CCF CCP

CCF CCP

CCF CCP

Product catalog summary

Overview

This document provides detailed technical specifications, dimensions, accessories, and operational characteristics for a range of changeover switches compliant with IEC 60947-3 standards. The switches are designed for base mounting in 3-pole (3P) and 3-pole plus neutral (3P+N) configurations, covering rated currents from 200A up to 1250A.

Product Series and Models

The changeover switches are categorized by current ratings and sizes:

  • Size 1: 200A, 250A, 315A, 400A
  • Size 2: 500A, 630A, 800A
  • Size 3: 1000A, 1250A

Each size includes models with different pole configurations (3P and 3P+N) and types (CCF and CCP).

Electrical Ratings and Performance

  • Rated Thermal Current (Ith): Ranges from 200A to 1250A depending on size.
  • Rated Insulation Voltage (Ui): 1000 V across all models.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV for sizes 1, 12 kV for sizes 2 and 3.
  • Rated Operational Current (Ie) at 400V AC: Matches the thermal current rating for AC21A and AC22B utilization categories.
  • Rated Breaking and Making Capacity (AC22): Varies by size, e.g., 600-1200 A for size 1, 1500-2400 A for size 2, and 3000-3750 A for size 3.
  • Short-Circuit Making Capacity (Icm): 12 kA peak for size 1, 20 kA for size 2, and 32 kA for size 3.
  • Short-Time Withstand Current (Icw) 1 sec: 8 kA rms for size 1, 13 kA rms for size 2, and 25 kA rms for size 3.
  • Mechanical Operations: Between 3000 and 8000 cycles depending on size and model.

Mechanical and Dimensional Data

  • Dimensions and mounting details are provided for door drilling for external handles and key lock devices.
  • Terminal shrouds and rear protective plates are available for 3P and 4P configurations.
  • Shafts and shaft extensions are included or available as accessories, with detailed length and pitch dimensions.
  • Maximum conductor cross-section (Cu) and terminal screw sizes (M) are specified per model.
  • Weights vary by size and model, ranging from approximately 4.8 kg to 29.7 kg.

Accessories and Options

  • Auxiliary Contacts: 1NO+1NC (Code D5LAU01) and 2NO+2NC (Code D5LAU02), rated 16 A resistive and 4 A inductive at 250 Vac.
  • Safety Key Lock Devices: Simple and double versions available to lock the handle in OFF position (or ON on request), with key removal only possible when locked.
  • Handles: Direct handle (Code DCCLIxx) and external handle with shaft included (IP65 rated, Code DCCLAxx).
  • Terminal Shrouds and Rear Protective Plates: Various codes for 3P and 4P versions to enhance safety and installation flexibility.

Special Versions and Notes

  • Versions without OFF (0) position are available, featuring overlapped contacts (CCF I - I+II - II), designated as CCS series; consultation required.
  • 4-pole changeover switches are available upon request.
  • Short-circuit ratings are given without limiting protective devices, assuming short-circuit duration between 50 ms and 100 ms.
  • For other voltages or utilization categories, consultation with the manufacturer is recommended.

Standards Compliance

All changeover switches comply with IEC 60947-3, ensuring adherence to international standards for low-voltage switchgear and controlgear.

Summary

This document serves as a comprehensive technical reference for selecting and installing changeover switches across a wide range of current ratings and configurations. It includes critical electrical and mechanical parameters, accessory options, and safety features to support proper application and compliance with relevant standards.

See more

Catalog excerpts

CCF CCP-1

CHANGEOVER SWITCHES I-O-II CHANGEOVER SWITCHES I-O-II Changeover switch base mounting 3P - 3P+N Direct handle Terminal shrouds Common output External handle Auxiliary contacts Standard shaft included *(e1) L (mm) Simple CODE D5LCB11 Double CODE D5LCF11 Shaft extensions For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Safety key lock device Door drilling for handle and key lock device Simple Double Technical information Rear protective plate consult Rated breaking capacity Rated making capacity Short - circuit behaviour Rated impulse withstand voltage AC Rated operational current *(1) (Rated operational frequency 50 / 60 Hz) Ie = 16 A (resistive loads) 4 A (inductive loads) at 250 Vac. CODE CODE * Other voltages and / or utilization categories; please consult *(2) Without limiting protective device (short - circuit maintained 50 ms. - 100 ms.) *(3) AC22B Maximum weight (3/4 poles) Also available 4P changeover switches under request, please consult There are versions of changeover switches without OFF 0 position: “overlapped contacts”: CCF (I - I+II - II) = CCS _ _ _ _ _ _ _ _, please consult Door drilling for external handle Number of mechanical operations (according to the standards, for other values please consult) *(3) Short - time withstand current (1 sec.) Icw Short - circuit making capacity *(2) Rated insulation voltage Rated thermal current Ith in ambient at 40º C

 Open the catalog to page 1
CCF CCP-2

CHANGEOVER SWITCHES I-O-II CHANGEOVER SWITCHES I-O-II Changeover switch base mounting 3P - 3P+N Direct handle Terminal shrouds Common output External handle Auxiliary contacts Standard shaft included *(e1) L (mm) Simple CODE D5LCB21 Double CODE D5LCF21 Shaft extensions For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Safety key lock device Door drilling for handle and key lock device Simple Double Technical information Rear protective plate consult Rated breaking capacity Rated making capacity...

 Open the catalog to page 2
CCF CCP-3

CHANGEOVER SWITCHES I-O-II CHANGEOVER SWITCHES I-O-II Terminal shrouds External handle For external handle, lock the handle by means of a key in position “OFF” (under request, in “ON”), the key can only be removed with the handle locked Shaft extensions Door drilling for handle and key lock device Simple Double Simple CODE D5LCB31 Double CODE D5LCF31 Safety key lock device Standard shaft included *(e1) Ie = 16 A (resistive loads) 4 A (inductive loads) at 250 Vac. Technical information Rear protective plate 3P Rated breaking capacity Rated making capacity Rated insulation voltage Short - circuit...

 Open the catalog to page 3

All Telergon catalogs and technical brochures

  1. ATS

    8  Pages

  2. S5M DC

    3  Pages

  3. S6R DC

    2  Pages

  4. S6N DC

    2  Pages

  5. S6 DC

    4  Pages

  6. S5 DC

    5  Pages

  7. CIF22

    2  Pages

  8. series CTR

    7  Pages

  9. S5F

    6  Pages

  10. CEC series

    2  Pages

  11. S6N AC

    2  Pages

  12. S5M AC

    4  Pages

  13. S6 AC

    2  Pages

  14. S5 AC

    9  Pages

  15. ZBK

    4  Pages

  16. CITA

    4  Pages

  17. CITP CTFR

    3  Pages

  18. TP T TB TF

    8  Pages

  19. Cam switches

    17  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.