Smoke detector TSS8030R
4Pages

{{requestButtons}}

Catalog excerpts

Smoke detector TSS8030R - 1

Short description TSS8030R smoke detector is designed for early warning of a fire condition responding to fixed threshold smoke concentration detected in the protected premises. The smoke sensitivity is factory preset. The principle of functioning of the detector is based on infrared rays distraction caused by smoke particles entering the optic chamber. The fire detector is controlled by a microprocessor, operating on the basis of improved algorithm for self-compensation of the chamber contamination. Technical parameters LED indicators Both LED indicators (pos.3) allow range of visibility 360° and provide information for the status: - Duty mode - the LEDs are not lit; - Fire condition - the LEDs produce continuous light; - Contaminated chamber- the LEDs flash briefly every 1s.

Open the catalog to page 1
Smoke detector TSS8030R - 2

Installation The smoke detector consists of fire detector FD8000 and base with relay output 8000R. The fire detector (fig.1) consists of a printed circuit board and an optic chamber (pos.4), fixed in a plastic body (pos.5). TSS8030R can be used with controllers of series TCW1xx, TCW2XX and TCG1xx which have digital inputs in “dry contact” mode. Fore mode details see user manuals. The electrical connection is done according to the schematic below:

Open the catalog to page 2
Smoke detector TSS8030R - 3

It is recommended cable shoes to be used. The fire detector is placed on the base (fig.1,pos.1). It is rotated clockwise until reaching the guiding grooves (fig.1,pos.2). It is rotated until rest (fig.3.1). The slots of the base and the body should match (fig.3.2). Locking of the fire detector (fig.4). Before installation, the key (pos.3) is detached from the base and the rib (pos.1) of the locking click (pos.2) is cut out. Removing of a fire detector locked to the base. Insert the key into the slot (pos.4) push in as in the same time the fire detector is rotated anticlockwise. Remove the...

Open the catalog to page 3
Smoke detector TSS8030R - 4

1. Voltage is to the detector from controller or auxiliary power supply unit 24V DC/0,1A. 2. After one minute smoke detector should be activated using a Smoke Detector Tester. It should enter fire condition within 40s. 3. The supply voltage to the detector is interrupted within 2s. Smoke detector should enter duty mode and is ready for a new activation within 40s. Service schedule It is done by authorized personnel and includes the following activities: 1. Inspection for visible physical damage 2. Testing in real conditions 3.* Preventive cleaning of the optic chamber *The fire detector is...

Open the catalog to page 4

All Teracom catalogs and technical brochures

  1. TSV100

    2 Pages

  2. TDI340

    2 Pages

  3. TSA200

    2 Pages

  4. TSV200-60i

    2 Pages

  5. TSC200-15

    2 Pages

  6. TSH202v3

    2 Pages

  7. TST100

    2 Pages

  8. TST103

    2 Pages

  9. TCW181B-CM

    2 Pages

  10. TCW280

    2 Pages

  11. TCW220

    2 Pages

  12. TCW210-TH

    2 Pages

  13. TSP200

    2 Pages

  14. TSH206

    2 Pages

  15. TCW260

    2 Pages