Amik 200
8Pages

{{requestButtons}}

Catalog excerpts

Amik 200 - 1

AMIK 200 / 201 Technical Data Sheet RELIABILITY BEYOND MEASURE AMIK Special Features MODBUS (RS-485) Communication is included on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT Secondary from 100 VLL to 500 VLL L Don’t require PT for the voltage measurement up to 500 ACV t Programmable Energy format & Energy rollover count Wide auxilliary Power Supply which can accept any input between 40V – 300V AC/DC Amik 200/ 201 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters. Parameter System Volts System Current Volts R–N (Phase Voltage for Single phase) Volts Y–N Volts B–N Volts R-Y Volts Y–B Volts B–R Current R (Phase Current for Single phase) Current Y Current B Frequency System Active Power (kW) Active Power R (Phase Power for Single phase) (kW) Active Power Y (kW) Active Power B (kW) System Re-active Power (kVAr) Re-active Power R (Phase Power for Single phase) (kVAr)

Open the catalog to page 1
Amik 200 - 2

Parameter measurement and Display Sr No 19. 20. 21. 22. Parameter Re-active Power Y (kVAr) Re-active Power B (kVAr) System Apparent Power (kVA) Apparent Power R (Phase Power for Single phase) (kVA) Apparent Power Y Apparent Power B System Phase Angle System Power Factor Power Factor R Power Factor Y Power Factor B Phase Angle R Phase Angle Y Phase Angle B Active Energy Import (kWh) Active Energy Export (kWh) Reactive Energy Import (kVArh) Reactive Energy Export (kVArh) Apparent Energy (kVAh) RPM Max (System Voltage / System Current) Min (System Voltage / System Current) Hour Run ON Hour...

Open the catalog to page 2
Amik 200 - 3

Ordering Information Product Code Amik 200 (Without MODBUS) Amik 201 (With MODBUS) System Type Input Voltage Input Current Power Supply With RS 485 (Available only on Amik 201). Without RS 485 (Amik 200) Accessories – Three-Phase Current Transformer A three-phase terminal style current transformer must be used with A M I K three phase meters. The current transformer is equipped with terminals to permit easy connection to the AMI K units. These terminals are #8-32 brass studs and come with a flatwasher, lockwasher and a regular nut (leads are not provided). Ordering Information Catalog...

Open the catalog to page 3
Amik 200 - 4

Application Amik 200/ 201 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters. It measures electrical parameters like AC Voltage, AC Current, Frequency, Active, Reactive, Apparent Power, Import Export Energy & many more. Product Features On site programmable PT / CT ratios It is possible to program primary of external potential Transformer (PT), primary of external Current Transformer (CT) on site via front panel keys by entering into Programming mode. Optional Pulse Output / Limit switch (Relay output) User...

Open the catalog to page 4
Amik 200 - 5

Product Features True RMS measurement The instrument measures distorted wave form up to 15th Harmonic. Energy Measurement Active Energy (kWh), Reactive Energy (kVArh), Apparent Energy (kVAh). Any of the parameters can be assigned to optional Pulse output. (Import & Export) Programmable Energy format & Energy rollover count Burst Surge Customer can assign the format for energy display on MODBUS (RS-485) in terms of W, kW or MW. Additional to this, customer can also set a rollover count from 7 to 14 digits depending on the energy format, after which the energy will roll back to zero. Rated...

Open the catalog to page 5
Amik 200 - 6

Dimension Details Input Voltage With optional MODBUS / Limit switch Nominal input voltage (AC RMS) Phase –Neutral 290V L-N , Line-Line 500V L-L Max continuous input voltage Nominal input voltage burden < 0.3 VA approx. per phase (For external auxiliary meter) System PT secondary values 100VLL to 500VLL programmable on site. 100VLL to 692kVLL System PT primary values programmable on site. Input Current Nominal input current System CT secondary values System CT primary values Max continuous input current Nominal input current burden Auxiliary Supply External Aux Self powered ** input voltage...

Open the catalog to page 6
Amik 200 - 7

Installation Easy Clip in Installation on Panel. Display update rate Easy Clip-in mounting Response time to step input 1 sec approx. Swivel screw Safety Pollution degree Installation category High Voltage Test Panel Thickness : 1 - 3 mm for self clicking, 1 – 6 mm for swivel screws. 4.7 kV DC, for 1 minute between Aux. and measuring inputs Environmental Operating temperature Storage temperature Relative humidity Enclosure Front Dimensions and Weights Bezel size Panel cut-out Overall depth 55 mm.(without output option) Panel Thickness 1 - 3 mm for self clicking, 1 – 6 mm for swivel screws....

Open the catalog to page 7
Amik 200 - 8

Electrical Connections Self Powered Aux 2 3 Phase 4 Wire Unbalanced Load 3 Phase 3 Wire Unbalanced Load *Note: For Measurement of parameters, Voltage must be present between terminal 2 & 11 for single phase or 3 phase 4 wire network and between terminal 2 & 5 or 2 & 8 for 3 phase 3 wire network. Multifunction Meter MODEL : Amik 200 INPUT :500VL-L, 5A/1A, 45-65Hz AUX SUPPLY :40V-300V AC-DC , 3VA SR NO : 11/02/3232 +. AUX. -. ~. ~. 14 13

Open the catalog to page 8

All Simpson catalogs and technical brochures