XLPE Insulated Power Cable at Rated Voltage 19/33kV

XLPE Insulated Power Cable at Rated Voltage 19/33kV

XLPE Insulated Power Cable at Rated Voltage 19/33kV

Product catalog summary
Executive Standard
This document outlines the specifications for XLPE Insulated Power Cables rated at 19/33kV, manufactured according to BS 6622 and BS EN/IEC 60228 standards.
Application Scopes
The cables are designed for power transmission and distribution systems operating at a rated voltage of 19/33kV.
Operating Features
  • Rated Voltage: U0/U(Um) is 19/33(36)kV, where U0 is the voltage between earth and conductor, U is the voltage among conductors, and Um is the maximum system voltage.
  • Maximum conductor operating temperature is 90℃ under normal conditions and 250℃ during short circuits (max duration 5 seconds).
  • Minimum bending radius during installation is 15D for single-core and 12D for multi-core cables, where D is the cable's outer diameter.
  • Installation temperature should not be below 0℃; cables must be preheated if below this temperature.
Cable Structure
  • Conductor: Stranded copper as per BS EN/IEC 60228.
  • Insulation: XLPE type GP8 as per BS 7655.
  • Metallic screen: Copper tape or wire as per BS 6622.
  • Armor: Aluminum wire for single-core, steel wire for multi-core.
  • Outer sheath: PVC type 9 as per BS 7655.
Technical Parameters
The document provides detailed tables with parameters such as nominal cross-sectional areas, outer diameter, weight, maximum conductor D.C resistance, operating capacitance, and current ratings for both air and underground installations.
Laying Conditions
  • In Air: Multi-core cables should be laid separately, and single-core cables can be arranged in trefoil or flat formations. Ambient temperature is considered at 30℃.
  • In Soil: Cables should be buried at a depth of 800mm with a soil thermal resistivity of 1.5 K·m/W. Ambient temperature is considered at 20℃.
Correction Coefficients
Correction coefficients for current capacity are provided for different ambient temperatures, both in air and soil, to ensure optimal performance under varying conditions.
See more

Catalog excerpts

XLPE Insulated Power Cable at Rated Voltage 19/33kV-1

XLPE Insulated Power Cable at Rated Voltage 19/33kV Executive Standard 7. Wrapping tape: non-woven fabrics. 8. Separating sheath: PVC type 9 as per BS 7655. 9. Armor: aluminum wire for single-core cable, steel wire for multi-core cable. 10. Outer sheath: PVC type 9 as per BS 7655. Technical parameter This products will be manufactured as per BS 6622, BS EN/IEC 60228 standards. Application Scopes The cables are applied to power transmission and distribution system at rated voltage19/33kV. Operating Features 1.Rated Voltage: U0/U(Um): 19/33(36)kV. U0—Rated power frequency voltage between earth and metal shield to conductor for cable design; U—Rated power frequency voltage among conductors for cable design; Um—Bearable max value of “Max System Voltage” for equipment. 2.Max conductor operating temperature at normal operation: 90℃ for XLPE insulation. 3.Max conductor temperature during cable short circuit: 250℃ for XLPE insulation (max. duration is 5 sec.) 4.Min. bending radius of cable during installation: (1)Single-core cable: 15D. (2)Multi-core cable: 12D. D—Actual O.D of cable sample (mm) 5 .Cable Installation The ambient temp of cable installation shall not be less than 0℃, the cable shall be preheated if it is less than 0℃. Cable structure 1. Conductor: category stranded copper conductor as per BS EN/IEC 60228. 2. Conductor screen: semi-conducting screen material. 3. Insulation: XLPE type GP8 as per BS 7655. 4. Insulation screen: semi-conducting screen material. 5. Metallic screen: copper tape or wire screen as per BS 6622. 6. Filler: polypropylene nets PP strip. Electrical Parameters Nom. cross Structure Parameters sect areas Max conductor Outer Weight Operating of conductor diameter (approx.) D.C resistance at capacitance (approx) 20℃ 2 mm2 mm kg/km μF/km ≤Ω/km 50 70 95 120 150 185 240 300 400 Current rating of cable Underground (20℃) Conducto r current at short circuit (5 (5S) S)

 Open the catalog to page 1
XLPE Insulated Power Cable at Rated Voltage 19/33kV-2

Cable current capacity calculation conditions: Both end earthing is applied for cable metallic screen interconnection earthing. Laying in Air 1. Multi-core cable laying: separated cabling laying. (Single cable is laid independent or the heat produced by adjacent cable has no effect on that cable) 2. Single core arrangement: trefoil formation: contact with each other Flat formation: S=De (three cables laid in flat arrangement, the distance between cable cores (s) is the cable outer diameter (De)). 3. Ambient temperature: 30℃. 4. Correction coefficient for current capacity under different ambient...

 Open the catalog to page 2