Overview: The Series 5-1782-0-* density switches are pressure switches designed for monitoring SF6 gas pressure in medium voltage switchgears. They feature double level temperature compensation, allowing for the management of two pressure levels: an alert level for gas filling and an emergency protection level.
Requirements: The switchgear must have a pressure connection with a 1/4” BSP male thread to accommodate the density switch. A manifold basis is used to monitor pressure across all poles of the switchgear with a single switch.
Features: The density switch maintains functionality in adverse environmental conditions, with stable settings despite temperature and pressure changes. It is suitable for environments with varying temperatures and altitudes.
Functioning Scheme: The device consists of a pressure-sensitive element with two bellows, one exposed to gas and the other to atmospheric pressure. Two microswitches are positioned between these elements to detect pressure changes.
Principle of Functioning: The pressure-sensitive element is in contact with atmospheric pressure, making the device insensitive to environmental variations. The system uses a high sensitivity bellow that expands with gas pressure, triggering two microswitches for alert and alarm levels.
Overall Dimensions: The pressure switch is fixed using a 1/4” BSP female thread and features a nitrile rubber gasket. The device is made of stainless steel and anodized aluminum, with an IP 54 protection class.
Technical Data:
Double level density switch for gas
Open the catalog to page 1The density switches of series 5-1782-0-* are substantially pressure switches with double level temperature compensated, engineered to keep under control the pressure of SF6 gas inside middle voltage switchgears. These density switches are double switching level type and are therefore suitable for the monitoring of two different levels of pressure. This feature allows to manage a first alert level under which to foresee a gas filling up inside the switchgear, and a second intervention level over which the switchgear is put in emergency protection. The switchgear must also be provided of a pressure...
Open the catalog to page 2Thanks to its structural features, this density switch grants the correct functioning of the device even in particularly unfavourable environment conditions, keeping the setting parameters practically unchanged independently from the temperature and pressure variations. This device is therefore suitable for use in environments with extremely different temperature ranges and/or high altimetry. Functioning scheme The image represents the functioning diagram of the pressure switches of series 5-1782-0-*. The left part represents the area in contact with gas, the central part represents the microswitches...
Open the catalog to page 3Principle of functioning This density switch is characterized by an element sensible to pressure which is placed in contact to the gas section of the circuit to be monitored, it is composed of one bellow rigidly connected to a second bellow exposed to atmosphere pressure. The two microswitches of the device are positioned between the two elements sensible to pressure. Placing the sensible element in contact to atmospheric pressure renders the device insensitive to variations of both temperature and environment pressure, allowing the reading of the switching pressures at absolute level. Functioning...
Open the catalog to page 4Overall dimensions The figure represents the outer view with the overall dimensions of the pressure switch code 5-1782-0-*. The device is fixed to the host structure by means of a thread 1/4” BSP female, obtained on the lower side of the device. On the same side an OR gasket in nitrile rubber is assembled for front holding. The lower part of the pressure switch, as well as the bellows, are made of stainless steel while the housing is made of anodized aluminium. The outer protection class of the pressure switch body is IP 54.
Open the catalog to page 5Technical Data’s MECHANICAL FEATURES Body Threaded connection Limit of mechanical resistance Max working pressure Tolerance on calibration Operating temperature Clamping torque Anodized aluminium Stainless steel 30 bar 5 bar +/- 0.05 bar -25/+85 °C 5÷10 Nm ELECTRICAL FEATURES Max commutable tension Max commutable current Protection class Electrical connection Electrical scheme TECNOFLUID ENGINEERING srl Via Dei Mille, 1 20031 CESANO MADERNO (MB) TEL. 0362.645981 FAX 0362.645999 e-mail: [email protected] http: www.tecnofluid.info