤ Make connection so that the screw heads face toward the mounting surface. 21.0 Connection (two electric cables) ➤ ⎛ ⎜ ⎜ ⎝...

Open the catalog to page 13
Moulded Case Circuit Breakers New TemBreak2 - 14

Molded Case Circuit Breakers 3 Terminal screw sizes and standard torques Wire clamping screw Pan head screw Hex socket head bolt

Open the catalog to page 14
Moulded Case Circuit Breakers New TemBreak2 - 15

2 Mounting and Connection Molded Case Circuit Breakers vInsulation distance from the line side The insulation distance between the breaker and earthed metal parts and insulators shown in the table on the next page must be maintained to prevent arcing faults occurring due to conductive ionised gas. In addition, completely cover exposed conductors, to their roots at the breaker or to below the height protected by interpole barriers, on the line side of the breaker using insulation tube or tape, in order to provide positive ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ protection against short...

Open the catalog to page 15
Moulded Case Circuit Breakers New TemBreak2 - 16

2 Mounting and Connection Molded Case Circuit Breakers vInsulation distance from the line side Insulation distance, mm (AC 460 V or less) Note q Molded Case Circuit Breakers 1 Breaker 2 E100-SF 30 10 10 ✽ Possible to set close 25 Not less than the length of the bare live part Note 3 E250-SF, E250-SJ 50 40 40 ✽ Possible to set close 50 Not less than the length of the bare live part Note 3 S160-SCF, S160-SF, S160-SCJ, S160-SJ 50 50 10 ✽ Possible to set close 25 Not less than the length of the bare live part Note 3 S250-SF, S250-SJ 50 50 40 ✽ Possible to set close 50 Not less than the length...

Open the catalog to page 16
Moulded Case Circuit Breakers New TemBreak2 - 17

(2) CR for rear-connected and plug-in breakers

Open the catalog to page 17
Moulded Case Circuit Breakers New TemBreak2 - 18

Molded Case Circuit Breakers 1 Internally mounted accessories 1. Connection diagrams and terminal numbers Combination symbol Connection diagram and terminal No. »With anti-burn switch Applicable to E100-SF. . Shunt trips are fitted with anti-burn switches »Without anti-burn switch Applicable to other breakres except E100- SF. Shunt trips are continuous rating without anti-burn switches. Nr*TRIP NrTRIP Molded Case Circuit Breakers Shunt trip |~~| CD: The two-pole type breaker obtained by modifying a three-pole breaker by removing the conductive part of its central pole is regarded as the...

Open the catalog to page 18

All Terasaki Electric Circuit Breaker catalogs and technical brochures

  1. WE500

    6 Pages

  2. GS50

    8 Pages

  3. APS 22

    2 Pages

  4. TERANET 50X

    4 Pages

  5. GAC21

    8 Pages

  6. HS21

    20 Pages

  7. MS22