1. Catalogs
  2. TECHSYS - HW a SW, a.s.
  3. Multifunction electrical converter

Multifunction electrical converter

Multifunction electrical converter

Multifunction electrical converter

Product catalog summary
Overview: The document describes a multifunction electrical converter designed for universal use, offering high accuracy and a wide range of measurement and indication functions. It is particularly suited for the power and electrical engineering sectors, facilitating the measurement of AC quantities.
Basic Characteristics:
  • Measures basic and derived electrical quantities in 3-phase 50 and 60 Hz AC grids with accuracy starting at 0.5%.
  • Supports direct and indirect measurement using transformers and sensors like resistive and capacitive dividers, and Rogowski coils.
  • Includes fault indication and data recording capabilities.
  • Features binary inputs and outputs for monitoring and control.
  • Allows for user-defined measurement, automation, and regulation functions.
  • Offers communication interfaces for integration via standard protocols.
  • Includes software for configuration, parameter setting, and diagnostics.
Typical Use:
  • Fault measurement and indication in electrical grids, buildings, and equipment across all voltage levels (HV, MV, LV).
  • Measurement in supply and technological switchgear.
  • Monitoring equipment with specific measurement requirements, such as transformer bushing voltage.
  • Serves as a universal converter for OEM units, manufacturers, suppliers, and system integrators.
  • Functions as a standalone measurement, automation, and regulation module with user-defined functions.
Communication:
  • Supports secure communication according to IEC 62351.
  • Includes serial and network communication interfaces, such as Ethernet.
  • Offers a broad range of communication protocols and parameter settings.
Technical Parameters:
  • AC Voltage Measurement: Nominal voltage 230/400 V AC, measuring range 120% Unom, accuracy ±0.5% of range, overload capacity 2x Unom permanently.
  • AC Current Measurement: Nominal current 1 A and 5 A AC, measuring range 400% Inom, accuracy ±0.5% of range, overload capacity 2x Inom permanently.
  • Calculated Quantities: Active, reactive, and apparent power, 4-quadrant energy metering, power factor with measurement accuracy of ±1% of range.
Technical Specification:
  • Includes 3x input for both AC voltage and current measurement.
  • Digital inputs and outputs for control and monitoring.
  • Communication interfaces include Ethernet LAN, RS-232, and RS-485.
  • Mechanical build in a 6M width plastic case, suitable for 35 mm DIN rail mounting.
  • Protection level IP 20, operating temperature range -25 to 70 °C.
  • Complies with EMC emission and resistance standards IEC 61000-6-2, IEC 61000-6-4, IEC 55022, IEC 55024.
Communication Protocols: Supports RS-232, RS-485 with IEC 60870-5-101, Modbus (RTU), and Ethernet with IEC 60870-5-104, Modbus TCP, DNP 3.0 TCP.
Additional Features: The converter can be adapted to external measuring transformers and current sensors. Input impedance and voltage can be customized based on the sensors used.
Fault Indication Functions: Includes instantaneous overcurrent (ANSI 50), time overcurrent (ANSI 51), and directional overcurrent (ANSI 67, 67N).
See more

Catalog excerpts

Multifunction electrical converter-1

Multifunction electrical converter accurate measurement fault indication automation functions Multifunction converter for universal use. High accuracy and a broad range of measurement and indication functions, including custom-defined ones. Functions for special technological measurement, the ability to use modern measurement sensors. Extra communication interfaces and protocols facilitate virtually unlimited integration. Typical use is in the power and electrical engineering sectors for measuring AC quantities. Basic Characteristics • measurement of basic as well as derived electrical quantities in 3-phase 50 and 60 Hz AC grid with accuracy starting at 0.5 % • direct and indirect measurement, optional use of measurement transformers and sensors (resistive and capacitive dividers, Rogowski coils) • indication of faults in the electrical grid and data recording (fault recorder) • binary inputs and outputs for monitoring and control • the ability to add special user-defined measurement, automation and regulation functions • communications interfaces for easy integration via standard protocols • SW for configuration, parameter setting and diagnostics included TECHSYS – HW a SW, a.s. Sídlo společnosti Praha, Březinova 640/3a, 186 00 Praha 8 Pracoviště České Budějovice, U Výstaviště 1485, 370 05 České Budějovice Typical Use • measurement and indication of faults in electrical grids, buildings and equipment at all voltage levels (HV, MV and LV) • measurement and indication of faults in supply and technological switchgear • measurement unit with specific requirements for measurement functions for equipment monitoring (e.g. measurement of voltage on transformer bushings) • universal converter for a wide range of uses, as an OEM unit for manufacturers, suppliers and system integrators for monitoring, control and information systems • stand-alone measurement, automation and regulation module with user-defined functions Communication • support for secure communication according IEC 62351 • serial and network communication interfaces, Ethernet • broad range of communication protocols is available • broad range of communication parameter settings (data rate, parity, device address, network communication parameters)

 Open the catalog to page 1
Multifunction electrical converter-2

Multifunction electrical converter Technical Parameters of AC Voltage Measurement Technical Specification AC voltage measurement AC current measurement Digital inputs Digital outputs Communic. interface Mechanical build Mounting Protection Power voltage Typical draw Operating temperature Max. ambient temp. Weight Dimensions (w × h × d) EMC emission and resistance standards 3x input 3x input 4x opto-element, passive input 2x switching contacts relay Ethernet LAN 10/100, RS-232, RS-485 6M width plastic case 35 mm DIN rail IP 20 24 V DC 50 mA -25 ÷ 70 °C 95 % non-condensing max. 210 g 105 × 90 ×...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.