2020 TELE Catalog USA
40Pages

{{requestButtons}}

Catalog excerpts

2020 TELE Catalog USA - 2

Made in Austria TELE Haase Steuergeraete GesmbH PAST TELE Haase Steuergeraete is an Austrian based, family owned technology company that is passionate about hiring the best in the business to develop and manufacture control and monitoring solutions for both, the energy and industrial sector. Founded in 1963, TELE Haase has been a market leader for time and monitoring relays and has been developing customized solutions and components for the industrial and energy sectors for more than five decades. PRESENT TELE products are being used the world over and are most often used in control...

Open the catalog to page 2
2020 TELE Catalog USA - 3

Serving the USA TELE Controls Inc. All of TELE Haase’s industrial electronic technology products are developed and manufactured in Vienna, Austria. Our products are designed to protect, monitor and automate systems for a wide range of industries. Since 2018, TELE Controls Inc. has been based out of Arlington, Virginia, fulfilling and exceeding the local sourcing needs of OEMs to resellers, and distributors all throughout North America. We are able to provide excellent on-demand project support as well as personal sales assistance. Headquartered in Vienna, Austria Offices in the UK and USA...

Open the catalog to page 3
2020 TELE Catalog USA - 4

Time Delay RelaysMonitoring Relays Power Meters ■ Single Function Timers ■ ON and OFF delay ■ Multi-Function Timers ■ Timer Modules for Industrial Switching Relays ■ Star-Delta Timers ■ Digital Timers ■ Staircase Timers ■ Impulse Encoders ■ Alternating Function Timers ■ Pump/Load Alternators ■ Phase Failure/Loss ■ Phase Sequence ■ Phase Unbalance/Asymmetry ■ Voltage up to 900V AC ■ Current up to 100A AC/DC direct or higher via external CTs ■ Effective Frequency from 40-70Hz ■ Temperature via PTC, NTC or PT100 ■ Conductive Liquid Level ■ 1~ Power Meter up to 50A and 1000V with ModbusRTU...

Open the catalog to page 4
2020 TELE Catalog USA - 5

Marking area Product standards Energy consumption Electrical connection Overvoltage category 0.88 / 1.76 x 2.64 x 2.99 in (22.5 / 45 x 67 x 76 mm) Compact Industrial Design 0.88 / 1.76 x 3.54 x 4.25 in (22.5 / 45 ^ 90 x 108 mm) Advanced Industrial Design Screw Terminals Screw or Push-In Terminals Screw Terminals

Open the catalog to page 5
2020 TELE Catalog USA - 6

- Economical design - Time delay and monitoring relays - Single and Multifunction versions - Fully adjustable - SPDT or DPDT outputs - Operating temeperature -13 to + 131°F (-25 to +55°C) - LED indicators - 12 to 240V AC/DC, power supply - cULus listed - CE compliant - RoHs compliant - Compact industrial design - Time delay and monitoring relays - Single and multifunction versions - Fully adjustable - SPDT or DPDT outputs - Low profile - Extra efficient - Operating temperature -13 to + 140°F (-25 to +60°C) - LED indicators - 12 to 240V AC/DC, power supply - cULus listed - CE compliant -...

Open the catalog to page 6
2020 TELE Catalog USA - 7

El ZM10 12-240 VAC/DC Extra compact and multifunctional time delay relay for operating voltages from 12-240V AC/DC. See page 12 Timer Module COM3T Transform your regular switching relay into a multifunctional super time delay relay and contactor. See page 33 V4PF480Y/277VSY02 The ultimate motor protection: Phase and temperature monitor in one compact device. See page 22 G4BM480V12ADTL20 The real power monitor that does not require software skills for set-up. See page 27

Open the catalog to page 7
2020 TELE Catalog USA - 8

Functions time delay relays Function Overview Time Delay RelaysOur Functions In DetaiE ON DELAY When the supply voltage U is applied, the set interval t begins. After the interval t has expired the output relay R switches into on-position. This status remains until the supply voltage is interrupted. If the supply voltage is interrupted before the expiry of the set interval, the interval t already expired is erased and is restarted when the supply voltage is next applied. When the supply voltage U is supplied, the output relay R swiches into on-position. If the supply voltage is interrupted,...

Open the catalog to page 8
2020 TELE Catalog USA - 9

Functions time delay relays When the supply voltage U is applied, the set interval t1 begins. After the interval t1 has expired, the output relay R switches into on-position and the set interval t2 begins. After the interval t2 has expired, the output relay switches into off-position. If the supply voltage is interrupted before the interval t1+t2 has expired, the interval already expired is erased and is restarted when the supply voltage is next applied. nWu MAINTAINED SINGLE SHOT LEADING EDGE When the supply voltage U is applied, the output relay R switches into on-position and the set...

Open the catalog to page 9
2020 TELE Catalog USA - 10

Functions time delay relays The supply voltage U must be constantly applied to the device. When the control contact S is closed, the set interval t1 begins. After the interval t1 has expired, the output relay R switches into on-position and the set interval t2 begins. After the interval t2 has expired, the output relay switches into offposition. During the interval, the control contact can be operated any number of times. A further cycle can only be started when the cycle run has been completed. The supply voltage U must be constantly applied to the device. Closing the control contact S has...

Open the catalog to page 10
2020 TELE Catalog USA - 11

Functions time delay relays Wt PULSE SEQUENCE MONITORING When the supply voltage U is applied, the set interval t1 begins and the output relay R switches into on-position. After the interval t1 has expired, the set interval t2 begins. So that the output relay R remains in on-position, the control contact S must be closed and opened again within the set interval t2. If this does not happen, the output relay R switches into off-position and all further pulses at the control contact are ignored. To restart the function the supply voltage must be interrupted and reapplied. ASYMMETRIC FLASHER...

Open the catalog to page 11
2020 TELE Catalog USA - 12

Our 3in1 pump alternating relay offers the most capability in the industry's most compact and space-saving DIN-Rail enclosure style. TELE's duplexer controls two loads simultaneously while enhancing the regular alternating function through integrated ON and OFF Delay functionality. The selector switch allows the user to lock in one sequence while the relay works with a wide range control voltage of 24 - 240V AC/DC. Our E1ZMLA is commonly used in special applications where the optimization of load usage is required by equalizing the run time of two loads. Identical loads are used for the...