TFD-13XX SERIES CONVENTIONAL FIRE DEDECTORS Ÿ wires to use with fire alarm panels. 2 Ÿ Remote indicator function. Ÿ Plugged contact structure to prevent Ÿ Stylish, fireproof plastic ABS body. intermittent contact. (Figure 1-b) Ÿ Microprocessor design: High Ÿ LEDs, visible from every angle. Flash in 2 electromagnetic immunity, does not allow false alarms, not affected by light sources such as florescence, etc. Ÿ Adaptive threshold: Prevents false alarms each 10 seconds to show that it is working. Ÿ Compatible with EN 54-7. Ÿ Dimensions: ɸ:110mm, h:50mm Ÿ Weight: 198g. that occur due to dust.
Open the catalog to page 1TFD-13XX SERIES CONVENTIONAL FIRE DEDECTORS Technical specifications WORKING PRINCIPLES Detection Optical Sampling Frequency 3 seconds ELECTRICAL SPECIFICATIONS Operating voltage 10-30V DC Operating wire 2 wires Average operating current 60µA Alarm Current 35mA MECHANICAL SPECIFICATIONS Material Fireproof ABS Alarm LED 2 pieces Dimensions Ø:110mm, h:50mm Weight 198g. ENVIRONMENTAL SPECIFICATIONS Temperature -10ºC ~ +55ºC Ÿ TFD-1350 Optical Smoke + Heat Multisensor Detector o 57°C heat and visible smoke. o 35mA maximum alarm current. Ÿ TFD-1332 Optical Smoke Detector 2 o Detection Area: 60m (4m....