(ZEp TAVRIDA ELECTRIC Excellence in Engineering VACUUM CIRCUIT BREAKER
Open the catalog to page 1This User Guide describes the Vacuum Circuit Breakers manufactured by Tavrida Electric. Tavrida Electric circuit breakers are designed for rated voltages up to 24 kV. Vacuum Circuit Breakers described in the current document can be used in various kinds of switchgear and RMUs and are intended to perform switching operations in network rated and faulty modes. The breakers are comprised of following main components: • Indoor Switching Module (ISM) - The air insulated ISM incorporates Tavrida Electric vacuum interrupters with monostable magnetic actuators and solid dielectric insulating...
Open the catalog to page 6Table 1 - Main technical parameters 1) For VCB ISM15_Shell with Low upper terminal - up to 1250 A, with High upper terminal - up to 2000 A. 2) Rating for metal enclosed switchgear with limited ventilation. Temperature rise type test at 2500 A in Cradle was successfully passed in KEMA. 4) The information in brackets refers to the national Chinese standards GB1984-2003 and installation altitude of maximum 1000 m. 5) Parameter valid only when ISM is used with insulation kit. For details see dimensional drawings and accessory information. 6) Parameter valid only when ISM is used with insulation...
Open the catalog to page 7The number of sequential Close-Trip operations with interval 10 seconds should not exceed 10. The number of Close-Trip operations should not exceed 60 per hour. Sequence of 10s Close-Trip operations can be repeated only after 260 s pause. At Cos j >0.66. At Cos j >0.33. Up to an installation altitude of 1000 m above sea level. Above 1000m, the external insulation measurement of the ISM must be increased by the atmospheric correction factor Ka according to IEC 62271-1 compared to the insulation measurement at sea level. The maximum allowed altitude is 2000 m above sea level. 1.3 Disclaimers...
Open the catalog to page 8The Vacuum Circuit Breakers itself does not have nameplates or seals but main components (ISM, CM and manual generators) it is comprised of have them. ISM nameplates and seals Each ISM has the following plate and labels: Label Serial number plate Seals Manufacturer Rated voltage Ur Rated power frequency withstand voltage Vd Rated impulse withstand voltage Up Applicable standards ISM designation Rated duration of short circuit tk Rated short-circuit current Isc Rated normal current Ir Phase center distance p Weight W Year of manufacturing Rated operating sequence The serial number...
Open the catalog to page 10Figure 4 Serial number and designation label arrangement CM nameplates and seals Each CM has the following labels: Serial number label Label with applicable ISM designation Warning label Firmware version label Information label with terminals connections and main parameters Seals Serial number label Label with applicable ISM designation Warning label Firmware version
Open the catalog to page 11Figure 9 Information label with terminals connections and main parameters Figure 10 CM labels placement Serial number label Label with applicable ISM designation Warning label Warranty seal Firmware version label Information label with terminals connections and main parameters
Open the catalog to page 12TH>TAVRIDA ELECTRIC Manual generator Figure 11 Designation label
Open the catalog to page 133.1 Transportation The VCBs are transported in the original packing only. Any kind of transport and combinations thereof are applicable. Transportation shall be provided in waterproof compartments. If air transport is used all products shall be transported inside heated, pressurized compartments. The packed goods shall be handled in accordance with the handling symbols. Loading procedures for VCB packaging shall be carried out only with use of fork lifts, hoists or cranes. If possible the packaged VCB shall be placed on a pallet. During transportation the VCB must not be subjected to sharp...
Open the catalog to page 15All items should be checked visually for: mechanical damage, scratches, discoloration, corrosion; damage to the seals Figure 3, Figure 5). Any transport damage must be reported immediately to the carrier in writing. Damages shall be photographically documented. VCB packaging and scope of supply The VCB are placed in cardboard boxes (Figure 18): handling symbols label for transport and storage of the delivery unit (Figure 16); labels for manufacturers and product information (Figure 19); label for logistics data (Figu
Open the catalog to page 16The VCB scope of supply is presented in Appendix 1. 3. Protect from rain 4. Max. weight on the delivery unit Consignee: Address Address Address Address Address Phone: Contact person P/O Number: Article: Serial Number: Customer reference Article description 111999/16402484 | TAVRIDA ELECTRIC GmbH, Im Lei man 14, 88069 Tettnanq/Tannau, Germany, Phono: 0049-7542-946785-1 | Figure 17 Label 2 Logistics data VCB has in its package: 1. Indoor Switching Module (ISM); 2. Control Module (CM); 3. Additional kits and/or components (if applicable); 4. Routine test certificate of VCB. The ISM shall have...
Open the catalog to page 17Manufacturer Product name Type of device Serial number Product code Handling symbols Figure 21 CM packaging labels The CM shall have undamaged warranty seals (its placement on the CM is shown in Figure 10). The CM designation and serial number shall comply with data in the VCB packing list and the CM routine test certificate (appearance of the CM serial number label and designation label are shown in Figure 5 and Figure 6, their placement on the CM – in Figure 10). Each CM is supplied with the following components: Figure 22 CM scope of supply ISM packaging and scope of supply As part of...
Open the catalog to page 18Figure 23 ISM15_LD, ISM25_LD scope of supply Each HD ISM is supplied with the following components: position indicator CBkit_PosInd_1 with indication cable CBcomp_ IndCable_1 Figure 24 ISM15_MD_1 scope of supply
Open the catalog to page 19d) position indicator CBkit_PosInd_1 indication cable CBcomp_IndCable_1 Figure 25 ISM15_MD_3 scope of supply Figure 26 ISMD15_Shell scope of supply position indicator CBkit_PosInd_1 with indication cable CBcomp_ IndCable_1
Open the catalog to page 20position indicator CBkit_PosInd_1 with indication cable CBcomp_ IndCable_1 Figure 27 ISMD15_HD scope of supply CBkit_Ins_3 scope of supply 24 kV variants of VCB25_LD1_16.F and VCB25_LD3_16.F include CBkit_Ins_3. As part of a VCB CBkit_Ins_3 is placed inside the VCB package. If the kit is delivered separately as a spare part of the VCB it is packed in a plastic bag. The kit includes for each pole of the ISM: Figure 28 CBkit_Ins_3 scope of supply
Open the catalog to page 21All TAVRIDA ELECTRIC NORTH AMERICA catalogs and technical brochures
-