Sewer monitoring - installation instructions

Sewer monitoring - installation instructions

Sewer monitoring - installation instructions

Product catalog summary
Components
  • GaugerGSM
  • Mechanical arm
  • Battery pack
  • Programmable Timer Switch (PTS)
  • Cables
Arm Types
The arm must securely hold the sensor above the sewage pipe/tunnel and allow precise placement. Options include fixed or stretchable length, with a rotating swivel for narrow manholes. Material should be non-corrosive, like stainless steel.
Vertical Placement of Sensor
  • Sewage Monitoring Applications: Position GaugerGSM 15cm above the highest expected sewage level with a beam angle of 15° or more.
  • Overflow Alert Applications: Place GaugerGSM as high as possible below the manhole cover. Refer to the user manual for configuration.
  • For poor cellular reception, install an external GSM antenna near the manhole cover.
  • Locate the battery pack near the manhole cover for easy replacement.
Horizontal Placement of Sensor
Position the sensor above the middle of the sewer pipe or tunnel. At junctions, place it over the widest sewage cross-section. Avoid torrents, wavy waters, or waterfalls.
Installation Steps
  1. Drill holes to fix the arm.
  2. Connect the arm.
  3. Prepare or order cables of appropriate length for connections. Ensure the battery pack cable allows for easy removal.
  4. Treat cables against pests using pesticides or conduits.
  5. Connect the battery pack, PTS, and GaugerGSM outside the manhole. Configure and test the system before installation.
  6. Test the complete system, including the control center.
Final Assembly Examples
Illustrations or examples of the final assembly are provided to guide the installation process.
See more

Catalog excerpts

Sewer monitoring - installation instructions-1

_____________________________________________________________________________________ Solid Applied Technology Ltd www.SolidAT.com 40, Hutzot Hayozer St. Ashkelon 78170, Israel [email protected] Tel: (972-8)6744051 1 Fax: (972-8)6744032 Installation of GaugerGSM systems within sewers 1. Components 1.1 GaugerGSM 1.2 Mechanical arm 1.3 Battery pack 1.4 Programmable Timer Switch (PTS) 1.5 Cables 2. Arm types The arm should hold the sensor at a fixed and robust location. The arm should also allow fine placement of the sensor right above the sewage pipe/tunnel. Arms may be of fixed length or of stretchable length. The arms may also have a rotating horizontal swivel option. The swivel option is required in cases where the sewer manhole is narrow and an upright fixed arm prevents human entry into the sewer. The arm should be produced from non-corrosive material such as stainless steel.

 Open the catalog to page 1
Sewer monitoring - installation instructions-2

_____________________________________________________________________________________ Solid Applied Technology Ltd www.SolidAT.com 40, Hutzot Hayozer St. Ashkelon 78170, Israel [email protected] Tel: (972-8)6744051 2 Fax: (972-8)6744032 2. Vertical placement of sensor 2.1 Sewage monitoring applications GaugerGSM should be located as close as practical to the measured sewage level but preferably 15cm above the highest expected sewage level. Preferably, the beam angle (see picture below) should be 15 or more. 2.2 Overflow alert applications GaugerGSM should be located as high as possible below the...

 Open the catalog to page 2
Sewer monitoring - installation instructions-3

_____________________________________________________________________________________ Solid Applied Technology Ltd www.SolidAT.com 40, Hutzot Hayozer St. Ashkelon 78170, Israel [email protected] Tel: (972-8)6744051 3 Fax: (972-8)6744032 The battery pack may be installed on the arm, on the side ladder or on a dedicated shelf. 3. Horizontal placement of sensor The sensor should be located right above the middle of the sewer internal pipe or tunnel. For sewer junctions, the sensor should be located right on top of the widest sewage cross section. Avoid placing the sensor above torrents or wavy waters...

 Open the catalog to page 3
Sewer monitoring - installation instructions-4

_____________________________________________________________________________________ Solid Applied Technology Ltd www.SolidAT.com 40, Hutzot Hayozer St. Ashkelon 78170, Israel [email protected] Tel: (972-8)6744051 4 Fax: (972-8)6744032 4.2 Connect the arm 4.3 Prepare, or pre-order from the SolidAT, cables of the correct length for the connection between the battery pack, PTS and GaugerGSM. Make sure that the battery pack cable is long enough to allow pulling out the battery pack out of the manhole for battery replacement. 4.4 Cables should be treated to against mice and similar creature. Treatment...