cad

A/140 Pressure Regulators - Bulletin
8Pages

{{requestButtons}}

Catalog excerpts

A/140 Pressure Regulators - Bulletin - 2

A/140 Regulators A/140 Series Pressure Regulator The regulators of the A/140 series due to their operating specifications are mainly used in those system where sudden capacity variations are required, or else, where the cut-off of the gas distribution is controlled by solenoid valve, such as for the feeding of burners. They can be used with natural gas, manufactured gas, air, propane and other gases, as long as they do not contain a high percentage of benzole. The A/140 series regulators are spring controlled single seated, whit counterbalanced valve disc. They are usually supplied with...

Open the catalog to page 2
A/140 Pressure Regulators - Bulletin - 3

A/140 Regulators Regulator Operation The movements of the diaphragm (D) are transmitted to the valve disc (O) by the stem (S) and the lever (L). The downstream pressure through the pulse pipe (I) exerts a force under diaphragm (D) and this force is counteracted by the adjusting spring (M). The gas pressure on the diaphragm tends to close the valve disc; the antagonist action of the adjustment spring tends to open it. Under normal conditions the balance between these antagonist actions positions the valve disc in such a way as to ensure a constant pressure and therefore the downstream...

Open the catalog to page 3
A/140 Pressure Regulators - Bulletin - 4

A/140 Regulators Shut-off Device Operation The A/140 series pressure regulators can be fitted with an OS/66 slam-shut valve. This safety device operates independently of the regulator and, according to customer request, can be made to trigger by any pressure variation, whether above or below set point, or by both. Outlet pressure acting upon diaphragm (D) is counteracted by maximum pressure spring (M2), thus overcoming the action of the minimum pressure valve (M3). Under such conditions, the moving part (E) of the valve is held in balance so that lever (L) is aligned with the projecting...

Open the catalog to page 4
A/140 Pressure Regulators - Bulletin - 5

Technical Features Body allowable pressure PS Highest operating pressure Pmax Maximum Operating Inlet Pressure Pumax Inlet pressure range bpu Outlet Set Pressure Ranges Wd Functional Features Accuracy class Lock-up pressure class Maximum capacity Shut-off device Independent pneumatic control Response time ta : < 1 second Body Sizes and End Connection Styles Standard version Versions without relief valve available on reguest Tightness cover versions available on reguest (e.g. A/149-D) Materials Servomotor body Aluminium Cover Aluminium Body Ductile iron (steel available on reguest) Sleeve...

Open the catalog to page 5
A/140 Pressure Regulators - Bulletin - 6

Slam-Shut Device The following slam-shut devices are used with A/140 series regulators with built-in shut-off device: Technical Features Body Aluminium Cover Steel Following flow tables (referred to Natural Gas) are advised for an optimal use of the A/140 series For other gases with different densities, the flow rate must be multiplied by the correction factor:

Open the catalog to page 6
A/140 Pressure Regulators - Bulletin - 7

Note: The regulator can be installed with vertical or horizontal * In high pressure versions (AP), this dimension must be increased by

Open the catalog to page 7
A/140 Pressure Regulators - Bulletin - 8

Industrial Regulators Emerson Process Management Emerson Process Management LP-Cas Equipment Emerson Process Management Emerson Process Management Tescom Corporation Middle East and Africa Dubai, United Arab Emirates For further information visitwww.emersonprocess.com/regulators Our Global Product Brands: The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher, Tartarini, Franceljeon, Tescom and Emerson Process Management and the Emerson Process Management design are marks of the Emerson Process Management...

Open the catalog to page 8

All Tartarini catalogs and technical brochures

  1. Type A/100

    8 Pages

  2. Cronos series

    20 Pages

  3. FL series

    20 Pages

  4. 971

    8 Pages

  5. RLC/20

    2 Pages

  6. R series

    8 Pages

  7. Type M

    2 Pages