1. Catalogs
  2. Supmea Automation
  3. SUP-PH2.3 pH controller
video corpo

SUP-PH2.3 pH controller

SUP-PH2.3 pH controller

SUP-PH2.3 pH controller

Product catalog summary
Overview
The SUP-PH2.3 is an online pH/ORP controller developed for continuous monitoring of pH and ORP values in various industries such as thermal power, chemical, and water treatment. It features remote data transmission and recording capabilities.

Key Characteristics
  • Modular circuit design with isolated transformer output to minimize interference.
  • Supports both manual and automatic temperature compensation.
  • Includes high and low alarm functions, buzzer switch, and quick access to online calibration.
  • Features a large LCD screen for display.

Specifications
  • Display: 2.8-inch monochrome LCD.
  • Dimensions: 96mm x 96mm x 112mm; Cutout: 92mm x 92mm.
  • Weight: 0.5Kg.
  • Measurement Range: pH 0.00-14.00, ORP -1000 to +1000mV (customizable to -2000 to +2000mV).
  • Accuracy: pH ±0.02, ORP ±1mV.
  • Temperature Compensation: NTC10K, range -10 to 130°C.
  • Current Output: 4-20mA, max load 750Ω, accuracy ±0.2% FS.
  • Alarm Function: 2 channels, AC250V/3A capacity.
  • Operating Conditions: Temperature 0-60°C, Humidity 10-85% RH.
  • Power Supply: AC 220V ±10%, 50Hz or DC 24V.
  • Communication: RS485 interface.

Installation and Wiring
  • Includes detailed terminal identification for easy setup.
  • Supports fixed installation with specified dimensions.

Calibration
  • Regular calibration is necessary due to electrode aging and coating.
  • Multi-point calibration is recommended for accuracy, covering a range of pH values.
  • Example calibration points include pH 4.00, 7.00, and 10.00.

Ordering Information
  • Various sensor types and cable lengths available.
  • Standard functions include 4-20mA, RS485, and relay output.
  • Order codes specify sensor type, cable length, calibration points, power supply, and medium type.
See more

Catalog excerpts

SUP-PH2.3 pH controller-1

E-mail: [email protected] Online pH/ORP controller Committed to process automation solutions Add : 5th floor, Building 4, Singapore Hangzhou Science Technology Park, Hangzhou Economic Development Area, 310018, Hangzhou, China

 Open the catalog to page 1
SUP-PH2.3 pH controller-2

E-mail: [email protected] SUP-PH 2.3 meter is an instrument independently developed by our company for online monitoring of pH/ORP value and through the current analog output to the monitoring room for record preservation. pH /ORP controller is widely used in thermal power, chemical fertilizer, metallurgy, environmental protection, Pharmaceutical, biochemical, food and water industries and for solution pH or ORP Values and temperatures are continuously monitored.The continuous monitoring data can be recorded by remote transmission through substation and output connection. Characteristics ■ Circuit...

 Open the catalog to page 2
SUP-PH2.3 pH controller-3

E-mail: [email protected] www.supmea.com Isolation type, 4~20mA can be set corresponding pH/ORP and Current output temperature measurement range, maximum load 750 Ω, output accuracy + / - 0.2% FS. Alarm function 2 channels, capacity AC250V/3A,normally open Relative humidity Operating temperature Power supply Storage condition Relative humidity: 5~85%RH (no condensation) Altitude: <2000m Add : 5th floor, Building 4, Singapore Hangzhou Science Technology Park, Hangzhou Economic Development Area, 3100

 Open the catalog to page 3
SUP-PH2.3 pH controller-4

E-mail: [email protected] Installation dimension Fixed installation Add : 5th floor, Building 4, Singapore Hangzhou Science Technology Park, Hangzhou Economic Development Area, 310018, Hangzhou, China

 Open the catalog to page 4
SUP-PH2.3 pH controller-5

E-mail: [email protected] Description ■ Press [ MENU ] to enter password verification page; input password to enter the home page. ■ Press [ ENT ] to enter alarm inquiry page, to inquire the current warning configuration information. Identification of terminal ■ REF: Reference terminal of the electrode ■ INPUT: Measuring terminal of the electrode ■ TEMP1: Temperature compensating end 1 ■ TEMP2: Temperature compensating end 2 ■ RS485A+:RS485 communication interface A+ ■ RS485B-:RS485 communication interface B■ NC: Unidentified ■ 4-20mA (+): 4-20mA output end+ ■ 4-20mA (-): 4-20mA output end■ AC220V...

 Open the catalog to page 5
SUP-PH2.3 pH controller-6

E-mail: [email protected] pH calibration A pH calibration is the procedure of adjusting the pH meter by measuring solutions of known pH values. Why you need to calibrate: The characteristic of a pH electrode will change with time due to electrode coating and aging. And even a pH electrode would be stable over time, pH electrodes cannot be produced with identical characteristics. In practice the response of a real pH sensor does not exactly follow the Nernst equation. This difference between the theoretical and actual behavior of a pH electrode must be compensated for. A calibration is required...

 Open the catalog to page 6
SUP-PH2.3 pH controller-7

E-mail: [email protected] Multi-point calibration To achieve the best possible accuracy, the calibration should cover the range of the desired measurement values. If the readings go beyond the calibrated range, the pH meter assumes linearity and simply extrapolates the value to be displayed. The true value may be slightly different. More advanced pH meters will let the user calibrate at three, four or five and even higher numbers of pH values. A multi-point calibration mean, in comparison to a two-point calibration, that you can calibrate your pH tester on both sides of the zero point (pH 7.00)....

 Open the catalog to page 7
SUP-PH2.3 pH controller-8

E-mail: [email protected] Ordering Code Basic Type pH2.3 Plastic pH/ORP sensor with NTC 10K (0-60℃) Glass pH/ORP sensor with NTC 10K (0-80℃) High Temperature pH sensor with NTC 10K (0-130℃) pH/ORP Probe Made in Germany pH sensor Made in Germany pH sensor Jumo (0-80℃) Plastic pH/ORP sensor with NTC 10K (0-60℃) Glass pH/ORP sensor with NTC 10K (0-80℃) 5 meters Cable Length Calibration Points Power Supply 24VDC Normal water Waste water Nutrient solution Galvanic plating Cooling water Drinking water Others: Note: 4-20mA ,RS485 and relay output are standard functions, make inquiries by placing letter...

 Open the catalog to page 8
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.