video corpo

Programmable Power Supplies
16Pages

{{requestButtons}}

Catalog excerpts

Programmable Power Supplies - 1

Programmable Power Supplies Innovating Reliable Power

Open the catalog to page 1
Programmable Power Supplies - 2

The next generation has arrived. And it´s small and mighty. The family of programmable power supplies sets a new standard for flexible, reliable, AC-DC power systems in OEM, Industrial and Laboratory applications. VERSATILE COMMUNICATION PROTOCOLS SMALLEST AND LIGHTEST PRODUCT ON THE MARKET HIGH FUNCTIONALITY SPEEDS UP TEST TIMES SIMPLIFIES CONTROL HIGHEST POWER DENSITY ON THE MARKET

Open the catalog to page 2
Programmable Power Supplies - 3

• 1U benchtop and 19 Inch standard rack package • Constant voltage/constant current/constant power • Wide Range of popular worldwide AC inputs, 3ø (208VAC, 400VAC & 480VAC) • Internal resistance programming function Control interfaces: • Output voltage up to 600V, current up to 500A • High resolution 16 bit ADCs & DACs • RS232/485, USB, LAN ( 1.5) built-in, isolated analogue as standard • Integrated Anybus CompactCom interface platform • Isolated analogue remote control and monitoring • Communications compatible with Z+ and GenesysTM Programming: • Arbitrary waveform (up to 100 steps)...

Open the catalog to page 3
Programmable Power Supplies - 4

Programmable Power Supplies Front Panel Description 4 3 1. ON/OFF Switch 2. Air Intake allows zero stacking for maximum system flexibility and power density 3. Reliable Detent Encoders for settings and Menu navigation 4. High Contrast/Brightness display with wide viewing angle, 16 segment LCD 5. Function/Status LEDs: Active modes and function indicators 6. Pushbuttons allow flexible user configuration Rear Panel Description 1. DB26 (Female) connector for Isolated Analogue Programming, Monitoring and other functions 2. USB Interface 3. RS-232/RS-485 IN/OUT Remote Serial Programming 4. LAN (...

Open the catalog to page 4
Programmable Power Supplies - 5

Programmable Power Supplies Front Panel Display Voltage Encoder (Clickable) Current Encoder (Clickable) Output Control buttons and Status LEDs MENU buttons and Active menu LEDs Back Programme Menu System Menu Configurations Menu Protection Communications Menu Menu External Voltage Programming Voltage Display + ‘V’ Symbol (16 Segment) AUTO-start SAFE-start Indicator FOLDback Voltage Current Indicator LFP (Locked Front Panel) FINE Output setting Voltage/Current Preview mode Output ON/OFF Status LED Alarm LED External Current Programming Operation Mode Power Supply Address & Power Indicator...

Open the catalog to page 5
Programmable Power Supplies - 6

Virtual Panel allows programming and monitoring units with or without front panel. 1. Control and monitor up-to 31 units 2. Data logging including errors, events and recovery 3. Realtime Graph and Waveform creator, store/load sequence 4. Solar array mode - calculate MPP (Max Peak Power) for solar array 5. Registers View: Operation Status, Fault, Event Status, ENABLE and INTERLOCK signals 6. Remote communication state LOC, REM, LLO Filt Ed4 Vitw Operlte Hdp Measure ‘■■uttage 19.9flQ Measure C ur i * n I^HOl 3 5 Mtliltfl CiMtnUKNMfi' Measure ValLtfle_l7,2iJ Ma, "System » poweied...

Open the catalog to page 6
Programmable Power Supplies - 7

Programmable Power Supplies Blank Panel Blank Front Panel is available for applications where the front panel display and controls are not required and only remote interface (digital/analogue) is needed. Blank Front Panel option has all the standard product functions and features except the display. The power supply can be controlled via the rear panel connectors (LAN, USB, RS-232/RS-485, Isolated analogue programming and monitoring). Parallel and Series Configurations Parallel operation - Master/Slave: • Auto paralleling Scalable Master-Slave Operation • Active current sharing allows up to...

Open the catalog to page 7
Programmable Power Supplies - 8

Programmable Power Supplies Front Panel dust filter Front panel dust cover is available for dusty air environment applications. Dust cover is removable snap-in filter (for easy maintenance) Order part number: G-AFK Order part number: GB-AFK Accessories Front Panel dust filter / Field installation kit: Air Filter 1. Material: Reticulated polyurethane Foam 2. Thickness 4.0 mm 3. 30 PPI 4. Storage temperature : -40º ~ 85ºC 5. Operating temperature : 0º ~ 60ºC 6. Humidity 95% RH Thermal derating: For all models derate 10˚C up to 2000 meter. Above 2000 m derate 2˚C / 100 meter or 2% of current...

Open the catalog to page 8
Programmable Power Supplies - 10

1. Rated output voltage(*1) V 10 20 30 40 60 80 100 150 300 600 OUTPUT RATING CONSTANT VOLTAGE MODE 1. Max. Line regulation (*7) 2. Max. Load regulation (*8) 3. Ripple and noise (p-p, 20MHz) (*9) 4. Ripple r.m.s. 5Hz~1MHz (*9) 5. Temperature coefficient 6. Temperature stability 7. Warm-up drift 8. Remote sense compensation/ wire (*10) 9. Up-prog. Response time (*11) 10. Down-prog. FuI1 load f*11) response time: No load (*12) 11. Transient response time --- 0.01% of rated output voltage --- 0.01% of rated output voltage +5mV ppm/°c 50PPM/°C from...

Open the catalog to page 10
Programmable Power Supplies - 11

1. Parallel operation 2. Series operation 3. Daisy chain 4. Constant power control 5. Output resistance control 6. Slew rate control 7. Arbitrary waveforms Possible. Up to 4 identical units in Master/Slave mode. Refer to instruction manual. Possible. Two identical units. Refer to instruction manual. Power supplies can be connected in Daisy chain to synchronize their turn-on and turn-off. Limits the output power to a proggrammed value. Programming via the communication ports or the front panel. Emulates series resistance. Resistance range: 0~1000mQ. Programming via the communication ports...

Open the catalog to page 11
Programmable Power Supplies - 13

NOTES: *1: Minimum voltage is guaranteed to maximum 0.1% of rated output voltage. *2: Minimum current is guaranteed to maximum 0.2% of rated output current. *3: Derate 5A/1°C above 40°C. *4: For cases where conformance to various safety standards (UL, IEC, etc...) is required, to be described as 190-240Vac (50/60Hz) for 3-Phase *5: 3-Phase 200V models: At 200Vac input voltage, 3-Phase 400/480V: At 380Vac input voltage. With rated output power. *6: Not including EMI filter inrush current, less than 0.2mSec. *7: 3-Phase 200V models: 170~265Vac, 3-Phase 400V models: 342~460Vac, 3-Phase 480V...

Open the catalog to page 13
Programmable Power Supplies - 14

NOTE 1. MOUNTING HOLES FOR SLIDES P/N:CC3001-00-S160,GENERAL DEVICES OR EQUIVALENT. USE #10-32x0.38INCH x3 SCREWS FOR EACH SLIDE. ENSURE THAT THE SCREWS DO NOT PENETRATE MORE THAN 6.0mm INTO THE UNIT. 2. MOUNTING HOLES FOR 19" RACK, USE M6xl 6 SCREWS TO FIX THE UNIT TO THE RACK.