Overview: The document provides technical specifications and features of the Southern States LLS®-II load and line switchers, designed for high voltage switching applications. These switchers are compatible with various vertical break
disconnect switches and offer robust performance for load breaking, line dropping, and loop splitting.
Specifications:- Voltage Ratings: 72.5 kV to 245 kV
- Load Breaking Capability: Up to 3000 A
- Line Dropping Capability: Up to 300 A
- Loop Splitting Capability: Up to 3000 A
- Full Load Operations: Rated for 2000 operations
- Ambient Temperature Range: Standard -40º C to +50º C, Optional -50º C to +50º C
Key Features:- Single gap SF6 puffer interrupters for disturbance-free switching
- Visual dielectric indication with a color-coded, temperature-compensated gas density gauge
- Fully pressurized shipment to eliminate field filling
- Simple toggle mechanism for low operating effort
- Composite interrupter housing for reduced weight and UV resistance
- High potential testing not required upon receipt or periodically
- Mountable on various configurations of vertical break switches
- 5-year warranty for reliable operation
Applications: Suitable for load breaking, line dropping, loop splitting,
transformer magnetizing current interrupting, cable dropping, bus dropping, and reactor switching.
Contact Information: Southern States, LLC, 30 Georgia Avenue, Hampton, GA 30228, Email:
[email protected], Phone: 770-946-4562, Website: www.southernstatesLLC.com