video corpo

SC100

SC100

Product catalog summary
Overview: The document provides technical specifications for the SC 100 energy storage power supply system by Sungrow-Samsung. It outlines the system's capabilities, protection parameters, and general data.
Features: The SC 100 supports both on-grid and off-grid operations with an independent inverter. It includes a multi-machine parallel function and an optional virtual synchronous motor control function. The system can handle a three-phase 100% unbalance load.
Specifications:
  • Nominal Power: 100kW
  • Max. AC Power: 110kVA (long time operation)
  • Max. AC Current: 159A
  • Max. THD: <3% at nominal power
  • Nominal Grid Voltage: 400V
  • Grid Voltage Range: 310~450V
  • Nominal Grid Frequency: 50/60Hz
  • Grid Frequency Range: 47~52Hz/57~62Hz
  • Power Factor at Nominal Power: >0.99
  • Isolation Transformer: Yes
  • Power Factor Range: 0.9 (lagging) ~ 0.9 (leading)
  • Individual Inversion Voltage Range: 370~410V
  • Individual Inversion Output Voltage Distortion: <3% (linear load)
  • Unbalance Load Capacity: 100%
  • Individual Inversion Voltage Transition Range: Within 10% (resistance load 0%~100%)
  • Max. DC Voltage: 820V
  • Working Voltage Range: 500~800V
  • Min. DC Voltage: 480V
Protection Parameters: The system includes DC and AC side disconnection devices, DC and AC over-voltage protection, reverse polarity protection, and module temperature protection.
General Data:
  • Dimensions (W*H*D): 806×1884×636mm
  • Weight: 760kg
  • Operating Ambient Temperature Range: -30℃ to +55℃
  • Power Consumption at Stop: <40W
  • Cooling Concept: Temperature-controlled forced air cooling
  • Ingress Protection Rating: IP21
  • Relative Humidity: 0~95% (Non-condensing)
  • Max. Operating Altitude: 6000m (derating >4000m)
  • Display: Touch screen
  • Dispatch Communication: RS485, Ethernet
  • BMS Communication: RS485, CAN
  • Communication Protocol: Modbus/IEC104
  • Max. Efficiency: 97.30%
See more

Catalog excerpts

SC100-1

Features Support on-grid charge/discharge and off-grid independent inverter Multi-machine parallel function Optional virtual synchronous motor control function Three-phase 100% unbalance load ability equipped Input (DC) side Max. DC voltage Working voltage range Min. DC voltage General Data Dimensions (W*H*D) Weight Operating ambient temperature range Power consumption at stop Cooling Concept Ingress protection rating Relative humidity Max. operating altitude Display Dispatch communication BMS communication Communication protocoll DC side disconnection device AC side disconnection device DC over-voltage protection AC over-voltage protection Reverse polarity protection Module temperature protection Circuit breaker Circuit breaker Yes Yes Yes Yes Output (AC) Side Nominal power Max. AC power Max. AC current Max. THD Nominal grid voltage Grid voltage range Nominal grid frequency Grid frequency range Power factor at nominal power Isolation transformer Power factor range Individual inversion voltage range Individual inversion output voltage distortion Unbalance load capacity Individual inversion voltage transition range @ 2016 SUNGROW-SAMSUNG SDI ENERGY STORAGE POWER SUPPLY CO.,LTD All rights reserved. Subject to change without Notice.Version#1.0