Series_FLOMID_Electromagnetic_flowmeter - 1

Electromagnetic flowmeters Series FLOMID Electromagnetic flowmeter for conductive liquids           Flow rate measurement is independent temperature, viscosity and pressure Pulsed coil excitation to obtain a minimum zero drift No moving parts involve low maintenance, low pressure drop and allows the pass of solids Can be mounted in any position (full pipe required) Can be installed with short straight pipe sections of minimum 5 x DN before and 3 x DN after the flowmeter Good chemical resistance Flow rate: 10 l/h ... 14100 m3/h Accuracy: ±0.5% reading value Minimum electric conductivity: 20 μS/cm Connections: - Between EN 1092-1 or ANSI flanges: DN3 … DN150 - EN 1092-1 or ANSI flanges: DN10 … DN1000 - Sanitary connections: DN10 ... DN100 According to ISO 2852, SMS 1145, DIN 11851, TRI-CLAMP® Other standards on request Materials: - Lining in PP, PVDF, PTFE and Ebonite (hard rubber) - Electrodes in Hastelloy C22 (UNS-06022), Titanium, EN 1.4404 (AISI 316L), Tantalum, Zirconium - Flow tube in EN 1.4301 (AISI 304) Local indication, volume totalizer, 4-20 mA and pulse outputs Alarms, empty pipe detection, etc. depending on converter model Full diagnosis for MX4 converter HART and Modbus Communication protocols available on request Modular design in two versions: - Compact converter, mount

Open the catalog to page 1
Series_FLOMID_Electromagnetic_flowmeter - 2

Working principle The measurement principle is based on Faraday`s induction law. A voltage V is induced between a pair of electrodes when a conductive liquid flows in a pipe of diameter D at an average velocity vm, through a magnetic field B (which is perpendicular to the flow direction). This voltage, proportional to the average velocity of the liquid, is acquired by the electronic converter in order to be processed and converted to a flow rate measurement. V = B · vm · D V = Voltage across the electrodes vm = Liquid velocity B = Magnetic field strength D = Pipe diameter  Alarms, empty...

Open the catalog to page 2
Series_FLOMID_Electromagnetic_flowmeter - 3

Electromagnetic flowmeters Series FLOMID Straight sections of pipe are necessary for the proper operation of the flowmeter. Required straight pipe run depends on the flow profile, which can be affected by the disturbing elements found in the installation before and after the sensor. A minimum distance of at least 5 x DN upstream and 3 x DN downstream from the flowmeter must be kept. Valves should be downstream from the flowmeter to keep the pipe full and to avoid vacuums which can damage the flowmeter liner. Pumps should be upstream from the flowmeter to avoid vacuums. Earth connection In...

Open the catalog to page 3
Series_FLOMID_Electromagnetic_flowmeter - 4

Dimensions FLOMID-0FX (ANSI B16.5 wafer mounted) FLOMID-0FX with compact MX4 converter

Open the catalog to page 4
Series_FLOMID_Electromagnetic_flowmeter - 5

Electromagnetic flowmeters Series FLOMID FLOMID sensor flanged mounted, common dimensions DN FLOMID-4FX (ANSI flanged mounted) ANSI

Open the catalog to page 5
Series_FLOMID_Electromagnetic_flowmeter - 6

Electromagnetic flowmeters hygienic execution FLOMID sensor fully hygienic execution, common dimensions L1 Sensor with PTFE lining and AISI 316L end connectors, suitable for hygienic applications in pharmaceutical and food and beverage industries, among others. Available with MX4 and XT5 converters.

Open the catalog to page 6
Series_FLOMID_Electromagnetic_flowmeter - 7

Electromagnetic flowmeters Series FLOMID FLOMID-5DFX (CLAMP DIN 32676) * OD = pipe outer Ø according to DIN 11850 (Series 2) * OD = pipe outer Ø according to ISO 2037 * OD = pipe outer Ø according to ASME BPE DT-1 Also available FLOMID-9WIFX (ISO 2037 weld-on connections) Also available FLOMID-6BFX (BSP connection) and FLOMID-6NFX (NPT connectio

Open the catalog to page 7
Series_FLOMID_Electromagnetic_flowmeter - 8

Sensor selection The diagram shows the correspondance between the liquid velocity and the flow rate for different sensor sizes. The sensor size should be chosen selecting a liquid velocity of about 3-4 m/s. The minimum liquid velocity should not be below 0.5 m/s. 10 When the liquid has solids in suspension, it is better to work between 3 and 5 m/s in order to avoid sedimentation in the pipe and sensor. Accuracy curve (error vs velocity) 100 ± e (%) 6 e = ± 0.5% reading value e = ± [0.2 / v (m/s)] % reading value m3/h FLOMID-2FX with compact XT5 converter

Open the catalog to page 8
Series_FLOMID_Electromagnetic_flowmeter - 9

Electromagnetic flowmeters Series FLOMID Lining materials. Temperature, pressure and vacuum limits PTFE PVDF / PTFE EBONITE (hard rubber) Temp. range In mbar absolute, 40ºC / 80ºC reference temperature FLOMID-0FX with compact XT5 converter

Open the catalog to page 9
Series_FLOMID_Electromagnetic_flowmeter - 10

Electronic converters Different models of electronic control units are available to comply with the options of flow indication, maximum / minimum flow rate control, analog and pulse outputs. All of them are compatible with the different FLOMID-FX sensor models. Time These converters can be supplied for compact mounting directly on top of the sensor or for remote mounting. Cable is supplied. HART protocol is available for both MX4 and XT5 converters. Modbus RTU protocol is available for MX4 converter. Pulsed coil excitation XT5 converter Remote mounted converter (model XT5M) Technical data...

Open the catalog to page 10
Series_FLOMID_Electromagnetic_flowmeter - 11

Electromagnetic flowmeters Series FLOMID Remote mounted converter (model MX4M) MX4 converter Technical data  IP67 coated aluminium enclosure  Programming via front push buttons  128 x 64 graphic display  Linearity: ±0.2% f.s.  Repeatability: ±0.1% f.s.  Ambient temperature range: -20ºC ... +60ºC  Power supply: 90 … 265 VAC 50 / 60 Hz 12 … 48 VDC  Power consumption: ≤ 5 VA  Flow rate and liquid velocity indication: * DIN 571 screws or similar are required (depending on the installation) - No. of digits: 5 (0 to 2 decimal configuration) - Digit size: 11 mm  Volume...

Open the catalog to page 11
Series_FLOMID_Electromagnetic_flowmeter - 12

R-CT-FLOMID Rev. 3 english version PRESENCE IN MORE THAN 50 COUNTRIES ALL OVER THE WORLD Tecfluid S.A. Narcís Monturiol 33 08960 Sant Just Desvern Barcelona Tel: +34 93 372 45 11 Fax: +34 93 473 44 49 tecfluid@tecfluid.com www.tecfluid.com Quality Management System ISO 9001 certified by Pressure Equipment Directive 97/23/CE certified by ATEX European Directive 94/9/CE certified by HART® is a registered trademark of HART Communication Foundation The technical data described in this specification sheet is subject to modification without notification if the technical innovations in the...

Open the catalog to page 12