1. Catalogs
  2. STEGO
  3. CSS014 IO-Link Parameter EN 2019

CSS014 IO-Link Parameter EN 2019

CSS014 IO-Link Parameter EN 2019

CSS014 IO-Link Parameter EN 2019

Product catalog summary
General Information
The document details the technical specifications for the STEGOSMART SENSOR CSS 014 by STEGO Elektrotechnik GmbH. It includes identifiers such as manufacturer ID, product ID, device ID, and IO link version. The sensor operates at a COM2 bitrate with a minimum cycle time of 10.0 ms, supports data storage, but does not support SIO mode.
Pin Assignment
The sensor's pin configuration is: Pin 1 (+24 V DC), Pin 2 (not applicable), Pin 3 (GND), and Pin 4 (IO link communication).
Process Data
The sensor measures temperature and humidity, providing current values and status alarms. Values are displayed with a factor of 0.1, and alarms are triggered based on predefined thresholds.
Parameters
User-specific parameter assignments are possible, with factory settings initially deactivated. Parameters include configurable temperature and humidity settings for alarms and warnings.
Diagnostics Data
The sensor provides diagnostics data such as device status, error counts, operating hours, and power-on counts. It records maximum and minimum temperature and humidity values during the activation period.
Temperature and Humidity Parameters
Detailed settings for temperature and humidity alarms and ranges are provided, with configurable high and low alarms. A histogram of temperature and humidity ranges is included.
Events and Messages
The document outlines events and messages related to temperature and humidity alarms, including event codes for threshold warnings.
Alarm and Error Notifications
  • Humidity Alarm Low: Indicates if humidity is below the threshold. Status: true/false. Warning code: 6213.
  • Sensor Humidity Raw Data Too Low: Raw data below minimum for 0.0% calculation. Status: true/false. Error code: 6214.
  • Sensor Humidity Raw Data Too High: Raw data exceeds maximum for 100.0% calculation. Status: true/false. Error code: 6215.
  • Histogram Data Max Time Reached: Indicates maximum time in a histogram range reached. Status: true/false. Message code: 6220.
Commands
  • Password: Required for resetting values. Default: "stego". Index: 0x0FA0, Subindex: 0x00, Data type: StringT [16].
  • Production Commands: Require password. Index: 0x0FA1, Subindex: 0x00, Data type: UIntegerT_8.
    • Store Production Settings: Saves current settings.
    • Reset Production Settings: Resets to default.
    • Reset All, Including Histogram Data: Resets all diagnostics data.
    • Reset All Alarm/Range Counters: Resets all alarm and range counters.
    • Reset Temperature Alarm/Range Counters: Resets temperature-related counters.
    • Reset Humidity Alarm/Range Counters: Resets humidity-related counters.
  • Standard Commands: Index: 0x02, Subindex: 0x00, Data type: UIntegerT_8.
    • Restore Factory Settings: Resets all variables and parameters to zero.
Temperature and Humidity Points
  • Temperature Points Reset/Disable (Preset 0): Deactivates all temperature parameters.
  • Temperature Points Preset 1: Loads preset 1 to temperature parameters.
  • Humidity Points Reset/Disable: Deactivates all humidity parameters.
  • Humidity Points Preset 1: Loads preset 1 to humidity parameters.
See more

Catalog excerpts

CSS014 IO-Link Parameter EN 2019-1

© IO-Link SMART SENSOR CSS 014 | IO link parameters

 Open the catalog to page 1
CSS014 IO-Link Parameter EN 2019-2

SMART SENSOR CSS 014 | IO link parameters GENERAL INFORMATION GENERAL DATA Manufacturer name Manufacturer ID Manufacturer URL Product ID Device ID IO link version Bitrate Minimum cycle time SIO mode Data storage STEGO Elektrotechnik GmbH 0x04C6 / 1222d www.stego.de CSS 01411.2-00 ID 0x000012 / 18d V 1.1 COM2 10.0 ms No Yes IDENTIFICATION Parameter name Vendor Text Manufacturer text 0x11 0x00 StringT [ 64 ] www.stego.de Product Name Device name 0x12 0000 StringT [ 64 ] CSS 014 IO link Product ID ID number of the device 0x13 0000 StringT [ 64 ] CSS 01411.2-xx Product Text Device description 0x14...

 Open the catalog to page 2
CSS014 IO-Link Parameter EN 2019-3

Humidity Alarm High Humidity status, alarm H 1.x 0x0B 0x00 BooleanT false, true Humidity Range High Humidity status, warning H 2.x 0x0C 0x01 BooleanT false, true Humidity Range Low Humidity status, warning H 3.x 0x0D 0x02 BooleanT false, true Humidity Alarm Low Humidity status, alarm H 4.x 0x0E 0x03 BooleanT false, true SMART SENSOR CSS 014 | IO link parameters Temperature Current sensor measurement value (factor for 0x01 0x20 IntegerT_16 °C/°F calculating the display value: 0.1) Temperature Alarm High Temperature status, alarm T 1.x 0x02 0x18 BooleanT false, true Temperature Range High Temperature...

 Open the catalog to page 3
CSS014 IO-Link Parameter EN 2019-4

SMART SENSOR CSS 014 | IO link parameters PARAMETERS The parameters for the alarm and warning limits are deactivated when the device is in its delivered condition (factory setting). These parameters can be overwritten by the user. Customer-specific parameter assignment is therefore possible. The sensor outputs the data as raw data (IO link values). However, the parameters in the IO link tool are input directly as a value in °C / °F. The factor for calculating the display value for temperature and humidity is 0.1. The parameters for temperature and humidity are checked in terms of their mutual...

 Open the catalog to page 4
CSS014 IO-Link Parameter EN 2019-5

SMART SENSOR CSS 014 | IO link parameters status bit is set in the process data. Calculation of the display value for the humidity 17/09/2019, V1.0 | Subject to technical changes. We provide no assurances as to the accuracy of the specifications. The information cited does not absolve the customer from its responsibility for independent application checks. www.stego.de

 Open the catalog to page 5
CSS014 IO-Link Parameter EN 2019-6

SMART SENSOR CSS 014 | IO link parameters DIAGNOSTICS DATA Parameter name Device is OK Maintenance required Out of specification Functional check Failure Detailed Device Status Detailed Device Status [1] Detailed Device Status [2] Detailed Device Status [3] Detailed Device Status [4] Detailed Device Status [5] Detailed Device Status [6] Error Count Operating Hours Power-on counter Additional device-dependent information (errors/warnings/messages) Output of errors/warnings/messages Error counter Operating hours counter (base unit 0.001 h) Activation counter See „Events und Meldungen“ auf Seite...

 Open the catalog to page 6
CSS014 IO-Link Parameter EN 2019-7

SMART SENSOR CSS 014 | IO link parameters HUMIDITY DIAGNOSTICS DATA Parameter name Minimum humidity across the entire activation period Event counter for humidity exceeded alarm quantity Event counter for humidity range exceeded quantity Event counter for humidity range undershot quantity Event counter for humidity undershot alarm quantity Duration of incidences in the humidity range 0% to 100% in 20x 5% humidity range steps 17/09/2019, V1.0 | Subject to technical changes. We provide no assurances as to the accuracy of the specifications. The information cited does not absolve the customer from...

 Open the catalog to page 7
CSS014 IO-Link Parameter EN 2019-8

SMART SENSOR CSS 014 | IO link parameters EVENTS AND MESSAGESThe messages are output via the variable Detailed Device Status [x] (see „Diagnosedaten“ auf Seite 6). Name Sensor Humidity raw data Raw data above the value for the calculation of 100.0% false/true Error 6215 Humidity Points: Preset 1 Preset 1 is loaded to the humidity parameters 17/09/2019, V1.0 | Subject to technical changes. We provide no assurances as to the accuracy of the specifications. The information cited does not absolve the customer from its responsibility for independent application checks. www.stego.de

 Open the catalog to page 8