Overview
The RLSwitcher® is a reactor switching device designed for use in electrical systems with voltage ratings between 38 kV and 72.5 kV. It is engineered to switch reactors with confidence and certainty, minimizing the risk of re-ignitions that can damage the system and reduce the lifespan of the reactor and switching device.
Benefits- Patented interrupter design reduces the probability and magnitude of re-ignitions.
- Decreases turn-to-turn voltage stress on reactor windings.
- Simplified and compact design enhances reliability and allows installation in tight spaces.
- Equipped with local and remote gas monitoring systems.
Specifications- Maximum Voltage Ratings: 38 kV to 72.5 kV.
- Reactor Switching Current Rating: 38 kV – 1600 A, 72.5 kV – 539 A.
- Maximum Shunt Reactor Rating: 38 kV – 105 Mvar, 72.5 kV – 67 Mvar.
- Primary Fault Interrupting Ratings: 38 kV – 25 kA, 72.5 kV – 36 kA.
- Fault Close Rating: 25 kA and 36 kA.
Key Features- Low probability of re-ignitions, with low magnitude if they occur.
- Operates with SF6 gas for making and breaking circuits.
- Single mechanism spring-open, spring-close for reliable performance.
- Ships fully assembled to reduce installation time.
- Local visual indication of gas pressure with a color-coded, temperature-compensated gas gauge.
- Common gas system with gas density switch for remote status monitoring.
- 5-year warranty for trouble-free operation.
Additional Ratings- Continuous Current Rating: 38 kV – 1600 A, 72.5 kV – 1200 A.
- Power Frequency: 50/60 Hz.
- BIL (Basic Insulation Level): 38 kV – 200 kV, 72.5 kV – 350 kV.
- Short Circuit Breaking Current: 38 kV – 25 kA, 72.5 kV – 36 kA.
- Interrupting Time: 38 kV – 5 cycles, 72.5 kV – 3 cycles.
- Short-Time Withstand: 38 kV – 25 kA (3 sec), 72.5 kV – 40 kA (3 sec).
- Short-Circuit Making: 38 kV – 25 kA, 72.5 kV – 40 kA.
- Peak Withstand: 38 kV – 62.5 kA, 72.5 kV – 104 kA.
- Insulator Design: Porcelain.
- Ambient Temperature Range: 38 kV – -40º C to +50º C, 72.5 kV – -30º C to +50º C.