4 ZONES CONVENTIONAL FIRE ALARM PANELS General Feature Technical Specifications Ÿ Used with only 1 piece of 12V 7Ah battery Ÿ Battery requirement: 1 piece of 12V 7Ah Ÿ Seperate status, alarm and trouble LEDs Ÿ EOL supervised siren output and zone inputs by end of line resistor Ÿ Zone test feature Ÿ 12V/24V selectable, automatic fuse protected auxilary power output Ÿ NC/NO fire relay Ÿ NC/NO trouble relay Ÿ Requested zones can be bypassed Ÿ Key lock system against unwanted intervention Ÿ Easy to understand front panel Ÿ Intelligent battery charging system to prolong battery life Ÿ SMD material technology Ÿ Metal box Ÿ Power output: 12/24V DC, 0.5A automatic fuse protected Ÿ Siren output: 24V DC, 6.8kOhm end of line resistor Ÿ Fire relay: 30V 1A NC/NO dry contact Ÿ Trouble relay: 30V 1A NC/NO dry contact Ÿ Key lock Ÿ Humidity: %98 RH (maximum) Ÿ Temperature: -10°C ~ 55°C (14°F ~ 131°F) Ÿ Dimensions: 210 x 300 x 80mm Ÿ Weight: 2.5 kg