Product Overview
The BASICEVO Infrared Gas Sensor is designed for detecting Dichlorotrifluoroethane R123 with a measurement range of 0 to 2000 ppm. It is pre-calibrated, features low drift, and operates with a supply voltage of 3.3 to 6 V DC. The sensor supports Modbus ASCII or RTU communication and provides status indication via LED.

Applications
This sensor is suitable for use in hotel air conditioning, food storage rooms, industrial refrigeration, food transport, and research.

Available Equipment
Additional equipment includes a connect interface, wall mount enclosure, calibration software, and mounting equipment. It is also available as a complete transmitter.

General Features
The sensor uses a Non-Dispersive Infra-Red (NDIR) dual wavelength measurement principle. It has a compact design with dimensions of 62 mm x 37 mm x 30 mm. The warm-up time is less than 2 minutes for start-up, less than 11 minutes for fade-in, and less than 30 minutes for full specification.

Measuring Response
The response time (t90) is approximately 60 seconds, with a digital resolution of 1 ppm. The detection limit is ≤ 10 ppm, repeatability is ≤ ± 20 ppm, and linearity error is ≤ ± 30 ppm. Long-term stability is ≤ ± 30 ppm for zero and ≤ ± 40 ppm for span over a 12-month period.

Influence of Temperature, Pressure, and Flow Rate
Temperature dependence for zero is ≤ ± 3 ppm per °C and for span is ≤ ± 6 ppm per °C. Pressure dependence is +0.100% of the actual reading per hPa.

Electrical Parameters
The sensor requires a supply voltage of 3.3 to 6.0 VDC, with a peak supply current of <400 mA at 3.3 V and <240 mA at 5.0 V. Inrush current is <450 mA, and average power consumption is <800 mW. It outputs a digital signal via Modbus ASCII/RTU.

Climatic Conditions
Operating temperature ranges from -20 to +40 °C, with a storage temperature range of -20 to +60 °C. It operates under air pressure of 800 to 1150 hPa and ambient humidity of 0 to 95% relative humidity (non-condensing).

Additional Information
All specifications are subject to change without notice. Recalibration is recommended at first initiation and periodically depending on application and ambient conditions. For more information, visit the smartGAS website or contact their sales team.
See more

Catalog excerpts

B3-732205-03000-1

BASICEVO Infrared gas Sensor Dichlorotrifluoroethane R123 2000 ppm smartGAS item number: B3-732205-03000 Pre calibrated Low drift Gas entry by diffusion 3.3 - 6 V DC supply voltage Modbus ASCII or RTU Status indication by LED Application examples Hotel air conditioning Food storage rooms Industrial Refrigeration Food Transport Research Available equipment Connect Interface Wall mount enclosure Calibration software Mounting equipment smartGAS Mikrosensorik GmbH I Huenderstr. 1 I 74080 Heilbronn I Germany T +49 7131 797553-0 I F +49 7131 797553-10 I [email protected] I www.smartgas.eu Available design in support Mechanical installation Data communication also, as complete Transmitter

 Open the catalog to page 1
B3-732205-03000-2

BASICEVO I Dichlorotrifluoroethane R123 I B3-732205-03000 General features Measurement principle: Non Dispersive Infra-Red (NDIR), dual wavelength Measurement range: 0 … 2000 ppm Full Scale (FS) by diffusion (atmospheric pressure) Gas supply: Mounting dimensions: Warm-up time: 62 mm x 37 mm x 30 mm (L x W x H) < 2 minutes (start up time) < 11 minutes (fade in finished) < 30 minutes (full specification) Measuring response* Response time (t90): Digital resolution: Linearity error (straight line deviation): Long term stability (zero): ≤ ± 30 ppm over 12 month period Long term stability (span): ≤...

 Open the catalog to page 2

All SmartGAS Mikrosensorik GmbH catalogs and technical brochures

  1. Ethylene C2H4

    2  Pages

  2. PAS

    4  Pages

  3. SILAREX

    4  Pages

  4. FLOW EVO

    2  Pages

  5. ANAREX

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.