GUARD

GUARD
1 / 19 PagesView full catalog

GUARD

Product catalog summary
Purpose of the Device
The air curtain is designed for moderate and cold climates, maintaining indoor temperatures between -10 to +40°C. It prevents heat loss in winter and blocks hot air and pollutants in summer. It is suitable for large spaces like supermarkets and showrooms, with a required mounting height of 4 meters.
Basic Technical Parameters
Noise levels are specified at a 3-meter distance in open spaces.
Heat Output Ranges
There are two types of air curtains: those with water heaters (GUARD 100-150-200 W) and those with electric heaters (GUARD 100-150-200 E). Electric heaters use PTC coils, offering benefits like lower coil temperatures, automatic heat control, and reduced energy consumption.
General and Safety Principles
The air curtains comply with quality and safety standards. Key safety instructions include avoiding use in flammable environments, ensuring proper grounding, and disconnecting power before maintenance. Installation must be performed by a qualified electrician.
Installation
Installation considerations include ease of access for servicing and proximity to water and electricity supplies. The curtain can be mounted horizontally or vertically, ensuring no blockage of inlets and outlets. Proper leveling is crucial to avoid damage.
Control Panel
The COMFORT control panel manages airflow and temperature. It should be installed outside the airflow zone and can control up to two curtains.
GUARD Door Switch
This optional component allows the curtain to switch on/off based on door movement. It includes a relay cabinet and reed relay for indoor installation.
Diagrams of Electrical Connections
Electrical connections must comply with building codes and be performed by qualified personnel. The document provides diagrams for connecting single and multiple curtains to the COMFORT panel, detailing power supply requirements and control panel connections.
Connection and Operation
The GUARD air curtain can be used in cold curtain mode by switching off the electric heater. This requires a simple power cut-off installation using an on/off switch between the Comfort Panel and the GUARD curtain. The BMS communication module allows monitoring and control of the curtain via digital signals, enabling integration with any BMS master protocol.
Maintenance
The engine and fan are maintenance-free, but regular check-ups are recommended. The heat exchanger should be cleaned systematically, especially before the heating period, using compressed air. Anti-freeze liquid must be added to the water system if temperatures drop below 0°C.
Troubleshooting
Common issues include no heating or fan operation due to power supply problems, fan damage, or switch issues. Solutions involve checking power connections, replacing damaged components, and ensuring proper sealing of the heating system.
Guarantee Terms
The warranty covers material defects for 24 months from delivery. It excludes damages from improper use, installation errors, and natural disasters. Warranty services must be conducted by qualified personnel and documented in the Guarantee Card.
Complaint Procedure
Complaints should be lodged with the Distributor, and repairs are conducted on-site. Necessary documents include a complaint form, Guarantee Card, and proof of purchase. Costs for unjustified complaints will be charged to the customer.
See more

Catalog excerpts

GUARD-1

Operation and Maintenance Documentation SONNIGER Polska Sp. z o.o. Sp.K. ul. Śląska 35/37, 81-310 Gdynia, Poland, infolinia 801 055 155, tel. + 48 58 785 34 80, www.sonniger.com Sąd Rejonowy Gdańsk-Północ, VIII Wydział Gospodarczy Krajowego Rejestru Sądowego, KRS 0000504509, NIP 586 227 35 14,Regon 22154369 kapitał zakładowy: 1.655.

 Open the catalog to page 1
GUARD-2

Technical manual air curtain GUARD v201709 1. PURPOSE OF THE DEVICE The air curtain is intended to be used in regions with a moderate and cold climate, in spaces where temperature ranges from -10 to +40°C, in conditions free from external factors such as pollens and hydrometeor (horizontal precipitation). In winter, air curtains protect against heat loss in rooms by directing an airstream accross the entrancy way and preventing cold air from entering the heated space.. In summer, the curtains may be used as cooling devices preventing the entry of hot air and pollutants from outside. The GUARD...

 Open the catalog to page 2
GUARD-3

Technical manual air curtain GUARD v201709 GUARD 100-150-200 E Air curtains with electric heater GUARD E series (with electric heater) are based on a new type of PTC electric coils It is a modern and safe solution, additonal advantages of PTC heaters 91 Lack of voltage on surface of electric coil t» Significantly lower coil temperature in comparison to old type of electric heaters (e.g. heating wires, spirals) 91 Large heat exchange surface (surface of contact of the heat exchanger with heated air) 91 Fully automatic heat control depending on air flow 91 Complete elimination of the risk of system...

 Open the catalog to page 3
GUARD-4

Technical manual air curtain GUARD v201709 4. GENERAL AND SAFETY PRINCIPLES The GUARD air curtains are manufactured in compliance with the rules and standards concerning quality, ecology, utility and work comfort . Before starting the device be sure to read the Manual carefully. The GUARD air curtains are delivered ready-to-use in a cardboard package that is to protect from any mechanical damages. The package consists of: the device, the Manual (Operation and Maintenance Documentation) and the Guarantee. If the optional automatic control ordered, it shall be delivered in a separate package. Make...

 Open the catalog to page 4
GUARD-5

Technical manual air curtain GUARD v201709 5. INSTALLATION When deciding on the air curtain position you should take into account such factors as: ffl Ease of access for servicing, Access to water and electricity supplies It is recommended to install the air curtain in position above the entrance opening, on the wall or under the ceiling, on support pins or horizontal mounting brackets. It is also possible to mount it vertically to a wall or other structure using vertical mounting brackets. It's important to make sure that the unit is properly levelled. In case of positioning in a different way...

 Open the catalog to page 5
GUARD-6

Technical manual air curtain GUARD v201709 It is important to note that the minimum distance between the device and the ceiling is not less than 150 mm. This will ensure easy access to the water exchanger spigots, cable entries as well as free air flow to the inlet grille. Wall installation by means of a horizontal brackets The curtain can be mounted to the wall in a horizontal position using 2 mounting brackets to the horizontal system. In the brackets there are 09mm holes for M8 screws. In the EPP housing, drill holes 0 12-13mm in front of existing holes in the steel intake grille. The exact...

 Open the catalog to page 6
GUARD-7

Technical manual air curtain GUARD v201709 Installation using brackets for vertical mounting It is also possible to install the unit vertically with the engine downwards and upwards. Two vertical mounts are used for this purpose. In the brackets there are 09mm holes for M8 screws. In the EPP housing, drill holes 0 12-13mm in front of existing holes in the steel intake grille. The exact location is indicated by_special tags on the EPP housing and the figure below. Then insert the spacer sleeves into the holes and fix the brackets. Screw the remaining screws into the nuts under the steel intake...

 Open the catalog to page 7
GUARD-8

Technical manual air curtain GUARD v201709 It is important to note that the minimum distance between the unit and the floor for installation with engine at the bottom is not less than 100mm. This allows access to the electrical terminal strip and to the water exchanger vent. Connection of heating medium The connection of the heating medium to the heat curtain, using G 1/2" threaded connections, should be made on the basis of a design by an authorized designer. If the air curtain is connected to a district heating network without a mixing unit, a water filter is required. In case of horizontal...

 Open the catalog to page 8
GUARD-9

Technical manual air curtain GUARD v201709 6. CONTROL PANEL The curtain control is done by using the COMFORT control panel, which allows to adjust the flow and air temperature. The control panel should be located outside the curtain airflow zone. Up to 2 GUARD curtains can be connected to one COMFORT panel. Description of the COMFORT control panel switches ON/OFF – switching on/off of the machine I-II-III – fan gear switches, COMFORT terminal strip clamps clamp 8 - high speed III clamp 7 - middle speed II clamp 6 - low speed I HEAT - when the room temperature is lower than the set value, the...

 Open the catalog to page 9
GUARD-10

Technical manual air curtain GUARD v201709 8. DIAGRAMS OF ELECTRICAL CONNECTIONS The electrical network to which the curtain will be connected should provide protection against overheating and short circuiting. It is necessary to protect the air curtain by grounding. Electrical installation and connection to the air curtain must be in accordance with applicable building codes and regulations, electrical connection should be carried out by a qualified person familiar with the above instruction. The fan motor has standard internal thermal protection to protect the motor from overheating. The set...

 Open the catalog to page 10
GUARD-11

Technical manual air curtain GUARD v201709 8.3 Diagram of connection of one GUARD 100-150-200 E curtain (electric heater) to the COMFORT panel 400V/50Hz power supply; wire cross section; current protection circuit o min. 5 x 2,5 mm˛ for G100E ; (B16) o min. 5 x 2,5 mm˛ for G150E; (B20) o min. 5 x 4 mm˛ for G200E; (B25) Control Panel COMFORT - 3-speed fan control with thermostat, (OMY 5x 1.0mm˛) 8.4 Diagram of connection of two GUARD 100-150-200 E curtain (electric heater) to one COMFORT panel In the MASTER curtain between the L1-NC terminal, replace the factory-made fuse (C 3.15) with C 6.3 400V...

 Open the catalog to page 11