S5M AC

S5M AC

S5M AC

Product catalog summary
Overview
The document provides detailed technical specifications, dimensions, accessories, and operational parameters for the S5M AC series of switch-disconnectors compliant with IEC 60947-3 standards. The series covers multiple sizes and current ratings from 125A up to 1000A, with configurations for 6-pole (6P) and 8-pole (8P) base mountings.

1. Product Range and Sizes
- Size 0: 125A, 160A, 200A
- Size 1: 250A, 315A, 400A
- Size 2: 500A, 630A
- Size 3: 800A, 1000A

2. Mechanical and Electrical Specifications
- Rated thermal current (Ith) varies by size and ambient temperature (40ºC to 60ºC).
- Rated insulation voltage (Ui): 1000 V for all sizes.
- Rated impulse withstand voltage (Uimp): 8 kV for sizes 0 and 1; 12 kV for sizes 2 and 3.
- AC rated operational current (Ie) at 400V for utilization categories AC21A, AC22A, and AC23A provided per size.
- Rated breaking and making capacities increase with size, e.g., 1000A size has breaking capacity up to 8000 A and making capacity up to 10000 A.
- Short-circuit making capacity (Icm) and short-time withstand current (Icw) specified, e.g., 13 kA peak and 7 kA rms for size 0, up to 60 kA peak and 25 kA rms for size 3.
- Mechanical endurance ranges from 3000 to 8000 cycles depending on size.

3. Dimensions and Mounting
- Detailed dimensions for mounting holes, shaft lengths, and handle door drilling are provided.
- Shaft lengths (L) and pitch (P) vary by size, e.g., size 0 shafts range from 155 to 263 mm, size 3 shafts from 408 to 573 mm.
- Terminal connection parameters include maximum cross-sectional area (S max), height (H max), length (L max), and torque (M) for copper conductors.

4. Accessories
- Handles: Direct handle, external handle with shaft (IP65 rated), emergency external handle.
- Auxiliary contacts: 1NO+1NC and 2NO+2NC rated at 16 A resistive and 4 A inductive at 250 Vac.
- Safety key lock devices: Simple and double versions allowing handle locking in OFF (or optionally ON) position with key removal only when locked.
- Terminal shrouds and phase barriers available for input/output protection; noted incompatibilities between certain accessories.

5. Installation and Safety Features
- Door drilling templates for handle and key lock devices are specified.
- Handles and shafts are included or available as separate codes.
- IP65 rating for external handles ensures protection against dust and water ingress.

6. Short-Circuit and Operational Performance
- Short-circuit making and withstand capacities are specified without limiting protective devices, assuming short-circuit duration of 50 to 100 ms.
- Rated breaking and making capacities are given for AC23 utilization category at 400 V.

7. Weight and Mechanical Data
- Maximum weights for 6P and 8P versions are listed per size, ranging from approximately 1.8 kg (size 0) to 20 kg (size 3).
- Mechanical operation cycles indicate durability and reliability under standard conditions.

Summary of Critical Parameters by Size
SizeRated Current (A)Icm (kA peak)Icw (kA rms)Breaking Capacity (A)Making Capacity (A)Mechanical CyclesWeight 6P (kg)
0125,160,2001371000-12801250-160080001.8-1.9
1250,315,40020122000-32002500-40005000-80005.5-5.8
2500,63026164000-50005000-6300500012.3-13
3800,100060256400-80008000-10000300018.5-20

Conclusion
The S5M AC series switch-disconnectors offer a comprehensive range of sizes and current ratings suitable for industrial electrical installations requiring reliable switching and disconnection functions. The devices comply with IEC 60947-3, provide robust mechanical endurance, high short-circuit withstand capabilities, and include a variety of accessories for enhanced safety and operational flexibility. Installation dimensions and accessory compatibility are clearly defined to facilitate integration into electrical panels.
See more

Catalog excerpts

S5M AC-1

Switch - disconnector base mounting 6P - 8P Direct handle CODE External handle (For frontal switch only) Emergency external handle (1 kit for input or output) *(T) These accessories aren’t compatible with each other. Safety key lock devices Simple CODE DS-CAB1 Double CODE DS-CEB1 For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Standard shaft included *(e1) Door drilling for handle and key lock device Simple Double ,5 Ie = 16 A (resistive loads) 4 A (inductive loads) at 250 Vac. Short - circuit behaviour Rated short-circuit making capacity *(2) Rated short-time withstand current (1sec.) Icw kA rms Mechanical features Door drilling for external handle Rated insulation voltage Rated impulse withstand voltage AC rated operational current *(1) (Rated operational frequency 50 / 60 Hz) Rated breaking capacity Rated making capacity *(1) Other voltages and / or utilization categories. Please consult *(2) Without limiting protective device (short-circuit maintained 50... 100 ms.) Number of mechanical operations (according to the standards, for other values please consult) 125 Rated thermal current Ith 40 ºC in ambient at 50 ºC Technical information CODE CODE Auxiliary contacts

 Open the catalog to page 1
S5M AC-2

Switch - disconnector base mounting 6P - 8P Direct handle CODE DS-CU11 (1 kit for input or output only frontal side) External handle without shaft Emergency external handle Safety key lock devices Simple CODE DS-CB12 Double CODE DS-CF11 For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Door drilling for handle and key lock device Simple Double Standard shaft included *(e1) Technical information (1 kit for input or output) *(T) These accessories aren’t compatible with each other. Rated short-circuit...

 Open the catalog to page 2
S5M AC-3

Switch - disconnector base mounting 6P - 8P Direct handle CODE (1 kit for input or output only frontal side) External handle Emergency external handle S5M05006PR0 S5M05008PR0 Safety key lock devices Simple CODE DS-CB21 Double CODE DS-CF21 For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Standard shaft included *(e1) L (mm) Door drilling for handle and key lock device Simple Double (1 kit for input or output) *(T) These accessories aren’t compatible with each other. Ie = 16 A (resistive loads)...

 Open the catalog to page 3
S5M AC-4

Switch - disconnector base mounting 6P - 8P Terminal shrouds *(T) CODE DS-CU31 (1 kit for input or output only frontal side) Direct handle CODE External handle (1 kit for input or output) *(T) These accessories aren’t compatible with each other. External handle without shaft Safety key lock devices Simple CODE DS-CB41 Double CODE DS-CF41 For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Door drilling for handle and key lock device Simple Double Rated thermal current Ith 40 ºC in ambient at 50 ºC...

 Open the catalog to page 4

All Telergon catalogs and technical brochures

  1. ATS

    8  Pages

  2. S5M DC

    3  Pages

  3. S6R DC

    2  Pages

  4. S6N DC

    2  Pages

  5. S6 DC

    4  Pages

  6. S5 DC

    5  Pages

  7. CIF22

    2  Pages

  8. series CTR

    7  Pages

  9. CCF CCP

    3  Pages

  10. S5F

    6  Pages

  11. CEC series

    2  Pages

  12. S6N AC

    2  Pages

  13. S6 AC

    2  Pages

  14. S5 AC

    9  Pages

  15. ZBK

    4  Pages

  16. CITA

    4  Pages

  17. CITP CTFR

    3  Pages

  18. TP T TB TF

    8  Pages

  19. Cam switches

    17  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.