Specifications OverviewThe document provides detailed specifications and standards for a specific product, with a disclaimer that specifications are subject to change without notice. It is printed on 100% recycled paper.
Standards and CertificationsThe product is certified with ISO9001 and ISO14001. It adheres to standards such as IEC60439, JEM1195, and NEMA ICS-2-322.
Service Conditions- Location: Suitable for both indoor and outdoor environments.
- Ambient Temperature: Indoor: -5 to +40°C, Outdoor: -25 to +40°C.
- Humidity: Indoor: 45-85%, Outdoor: 45-100%.
- Altitude: Maximum of 2000m.
- Anti-vibration Strength: JEM TR144 Class 1, with horizontal acceleration at 0.3G and vertical acceleration at 0.15G.
- Degree of Protection by Enclosure: Indoor: IP21/IP42, Outdoor: IP33W.
Electrical Specifications- Distribution System: Options for 3-phase 3-wire or 3-phase 4-wire systems.
- Rated Insulation Voltage: AC660V.
- Dielectric Withstand Voltage: AC2500V for 1 minute.
- Rated Frequency: 50Hz/60Hz.
- Main Bus-bar Current (Horizontal): Ranges from 1000A to 4000A.
- Main Bus-bar Current (Vertical): 800A.
- Rated Short-time Withstand Current: 50kA for 1 second, 65kA for 1 second.
- Applicable Motor Capacity (440V): Up to 132kW for withdrawable units, and above 132kW up to 200kW for fixed units.
Construction and Wiring- Enclosure Construction: Available in single or double face types.
- Wiring Systems: Configurations include B-B, B-C/C-B/C-C.
- Cable Entrance: Options for bottom cable or top cable/bus-duct entry.
- Control Voltage: Standard AC110V, with other specifications available upon request.
Contact InformationLocated at Nikko Kayabacho Building 5F, 1-6-10, Kayabacho, Nihonbashi, Chuo-ku, Tokyo 102-0025, Japan. Tel: +81-3-5644-0150, Fax: +81-3-5644-0155.