Overview: The HGHT-V Series is a range of roof-mounted axial flow fans designed for air extraction, particularly effective in smoke extraction during fire conditions. These fans are certified F400-120 and F300-120, indicating their capability to operate under high temperatures for specified durations.
Specifications: The fans feature a casing made from rolled sheet steel with a corrosion-resistant galvanized finish. The blades are high-grade die-cast aluminum, and the hub is pressed sheet steel. They include a backdraft shutter and proof guard at the discharge.
Motor Details: The series includes three-phase 4-pole motors with IP55 protection and class H insulation, operating at 400V-50Hz. Options for higher power and two-speed motors are available. An electrical isolator is fitted to the fan casing.
Configurations and Options: Standard air direction is in form (A) configuration, with the motor over the impeller. Optional configurations include 6-pole motors and 2-speed motors with 4/6 and 4/8 poles. Additional features include an outlet guard, support base, inlet flange, and web support for model 1250.
Technical Characteristics: Detailed technical specifications are provided for various models, including diameter, motor power, full load current, and weight. Models are categorized under F400 and F300 standards, with specific details for 4, 6, and 8 pole configurations.
Applications: These fans are suitable for specific applications such as car parks and are officially approved to the EN12101-3 standard, ensuring compliance with safety and performance requirements.
Dimensions: The document includes dimensions for different models, specifying measurements such as diameter and length for installation purposes.
Mounting Accessories: The document lists various mounting accessories, including:
  • ARO BRIDA: Matching flange for secure mounting.
  • DEF.ASP.TGT/THGT: Inlet guard for safety.
  • SIL CZ and SIL CZO: Circular silencers, with SIL CZO including an acoustic pod for noise reduction.
  • ACOPEL F400 N: Circular flexible connector, certified F400-120 for fire resistance.
  • EMB: Bellmouth with guard for airflow optimization.
Mounting Solutions: Includes the JBS-V flat roof up stand designed for mounting fans on horizontal roofs without existing up stands. It includes internal insulation to prevent condensation and is supplied with screws and a gasket for weather sealing. Detailed dimensions for JBS-V models (800, 900, 1000, 1250) are provided.
Conclusion: The document serves as a comprehensive guide for selecting and installing HGHT-V series fans, providing essential specifications and compatible accessories to ensure optimal performance and installation efficiency.
See more

Catalog excerpts

HGHT-V Series-1

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series Range of roof mounted axial flow fans, with vertical air discharge configuration, for air extract. Designed for smoke extraction in fi re conditions and certified F400-120 and F300-120 (HGHT-V - CE marked). Casing formed from rolled sheet steel welded on the base with a corrosion resistant hot dipped galvanized finish. High grade die-cast aluminum blades locked within a pressed sheet steel hub. Backdraft shutter and proof guard at the fan discharge. Cylindrical casing formed from rolled sheet steel protected against corrosion by grey polyester paint coating. Motors - HGHT-V F400-120: three-phase 4 pole motors 400V-50Hz, IP55, class H insulation. - HGHT-V: F300-120: three-phase 4 pole motors 400V-50Hz, IP55, class H insulation. - Electrical isolator fitted to fan casing. Three phase 230/400V-50Hz up to 3 kW. Three phase 400V-50Hz, for higher power motors and two speed motors. (See characteristics chart). Additional Information Standard air direction: form (A) configuration (Motor over impeller). On request - 6 pole motors. - 2 speed motors 4/6 and 4/8 poles. Specific applications Isolator Electrical isolator. Outlet guard Outlet guard protection. Support base Base for roof installation. Inlet flange Flange for duct connection or bellmouth inlet. Form (A) configuration Standard air direction: form (A) configuration (Motor over impeller). Web support To strengthen base support. Model 1250 only. Officially approved to EN12101-3 standard. Certificate nº 0370-CPD-0909 Officially approved to EN12101-3 standard. Certificate nº 0370-CPD-0923 Back draft shutter Prevent back draft of air and entrance of rain water when the fan is switched off. Roof mounted fans HGHT-V

 Open the catalog to page 1
HGHT-V Series-2

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series TECHNICAL CHARACTERISTICS Before installation check that the product electrical characteristics listed on the data plate label (voltage, power, frequency, etc.) match those of the intended electrical supply. TECHNICAL CHARACTERISTICS - F400 - 4 POLES Diameter (mm) Motor power Full load current at 400V (A) Motor power Full load current at 400V (A) TECHNICAL CHARACTERISTICS - F400 120 - 4/8 POLES Diameter Motor power (mm) Full load current 400V (A) Diameter Motor power (mm) Full load current 400V (A) HS Roof mounted fans HGHT-V

 Open the catalog to page 2
HGHT-V Series-3

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series TECHNICAL CHARACTERISTICS - F400 120 - 4/8 POLES (CONTINUATION) Diameter Motor power (mm) HS Full load current 400V (A) HS Diameter Motor power (mm) Full load current 400V (A) HS TECHNICAL CHARACTERISTICS - F400 120 - 4/6 POLES Diameter Motor power (mm) Full load current 400V (A) Diameter Motor power (mm) Full load current 400V (A) HS Roof mounted fans HGHT-V

 Open the catalog to page 3
HGHT-V Series-4

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series TECHNICAL CHARACTERISTICS - F400 120 - 4/6 POLES (CONTINUATION) Diameter Motor power (mm) Full load current 400V (A) TECHNICAL CHARACTERISTICS - F300 - 4 POLES Model Motor power Full load current at 400V (A) Motor power Full load current at 400V (A) Roof mounted fans HGHT-V

 Open the catalog to page 4
HGHT-V Series-5

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series TECHNICAL CHARACTERISTICS - F300 120 - 4/8 POLES Diameter Motor power (mm) Full load current 400V (A) Diameter Motor power (mm) HS Full load current 400V (A) HS Full load current 400V (A) TECHNICAL CHARACTERISTICS - F300 120 - 4/6 POLES Diameter Motor power (mm) HS Full load current 400V (A) HS Diameter Motor power (mm) Roof mounted fans HGHT-V

 Open the catalog to page 5
HGHT-V Series-6

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series TECHNICAL CHARACTERISTICS - F300 120 - 4/6 POLES (CONTINUATION) Diameter Motor power (mm) Full load current 400V (A) HS Diameter Motor power (mm) Full load current 400V (A) HS Roof mounted fans HGHT-V

 Open the catalog to page 6
HGHT-V Series-7

ROOF MOUNTED AXIAL FLOW FANS HGHT-V Series MOUNTING ACCESSORIES JBS -V Flat roof up stand - For mounting a fan on a flat roof without up stands. - For use on horizontal roofs. - Internal insulation to prevent condensation. - Supplied with screws and gasket for a complete weather seal. Matching Flange Inlet bellmouth Flexible connector Inlet guard Circular sound attenuator Attenuator with acoustic pod ARO BRIDA TGT/ THGT- 800 N ARO BRIDA TGT/ THGT- 900 N ARO BRIDA TGT/ THGT- 1000 N ARO BRIDA TGT/ THGT- 1250 N ACOPEL F400-800/300 N ACOPEL F400-900/300 N ACOPEL F400-1000/300 N ACOPEL F400-1250/300...

 Open the catalog to page 7

All Soler & Palau catalogs and technical brochures

  1. EB-N Series

    2  Pages

  2. TPSB Series

    6  Pages

  3. TD-EVO Series

    11  Pages

  4. SILENT DESIGN

    9  Pages

  5. SILENT

    9  Pages

  6. SILENT DUAL

    6  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.