Overview: The document provides technical specifications and installation guidelines for the Econ series air curtains by Stavoklima. These air curtains are designed for wall or under-ceiling mounting and are suitable for use in various commercial settings such as shops, restaurants, and hotels.
Specifications: The Econ air curtains are available in different lengths (1000mm, 1500mm, 2000mm) and can be equipped with either ambient or heated options. The heated models can use water or electric heating with varying capacities. The units operate at 230V and have a motor protection degree of IP22. Noise levels range from 54 to 58 dB(A).
Heating Capacities: Water heated models have capacities ranging from 8.6 kW to 18.1 kW, while electric models range from 2.5 kW to 17.5 kW. The document provides detailed tables for heating capacities at different water temperatures and electric power ratings.
Control and Accessories: The Econ series includes an inbuilt electronic regulator for easy control. Accessories such as thermostatic valves, room thermostats, and door contacts are available. The control system includes features like protection against overheating and fan delay.
Installation and Connection: The document outlines the connection requirements for both water and electric heated models, including diagrams for wiring and control connections. It specifies the use of flexible tubes and thermostatic valves for installation.
Order Key: The document provides a coding system for ordering different models based on unit length, heating type, and capacity.
Contact Information: Stavoklima's contact details are provided for further inquiries and support.
See more

Catalog excerpts

Econ-1

www.stavoklima.eu Air curtain Econ

 Open the catalog to page 1
Econ-2

01/09 Technical Modifications Reserved page 2 *) heating capacity based on 18¢ªC air inlet temperature **) acoustic pressure dB(A) measured at a distance of 3m Technical data: Econ 100 S Econ 150 S Econ 200 S Econ 100 W Econ 150 W Econ 200 W Air curtain length mm 1000 1500 2000 1000 1500 2000 Air volume m3/h 1400 1750 2350 1220 1850 2265 Heating capacity kW - - - 8,6 13,5 18,1 80/60¢ªC kPa - - - 6,9 2,7 3,4 I/hod - - - 360 576 756 Heating capacity kW - - - 4,8 7,5 10,3 60/40¢ªC kPa - - - 2,6 1,00 1,30 I/hod - - - 180 288 432 Unit voltage V 230 V 230 V 230 V 230 V 230 V 230 V W 115 184 230 115...

 Open the catalog to page 2
Econ-3

01/09 Technical Modifications Reserved page 3 Econ control functions: Accessories for Econ air curtains Valve: according to the customer´s request it is possible to deliver 2-way or 3-way-valve. Control head of the valve can be either self-acting (thermostatic) or electrothermic. Electrothermic head of the valve must be connected into the electronic placed in the unit and it is necessary to connect the thermostat. All valves are delivered as loose – uninbuilt, due to space reasons. Control: Econ Control description: the control is intended for fan and heater regulation (water heated and also...

 Open the catalog to page 3
Econ-4

170,0 29,5 20,5 964,0 / 1464 / 1964 20,5 239,0 R4,5 110,0 53,0 640 / 1140 / 1640 182,5 182,5 9,0 239 34 228 246 293 Tablet of cables and protection for water heated models FA1 1 X 10A/C WL1 3Cx 1,5 (2,5) FA2 See tablet. EO WL2 See tablet. EO FA3 See tablet. EO WL3 See tablet. EO Tablet of cables and protection for electric heated models (EO) Electric heater cable (WL2) circuit breaker (FA2) cable (WL3) circuit breaker (FA3) 2,5 kW / 230 V 3C x 4 1 x 16 A/B - - 2,5 kW 5C x 4 3 x 16 A/B - - 5 kW 5C x 4 3 x 16 A/B 5C x 4 3 x 16A/B 7,5 kW 5C x 4 3 x 16 A/B 5C x 4 3 x 16A/B 9 kW 5C x 2,5 3 x 10 A/B...