1. Catalogs
  2. TECHSYS - HW a SW, a.s.
  3. Terminal for monitoring and control of equipment and power stations

Terminal for monitoring and control of equipment and power stations

Terminal for monitoring and control of equipment and power stations

Terminal for monitoring and control of equipment and power stations

Product catalog summary
Overview
The Storm-01 is a versatile terminal designed for monitoring and control in various sectors such as power, industry, transport, and telecommunications. It integrates easily into SCADA systems and is commonly used as an RTU for distribution network management.

Basic Characteristics
  • Wide range of inputs and outputs.
  • Expandable with Storm modules for digital I/O or measuring converters.
  • Customizable functions and easy integration via standard communication protocols.
  • Local and remote updates, configuration, and diagnostics.
  • A reduced version, Storm-00, is available with fewer inputs and outputs.

Typical Uses
  • Monitoring and automation of electrical stations and switching elements in distribution grids.
  • Control and regulation of power generating stations, including renewable resources.
  • Universal RTU with PLC functions for industrial and transport equipment.
  • Data transmission from power and consumption meters for utilities.
  • Monitoring and control of telecommunication and building infrastructure.

Communication Features
  • Secure communication support (IEC 62351).
  • Optional GPRS/LTE and GPS modules.
  • Multiple communication protocols and simultaneous multi-directional communication.
  • Data storage during communication link failures and time synchronization options.

Technical Specifications
  • Digital Inputs: 16x opto-element, passive input.
  • Digital Outputs: 4x switching contacts relay.
  • Analog Inputs: 4x 0-20 mA/10 V measurement.
  • Communication Interfaces: Ethernet LAN, RS-232, RS-485, mobile (LTE/UMTS/EDGE/GPRS).
  • Physical Build: 9M width plastic case, DIN rail installation, IP 20 ingress protection.
  • Power Voltage: 24 V DC, Typical Draw: 70 mA.
  • Operating Temperature: -25 to 70 °C, Max Ambient Temperature: 95% non-condensing.
  • Weight: Max 250 g, Dimensions: 158 × 90 × 60 mm.
  • EMC Standards: IEC 61000-6-4, IEC 55024, IEC 55022, IEC 61000-6-2.

Digital and Analog Input/Output Parameters
  • Digital Outputs: 1 x 4 DO, common point, with galvanic isolation.
  • Analog Inputs: 4 x AI, with options for current or voltage measurement.
  • Digital Inputs: Organized in 1 x 8 + 1 x 8, with galvanic isolation and logical level specifications.
See more

Catalog excerpts

Terminal for monitoring and control of equipment and power stations-1

Terminal for monitoring and control of equipment and power stations -> universal use -> automation functions -» mobile communication The Storm-01 is the basic unit in the Storm line. It is a multi-functional terminal that meets all general standards for SCADA systems in the power sector, industry, transport, telecommunications, and other fields. It is equipped with communication modules and a number of communication interfaces through which it can be easily integrated into customers' SCADA systems. A typical use is as an RTU for distribution network monitoring and management. Basic Characteristics • broad range of inputs and outputs • easy addition of Storm expansion modules with digital I/O or a measuring converter • ability to add special custom functions • communication interface for easy integration through a number of standard communication protocols • local and remote update, configuration, parameter setting and diagnostics through supplied software • reduced Storm-00 version of the terminal is also available, with a limited number of inputs and outputs • monitoring, control and automation of electrical stations (substations, switching or distribution stations) and switching elements (breakers, reclosers, disconnectors) in HV, MV and LV distribution grids • monitoring, control and regulation of power generating stations (renewable resources - solar power, wind farms, small hydro stations, biogas stations, cogeneration units, backup and mobile generators) • universal RTU with PLC functions for monitoring and control of equipment in industry and transport • terminals for on-line transmission of data from power and consumption meters for other utilities (gas, heat, water) • monitoring and control of telecommunication infrastructure and the infrastructure of buildings, administrative and shopping centers. • versatile as well as special communication converter for a broad range of communication interfaces and protocols • specific functions and type configuration according to customer requirements for a broad range of uses, as OEM for manufacturers, suppliers and system integrators • delivery for integration into technological components and facilities, from individual units to large series • support for secure communication according IEC 62351 • GPRS/LTE mobile communication module (optional) • serial and network communication, Ethernet • large number of communication protocols • ability to communicate in multiple directions simultaneously • data storage when the communication link goes down • time synchronization via communication protocol or from GPS (optional) Si'dlo spolecnosti Praha, Brezinova 640/3a, 186 00 Praha 8 Pracoviste Ceske Budejovice, U Vystaviste 1485, 370

 Open the catalog to page 1
Terminal for monitoring and control of equipment and power stations-2

Terminal for monitoring and control of equipment and power stations Technical specification Input status indication Basic digital input parameters settings Digital inputs parameters Si'dlo spolecnosti Praha, Brezinova 640/3a, 186 00 Praha 8 Pracoviste Ceske Budejovice, U Vystaviste 1485, 370 05 Ceske Budejovice number of bits (1,2) input scan rate filters for suppression of interference and intermediate positions value inversion Digital output parameters Analog input parameters Communication protocols (by interface)

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.