Liquid Cooled Air Conditioners 150-1180 BTU/hr
8Pages

{{requestButtons}}

Catalog excerpts

Liquid Cooled Air Conditioners 150-1180 BTU/hr - 1

catalog 2011 working on.qxp 6/28/2011 2:10 PM 150-1180 BTU/hr LIQUID COOLED Page 72 Liquid Cooled Air Conditioners LHP SERIES Solid-state liquid-cooled air conditioners work well in tight enclosures. FEATURES • No compressor, fluorocarbons or filters • Virtually maintenance free operation • Stainless steel exterior housing • Mounts in any orientation • No air exhaust APPLICATIONS Cools equipment racks, PCs, Drives, Amplifiers, Motor Controls and other electronic equipment. 72 TECA 1-888-TECA-USA (832-2872) www.teca-usa.com

Open the catalog to page 1
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 2

catalog 2011 working on.qxp 6/28/2011 2:10 PM Page 73 AIR CONDITIONERS Liquid Cooled 150-1180 BTU/hr LHP-1700FF page 74 LHP-1200 page 76 950-1180 BTU/hr rating, 19.0" x 8.7" mounting area 120 and 240 VAC input. 590-640 BTU/hr rating, 15.0" x 7.3" mounting area 120 VAC input LHP-800FF page 78 LHP-300FF page 78 460-540 BTU/hr rating, 6.6" x 6.6" mounting area 24 VDC for TE, 120 VAC fan 150-175 BTU/hr rating, 4" x 4" mounting area 24 VDC for TE 120 VAC fan TEAM TECA CUSTOM ENGINEERING Call us at 888-TECA-USA. We’re here to help! www.teca-eu.com 1-888-TECA-USA (832-2872) TECA 73

Open the catalog to page 2
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 3

catalog 2011 working on.qxp 6/28/2011 2:11 PM Page 74 LHP-1700FF Liquid Cooled Air Conditioner Liquid Cooled Thru Mount NEMA-12 120 VAC, 240 VAC Input FEATURES • Standard 19” rack mount • Weighs only 46 lbs. (21 kg) • Ambient range 0ºC to +70ºC • Available in 120 or 240 VAC • Adaptable to NEMA-4 and explosion proof applications • Can be mounted entirely inside purged enclosure • No compressor, fluorocarbons or filters • Virtually maintenance-free operation • Stainless steel exterior housing • Mounts and operates in any orientation INCLUDES • Integral power supply • Compression fittings •...

Open the catalog to page 3
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 4

catalog 2011 working on.qxp 6/28/2011 2:11 PM Page 75 Air Conditioner - Liquid Cooled LHP-1700FF PERFORMANCE CURVE MOUNTING STYLE Thru Mount ENVIRONMENTS SERVED NEMA-12 IP 52 RATING (TRADITIONAL) 1050 BTU/hr @ 0 °F ⌬T 1320 BTU/hr @ +20 °F ⌬T * RATING (DIN 3168) 312 Watts L35 L35 225 Watts L35 L50 * See page 10 Equation of line: y=⌬T(°C) x=Capacity (Watts) Fluid Temp 20°C 40°C 60°C Enclosure Air y=.147x-41.0 y=.147x-46.0 y=.147x-51.0 Cold Sink y=.11x-41.0 y=.11x-46.0 y=.11x-51.0 Air Flow Pattern DIMENSIONS www.teca-eu.com 1-888-TECA-USA (832-2872) TECA 75

Open the catalog to page 4
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 6

catalog 2011 working on.qxp 6/28/2011 2:11 PM Page 77 Air Conditioner - Liquid Cooled LHP-1200 PERFORMANCE CURVE MOUNTING STYLE Thru Mount ENVIRONMENTS SERVED NEMA-4 IP 56 Class I Div 2 and NEMA-4X IP 56 Class I Div 1 and ATEX Zone 1 RATING (TRADITIONAL) 613 BTU/hr @ 0 °F ⌬T 770 BTU/hr @ +20 °F ⌬T * RATING (DIN 3168) 180 Watts L35 L35 125 Watts L35 L50 * See page 10 Equation of line: y=⌬T(°C) x=Capacity (Watts) Fluid Temp 20°C 40°C 60°C Enclosure Air y=.25x-44.0 y=.25x-46.0 y=.25x-48.0 Cold Sink y=.19x-44.0 y=.19x-46.0 y=.19x-48.0 Air Flow Pattern DIMENSIONS www.teca-eu.com 1-888-TECA-USA...

Open the catalog to page 6
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 7

catalog 2011 working on.qxp 6/28/2011 2:11 PM Page 78 LHP-800FF Liquid Cooled Air Conditioner LHP-300FF General Purpose VDC Input Liquid Cooled Thru Mount NEMA-12 FEATURES • Compact • Light weight • Ambient range 0ºC to +70ºC • No compressor, fluorocarbons or filters LHP-800FF • Adaptable to NEMA-4 and explosion proof applications. Can be mounted entirely inside purged enclosure • Virtually maintenance-free operation • Mounts and operates in any orientation INCLUDES • Compression fittings • Terminal strip for wire hook up LHP-300FF SPECIFICATIONS LHP-800FF MODEL PART NUMBER NOTES...

Open the catalog to page 7
Liquid Cooled Air Conditioners 150-1180 BTU/hr - 8

catalog 2011 working on.qxp 6/28/2011 2:12 PM Page 79 Air Conditioner - Liquid Cooled LHP-800FF PERFORMANCE CURVE MOUNTING STYLE Internal RATING (TRADITIONAL) 500 BTU/hr @ 0 °F ⌬T 615 BTU/hr @ +20 °F ⌬T * RATING (DIN 3168) 146 Watts L35 L35 105 Watts L35 L50 LHP-300FF MOUNTING STYLE Internal RATING (TRADITIONAL) 160 BTU/hr @ 0 °F ⌬T 200 BTU/hr @ +20 °F ⌬T RATING (DIN 3168) 48 Watts L35 L35 34 Watts L35 L50 Equation of line: y=⌬T(°C) x=Capacity (Watts) Fluid Temp 20°C 40°C 60°C LHP-800FF y=.32x-43.0 y=.32x-47.0 y=.32x-51.0 LHP-300FF y=.88x-38.0 y=.88x-42.0 y=.88x-46.0 * * See page 10...

Open the catalog to page 8

All TECA (ThermoElectric Cooling America) catalogs and technical brochures

  1. CPV Cascades

    1 Pages

  2. AHP-800MSP