Catalog excerpts
Partial Discharge Coupling Capacitor 12kV rms / 1000pF Nominal Voltage 12kVrms Build in Quadrupole with voltage reference output Build in Overvoltage Protection Capacitive floating Signal output to avoid Eddy Current Loops General Description Hydro Generators Turbo Generators Windmills Industrial Motors The 1000pF coupling capacitor is a sensor used for online and offline partial discharge measurements on rotating machines. The sensor will be usually installed at the busbar or on the high voltage terminals of the rotating machine. Permanent or temporary partial discharge detectors / analyzers can be connected via standard RG58 BNC cables to the coupler, usually by using a termination and safety box in between. The PDC12-1000 has an M12 High Voltage Terminal to connect the coupler to the high voltage terminal. The cable is usually connected via cable lugs to the high voltage busbars of the rotating machine to pickup partial discharge signals without any loss. A specially designed measurement impedance located in the base of the sensor allows to pick up partial discharge signals as well as the line frequency (1:2000). This allows to transfer partial discharge signals and line frequency signal over the same cable to the partial discharge detector. The Signal output is protected via 90V surge arrestor. The ’shield’ of the coaxial output is capacitive floating through a 1uF Capacitor to avoid eddy currents in the signal cables due to high magnetic fields. Ordering Information Order Code: 3x PDC12-1000, 1x TB-004, 100m Coax 6x BNC Crimp on Connectors, Installation Kit 4x PDC12-1000, 1x TB-004, 100m Coax 8x BNC Crimp on Connectors, Installation Kit Termination boxes (t): (0) TB-004, (1) TBS-003, (2) TBS-004, (3) TB-006, (4) TB-016, (x) custom Add „.h“ marking for halogenfree coaxial cable B58 (e.g. 18.3175.1000.t.h)
Open the catalog to page 1Partial Discharge Coupling Capacitor 12kV rms / 1000pF Technical Data Electrical ___________________________________________________________________ Nominal Voltage: Capacitance: Frequency Range: Withstand Voltage (1min): Lightning Impulse Withstand (BIL): (1.2/50us, 10p / 10n) PD Level @ Un: Voltage Divider: Signal Output Type: Ground Connection: Operating Temperature Range: -20 .. +125°C Mechanical Mounting / Fixing: Electrical Connection: Sparks Instruments reserves the right, without further notice, to change the product specifications and/or the information on this document to improve...
Open the catalog to page 2All Sparks Instruments SA catalogs and technical brochures
-
Partial Discharge Brochure
8 Pages