Balanced Pressure Proportioner Mk 2
1 / 2Pages

Catalog excerpts

Balanced Pressure Proportioner Mk 2 - 2

Page 2 of 2 (replaces datasheets 1010/19, 23 and 40) Operation The proportioner will operate automatically whenthe flows and pressure are within the flow range. The foam pressure must be at least one bar higher than the water pressure through the proportioner. Operates all valves in the system smoothly. Fitting A minimum of five diameters (D) of straight pipe isrequired in the water line before entering the proportioner and three diameters (D) after the proportioner. Order information - please specify:1. Size 2. Connection: DIN or ANSI 3. Foam concentrate mixing rate (%) PP-150 PP-200/80...