TD-MIXVENT HEATING System
8Pages

{{requestButtons}}

Catalog excerpts

TD-MIXVENT HEATING System - 1

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System TD-MIXVENT fan (from model 250) and a MBE electric heater installed on the discharge side of the fan. MBE heater type - Insulated element rods. - Automatic overheat thermostat wired in series with an additional safety overheat manual reset thermostat (RESET). Units are available for single phase (models 100, 125 and 160) or three phase (other models) electrical supply connection, with a circuit protection supplied on 230V single phase. - Connection box IP43. A range of duct or ambient temperature sensors and controllers accessories to accompany the electric heater are available. These controller accessories modulate the heater output as a function of the required environmental temperature. With this system it is possible to achieve temperature rise up to 50º on the supply air. MBE electric heater (installed on the discharge side of the fan). TD-MIXVENT + MBE ELECTRIC HEATER In those installations where MIXVENT HEATING system is required it is convenient to use filter boxes MFL to protect the electric heaters from the debris. MBE - Temperature difference between extracted air and new air ∆T (ºC) 00 In-Line duct fans MIXVENT HEATING SYSTEM

Open the catalog to page 1
TD-MIXVENT HEATING System - 2

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System TECHNICAL CHARACTERISTICS MBE TD-MIXVENT SELECTION EXAMPLE Speed controller type PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER PULSER TTC-25/TTC-2000 PULSER PULSER PULSER PULSER PULSER TTC-25/TTC-2000 PULSER PULSER TTC-25/TTC-2000 TTC-25/TTC-2000 TTC-25/TTC-2000 PULSER TTC-25/TTC-2000 TTC-25/TTC-2000 TTC-25/TTC-2000 TTC-40F PULSER TTC-25/TTC-2000 TTC-25/TTC-2000 TTC-25/TTC-2000 TTC-40F DATA: – Airflow: 700 m3/h (Q) – Input air temperature: +5 ºC – Required output temperature: +27...

Open the catalog to page 2
TD-MIXVENT HEATING System - 3

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System TD-MIXVENT fan (from model 250) and a MBE-R electric heater installed on the discharge side of the fan. MBE-R electric heater (installed on the discharge side of the fan). TD-MIXVENT + MBE-R ELECTRIC HEATER MBE-R heater type - Electric heater regulation, incorporated. - Insulated element rods. - Automatic overheat thermostat wired in series with an additional safety overheat manual reset thermostat (RESET). Units are available for single phase (models 100, 125 and 160) or three phase (other models) electrical supply...

Open the catalog to page 3
TD-MIXVENT HEATING System - 4

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System TECHNICAL CHARACTERISTICS MBE-R TD-MIXVENT SELECTION EXAMPLE DATA: – Airflow: 700 m3/h (Q) – Input air temperature: +5 ºC – Required output temperature: +27 ºC REQUIRED HEAT POWER: P Q x 0,36 x DT = 700 x 0,36 x 22 = 5544 W = HEATER ELECTION: or: MBE-200/50T-R or: MBE-250/60T-R Final election will depend of: – Total pressure drop – Desired sound level – Available space MBE-R ELECTRIC HEATERS ACCESSORIES For more information see Electrical accessories. TG-R Room temperature sensor. TG-K Duct temperature sensor. DPS...

Open the catalog to page 4
TD-MIXVENT HEATING System - 5

IN LINE MIXED FLOW DUCT FANS AND HOT WATER COIL TD-MIXVENT HEATING System TD-MIXVENT + MBW WATER COIL TD-MIXVENT fan (from model 250) and a MBW water coil installed on the discharge side of the fan. MBW water coil type - Range of connection diameters, 100 - 500 mm. - Galvanised steel housing. - Hot water coil with copper pipes and aluminium fins. - Removable side for maintenance purposes. - Can be mounted horizontally or vertically. - Connections with watertight seals. - Connection must be made between the coil and the hot water circuit. - Maximum pressure: 10 bar. - Maximum temperature:...

Open the catalog to page 5
TD-MIXVENT HEATING System - 6

In-Line duct fans MIXVENT HE

Open the catalog to page 6
TD-MIXVENT HEATING System - 7

IN LINE MIXED FLOW DUCT FANS AND HOT WATER COIL TD-MIXVENT HEATING System DIMENSIONS (mm) MBW ACCESSORIES FOR MBW WATER COIL TRW Temperature control unit. THE-F Thermostat with capillary tube anti-frost sensor. In-Line duct fans MIXVENT HEATING SYSTEM

Open the catalog to page 7
TD-MIXVENT HEATING System - 8

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT FILTER System TD-MIXVENT + FILTER BOX MFL-G4 The MIXVENT HEATING system consists on a MFL filtration box installed on the inlet side of the TD-MIXVENT fan and are used when the installation requires supplying filtered clean air. MFL filtration boxes are of EU4 grade filtration and are designed for direct connection with standard circular ducting. A usual application of MFL filtration boxes is to protect the electric heaters from the dirt, in installations where MIXVENT HEATING system is used. The MFL filtration boxes are supplied...

Open the catalog to page 8

All Soler & Palau catalogs and technical brochures

  1. EB-N Series

    2 Pages

  2. TPSB Series

    6 Pages

  3. TD-EVO Series

    11 Pages

  4. SILENT

    9 Pages

  5. SILENT DUAL

    6 Pages