Overview: This document provides comprehensive details on Teknim's Intelligent Addressable Fire Alarm Systems, specifically the TFP-1211, TFP-1212, and TFP-1214 models. These systems use the proprietary FLASHLINK protocol for loop communication and are designed to function reliably in harsh environments, complying with European Standards EN54-2 and EN54-4.
TFP-1211 Features: The TFP-1211 supports 1 loop with up to 240 devices, network capability for up to 16 control panels, and includes a 240x64 LCD graphic display. It supports up to 72 zones and cable distances up to 2.5 km per loop, with advanced programming via TFY-1000 software, multiple language support, and customizable display. It can log up to 12,000 events of alarms, errors, and warnings.
TFP-1212 Features: This model supports 2 loops with up to 480 devices in total, maintaining similar network and display features as the TFP-1211, with enhanced device support and zone management.
TFP-1214 Features: The TFP-1214 supports 4 loops with up to 508 devices in total, designed for larger installations with more extensive device support, while maintaining user-friendly interface and network capabilities.
Technical Specifications: The systems operate within a temperature range of -10°C to 55°C, with humidity tolerance up to 95% RH, and have a protection class of IP30. They require a power supply of 230/110 VAC with a 6A fuse and offer battery backup options.
Additional Components: The TFP-1240 Repeater Panel allows remote monitoring and control up to 1 km from the main panel. The TFC-1209 Network Module facilitates network connections among panels using the TdNET protocol, supporting Class A and B connections with a built-in isolator for network protection.
Conclusion: Teknim's fire alarm systems provide robust, scalable solutions for various installation sizes, with advanced networking capabilities and user-friendly interfaces, ensuring reliable fire detection and alarm management.
Technical Specifications and Features Overview:
TFC-1209 Protocol and Connectivity: The TFC-1209 uses the TdNET (RS-485) protocol with a maximum cable distance of 1,000 meters, supporting up to 16 control panel connections and includes a built-in isolator. It operates at an average consumption of 50mA at 24V, with dimensions of 61 x 110 mm, and functions within a temperature range of -10°C to 55°C.
TFC-1201 Loop Board: Communicates with addressable devices using the FlashLink protocol, supporting up to 240 devices, with Class A and Class B connection support. It operates within a power range of 18V to 30V and an average consumption of 65mA at 24V.
TFCM-1801 Device Programmer: This module allows for fast and easy programming of Teknim addressable devices, featuring a "Memorize" function to prevent double address errors, operating on a 9V battery.
TFY-1000 Configuration Software: Facilitates the configuration of Teknim addressable control panels, offering offline project design, scenario creation, and event log backup, supporting TCP/IP communication.
MOSAIC-2000 Monitoring Software: A web-based software providing graphical monitoring for Teknim fire alarm systems, supporting up to 16 control panels with features like pop-up alarms and remote command sending.
Detectors: The TFD-1251 and TFD-1250 Smoke Detectors use optical sensing technology and the FlashLink protocol, certified under EN54-7 and EN54-17. The TFD-1261 and TFD-1260 Heat Detectors support fixed heat and heat rise modes, certified under EN54-5 and EN54-17. The TFD-1271 and TFD-1270 Multi Detectors combine optical and heat detection technologies, certified under EN54-7, EN54-5, and EN54-17.
Other Components: The TFA-1196 Remote Indicator features a large red LED for visibility. The TFM-128X Detector Bases support various configurations with LED indicators. The TFD-1170 Natural Gas Detector includes an 85dB buzzer and LED indicators. The TFB-1166 Manual Call Point complies with EN54-11 and EN54-17, featuring dual LEDs for local alarms.
General Features: All devices are designed with UL94 non-flammable materials, offering various protection classes (IP21C, IP30), and operate within a temperature range of -10°C to 55°C, with humidity tolerance up to 95% RH.
See more

Catalog excerpts

ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-1

INTELLIGENT ADDRESSABLE ADRESLİ YANGIN ALARM FIRE ALARM SYSTEM SİSTEMLERİ

 Open the catalog to page 1
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-2

1 Loop Intelligent Addressable Fire Alarm Panel TFP-1211 Intelligent Addressable Fire Alarm Panel uses unique FLASHLINK protocol for loop communication which created by Teknim engineers. Supports 1 loop, 240 devices and network up to 16 control panels. It offers stable and reliable solutions for working in harsh environments. TFP-12XX Fire Alarm Panels are designed in accordance with European Standards which supports EN54-2 and EN54-4 Certificates. TFP-1211 comes with an LCD graphic display onboard to easily understand the error and alarm warnings and to make all the settings of the device. TFP-1211...

 Open the catalog to page 2
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-3

1 Loop Intelligent Addressable Fire Alarm Panel GENERAL FEATURES • EN 54-2 and EN 54-4 Certified • Technician and user friendly; easy to install, programming and operation • Supports 1 Loop Capacity • Supports 240 Devices per Loop • Supports up to 72 Zone • Cable distance up to 2,5 Km per loop • Network up to 16 Control panels via RS-485 by TFC-1209 Network Module • Up to 3.480 devices and 1.152 zones by network (Using optional TFC-1209 Network module) • Easy to read, 240*64 wide LCD graphic display and user-friendly interface • Display customize with company logo, contact information, images,...

 Open the catalog to page 3
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-4

1 Loop Intelligent Addressable Fire Alarm Panel Technical Specifection Ethernet (TCP/IP) Multiple Language Display Programming YES (Onboard) Yes 240x64 LCD Through Control Panel or via TFY-100 Software Loop Information Loop Number of Devices Supports Per Loop Total Device Support Cable Distance Network Protocol Max. Panel Network TdNET (RS-485) 16 (TFC-1209 Network Card Needed) Mechanical Dimensions (mm) Body Material and Color Options Weight 385 x 380 x 130 mm Metal Light Grey – TFP-1211 / Red – TFP-1211R 6,5Kg (Without Battery) Environmental Operating Temperature Humidity Protection Class Power...

 Open the catalog to page 4
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-5

2 Loop Intelligent Addressable Fire Alarm Panel TFP-1212 Intelligent Addressable Fire Alarm Panel uses unique FLASHLINK protocol for loop communication which created by Teknim engineers. Supports 2 loop, 240 devices per loop and network up to 16 control panels. It offers stable and reliable solutions for working in harsh environments. TFP-12XX Fire Alarm Panels are designed in accordance with European Standards which supports EN54-2 and EN54-4 Certificates. TFP-1212 comes with an LCD graphic display onboard to easily understand the error and alarm warnings and to make all the settings of the...

 Open the catalog to page 5
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-6

2 Loop Intelligent Addressable Fire Alarm Panel GENERAL FEATURES • EN 54-2 and EN 54-4 Certified • Technician and user friendly; easy to install, programming and operation • Supports 2 Loop • Supports 240 Devices per Loop and totally 480 Devices in a single Panel • Supports up to 72 Zone • Cable distance up to 2,5 Km per loop • Network up to 16 Control panels via RS-485 by TFC-1209 Network Module • Up to 7.680 devices and 1.152 zones by network (Using optional TFC-1209 Network module) • Easy to read, 240*64 wide LCD graphic display and user-friendly interface • Display customize with company...

 Open the catalog to page 6
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-7

2 Loop Intelligent Addressable Fire Alarm Panel Technical Specifications Ethernet (TCP/IP) Multiple Language Display Programming 240x64 LCD Through Control Panel or via TFY-100 Software Loop Information Loop Number of Devices Supports Per Loop Total Device Support Cable Distance Network Protocol Max. Panel Network TdNET (RS-485) 16 (TFC-1209 Network Card Needed) Mechanical Dimensions (mm) Body Material and Color Options Weight 385 x 380 x 130 mm Metal Light Grey – TFP-1212 Red – TFP-1212R 6,5Kg (Without Battery) Environmental Operating Temperature Humidity Protection Class Power Power Frequency...

 Open the catalog to page 7
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-8

4 Loop Intelligent Addressable Fire Alarm Panel TFP-1214 Intelligent Addressable Fire Alarm Panel uses unique FLASHLINK protocol for loop communication which created by Teknim engineers. Supports 4 loop, 127 devices per loop and network up to 16 control panels. It offers stable and reliable solutions for working in harsh environments. TFP-12XX Fire Alarm Panels are designed in accordance with European Standards which supports EN54-2 and EN54-4 Certificates. TFP-1214 comes with an LCD graphic display onboard to easily understand the error and alarm warnings and to make all the settings of the...

 Open the catalog to page 8
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-9

4 Loop Intelligent Addressable Fire Alarm Panel GENERAL FEATURES • EN 54-2 and EN 54-4 Certified • Technician and user friendly; easy to install, programming and operation • Supports 4 Loop • Supports 127 Devices per Loop and totally 508 Devices in a single Panel • Supports up to 72 Zone • Cable distance up to 2,5 Km per loop • Network up to 16 Control panels via RS-485 by TFC-1209 Network Module • Up to 8.128 devices and 1.152 zones by network (Using optional TFC-1209 Network module) • Easy to read, 240*64 wide LCD graphic display and user-friendly interface • Display customize with company...

 Open the catalog to page 9
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-10

4 Loop Intelligent Addressable Fire Alarm Panel Technical Specifications Ethernet (TCP/IP) Multiple Language Display Programming YES (Onboard) Yes 240x64 LCD Through Control Panel or via TFY-100 Software Loop Information Loop Number of Devices Supports Per Loop Total Device Support Cable Distance Network Protocol Max. Panel Network Yes 16 (TFC-1209 Network Card Needed) Mechanical Dimensions (mm) Body Material and Color Options Weight 385 x 380 x 130 mm Metal Light Grey – TFP-1214 Red – TFP-1214R 6,5 Kg Environmental Operating Temperature Humidity Protection Class Power Power Frequency Fuse Battery...

 Open the catalog to page 10
ADRESLİ YANGIN ALARM SİSTEMLERİ INTELLIGENT ADDRESSABLE FIRE ALARM SYSTEM-11

TFP-1211, TFP-1212, TFP-1214 Intelligent Addressable Fire Alarm Panel Technical Specifications General Ethernet (TCP/IP) Multi Language Support Through Control Panel or Via TFY-1000 Configuration Software Through Control Panel or Via TFY-1000 Configuration Software Through Control Panel or Via TFY-1000 Configuration Software Display Programlama Printer Support Number of Devices Supports Per Loop Total Device Support 16 (TFC-1209 Network Card Needed) 16 (TFC-1209 Network Card Needed) 16 (TFC-1209 Network Card Needed) Metal Light Grey – TFP-1211 Red – TFP-1211R Metal Light Grey – TFP-1211 Red –...

 Open the catalog to page 11

All TEKNIM ELEKTRONIK AŞ. catalogs and technical brochures

  1. PRODUCT CATALOG

    72  Pages

  2. TFS-301

    1  Page

  3. VAP-408P

    4  Pages

  4. VPC-104

    1  Page

  5. ATP-570

    1  Page

  6. VPC-108G

    1  Page

  7. VAP-408M

    4  Pages

  8. TFP-908

    2  Pages

  9. TRM-904

    1  Page

  10. VAV-210

    1  Page

  11. TFD-1530

    1  Page

  12. VAS-740F

    1  Page

  13. VAS-720RP

    1  Page

  14. VPC-116 G

    1  Page

  15. ATP-540P

    2  Pages

  16. VAS-740B

    1  Page

  17. VAP-304M

    3  Pages

  18. VAP-404M

    4  Pages

  19. VAP-304P SET

    3  Pages

  20. TFP-804

    1  Page

  21. ATP-540N

    2  Pages

  22. VAP-416

    4  Pages

  23. VPL-USB

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.