Technical Specifications:
  • Internal pipe diameter: 80 mm
  • Dimensions (incl. nozzle): 340 x 480 x 750 mm
  • Weight: 30 kg
  • Maximum flow: 5500 l/min
  • Maximum reach: 80 m
  • Maximum working pressure: 12 bar
  • Nominal operating pressure: 10 bar

Additional versions and sizes are available upon request.

Fire Monitor System:

The fire monitors are designed for complete installation in accordance with VdS 3884 standards. They are available in various sizes and designs, tailored to specific applications. The system integrates infrared cameras and fire monitors for effective fire prevention in storage areas, particularly in the wood industry.

Fire Detection and Extinguishing Process:

The system uses infrared cameras to monitor temperature distribution and detect fires. Upon detection, the cameras signal an alarm and communicate hotspot coordinates to the fire monitors, triggering an automatic extinguishing process. The software ensures synchronization between detection and extinguishing areas.

Key Features:
  • Made of stainless steel
  • Brushless DC motor (24 V)
  • 24/7/365 operation
  • 360° rotation and 180° vertical movement
  • Remote configuration and support
  • CE Marked, ISO 9001:2015, ISO 14001:2015 certified
  • Fully automatic extinguishing with individual specifications
  • Control via joystick, controller, or any computer with web access
  • Activation by flame detector possible
Intelligent Camera System:

The camera system includes AI software to minimize false alarms, activating extinguishing only for incipient fires. It can be certified by VdS or comply with EN 54-10. The system can integrate daylight optics for real-time monitoring, with customizable display options.

Fire Monitor Operation:

The fire monitor can operate automatically or manually, adjusting the nozzle opening based on transmitted coordinates to optimize the extinguishing process. Manual control allows precise targeting of the fire location.

See more

Catalog excerpts

Early fire protection with IR camera and fire monitor-1

The fire monitors can be completely installed in accordance with VdS 3884. They are available in different sizes and designs. We design cameras and fire monitors as a harmonised system for each specific application. Technical data of the fire monitor Internal pipe diameter: 50 mm 80 mm Dimensions (incl. nozzle): 250 x 350 x 580 mm 340 x 480 x 750 mm Maximum flow: 2100 l/min 5500 l/min Maximum working pressure: 12 bar 12 bar Nominal operating pressure: 10 bar 10 bar More versions and sizes on request. Do you have any questions or would you like advice? Get in touch with us directly: l&B electronic FIRE PROTECTION T&B electronic GmbH IndustriestraBe 3 31061 Alfeld | Germany 05/2025 | Technical changes reserved

 Open the catalog to page 1
Early fire protection with IR camera and fire monitor-2

Fire protection for storage areas in the wood industry Autonomous fire protection system with infrared cameras and fire monitors

 Open the catalog to page 2
Early fire protection with IR camera and fire monitor-3

Detect quickly – delete immediately. When storing wood, waste wood and fuels in closed bunkers or in open areas, reliable equipment for recognising and fighting fires is required. Our early fire detection system based on certified infrared cameras in combination with fire monitors offers effective prevention. Team play for efficient extinguishing. © Andrei Merkulov – stock.adobe.com Waste wood recycling Wood-based material The infrared cameras are focused to the freely definable sectors of the area to be monitored and continuously measure the temperature distribution at the various positions....

 Open the catalog to page 3
Early fire protection with IR camera and fire monitor-4

Intelligent camera system. The camera has software with an AI model that minimises false alarms. This means that an extinguishing operation is only activated in the event of an incipient fire. Depending on your processes and the requirements of your insurer, you can use the infrared camera with the required certification: Either certified by the VdS or in accordance with the European directive for fire alarm systems EN 54-10. In addition to the infrared sensors, daylight optics can be integrated into the camera. In this way, it is possible to display not only the thermal image but also the real...