Electrical Requirements
The IPC requires a supply voltage of +18 to +30 V DC with a maximum current consumption of 5.5 A. The inrush current can reach up to 6 A depending on the load. Without external devices, the current consumption is 0.8 A. The system provides various current outputs for different components, including S-DIAS and S-DVI, with specific maximums. Compliance with UL standards requires SELV/PELV and Limited Energy supply.
KTY Temperature Sensor Specifications
The sensor has three channels with a measurement range of 1367-2980 Ω and operates between -20 to +80 °C. It features a 16-bit converter resolution and a conversion time of 1 ms per channel. The sensor includes a cable break monitor and a low-pass input filter.
Mechanical Dimensions
The IPC 221 measures 218.5 x 110.3 x 77.2 mm and is equipped with a Celeron 1020E processor. It controls S-DIAS modules and includes various interfaces such as VARAN, Ethernet, USB, and more. It features a 7-segment display and status LEDs for CPU status indication.
Performance Data
The IPC is powered by an Intel Celeron 1020E processor and supports multiple bus systems. It includes a 512-Mbyte CompactFlash card for program memory and 256 kbytes of SRAM for data memory. The internal memory is 2-Gbyte DDR3 RAM, expandable to 8 Gbytes, with a 2-Mbyte L3 Cache.
Interfaces
The IPC provides a variety of interfaces including Ethernet, VARAN, CAN, USB, DVI, UART, and S-DIAS, facilitating extensive connectivity options.
Environmental Conditions
The IPC operates within a temperature range of 0 to +50 °C and can be stored between -20 to +85 °C. It is designed for indoor use with a pollution degree of 2 and can operate at altitudes up to 2000 m. It complies with EMC standards for industrial areas and has specific vibration and shock resistance ratings.
See more

Catalog excerpts

IPC 221-1

Performance Data Data buffer The IPC 221 is an industrial PC with a Celeron1020E processor. It is used to control S-DIAS modules and has various interface connections such as: a VARAN Manager with 2 VARAN Out interfaces. A 7-segment display and 3 status LEDs provide information on the actual status of the CPU directly on the IPC. yes (SRAM battery buffered) Status display Status LEDs Real-time clock KTY Temperature Sensor Specifications Number of channels Measurement range A CompactFlash card can be used as program memory. Converter resolution Conversion time per channel Sensor current PC compatible. The IPC works with a standard PC BIOS, where SIGMATEK specific settings can be made. Cable break monitor Input filter Precision of analog channel measurement ±1 % of maximum measurement value Voltage protection Electrical Requirements Performance Data Processor Internal program memory (CompactFlash) 512-Mbyte CompactFlash card (12-610-051, included in delivery) Internal data memory (SRAM) Internal memory (DDR3 RAM) Internal cache Interfaces 256 kbytes (battery powered) 2-Gbyte (SO-DIMM DDR3 1600 MHz) expandable up to 8 Gbytes 2-Mbyte L3 Cache 1x Ethernet1 10/100 (front) 1x Ethernet2 10/100 (front) 2x VARAN Out - Out 1 (front) - Out 2 (side, above the fan housing) 2x CAN 1x USB 2.0 (front) 1x DVI (front) 1x S-DVI (front) 2x UART - RS232 (front) 3x KTY temperature measuring (front) 1x machine EEPROM (for article 12-250-031) (front) 1x S-DIAS Supply voltage Supply voltage Current consumption (maximum total current) Inrush current Supply voltage Current consumption without external devices (+24 V) Current available for S-DIAS (+5 V) Current available for S-DIAS (+24 V) Available current for S-DVI (+24 V) Available current for PCI (+5 V) UL standard maximum 2 A maximum 0.5 A (per USB connection) for UL: must be supplied with SELV / PELV and Limited Energy Article Number and Misecellaneous Article number Standard Project backup 20-450-221 UL 61010-1, UL 61010-2-201 (E247993) internally on CompactFlash card

 Open the catalog to page 1
IPC 221-2

Environmental Conditions Storage temperature Environmental temperature Environmental temperature Maximum processor temperature Operating conditions EMC resistance EMC noise generation Indoor use pollution degree 2 Altitude up to 2000 m in accordance with EN 61000-6-2 (industrial area) in accordance with EN 61000-6-4 (industrial area) Vibration resistance Shock resistance Protection type

 Open the catalog to page 2

All SIGMATEK GmbH & Co KG catalogs and technical brochures

  1. PS 101

    1  Page

  2. CP 731

    1  Page

  3. CP 112

    1  Page

  4. CP 311

    1  Page

  5. CP 312

    1  Page

  6. Remtoe Access

    4  Pages

  7. CP 102

    1  Page

  8. C-IPC 171

    1  Page

  9. PC 521

    1  Page

  10. PC 444-W

    1  Page

  11. PVDM 086

    1  Page

  12. PVDM 087

    1  Page

  13. PVAI 011

    1  Page

  14. SCP 111

    1  Page

  15. SDI 101

    1  Page

  16. STO 081

    1  Page

  17. SDM 081

    2  Pages

  18. SNC 021

    1  Page

  19. SRO 021

    1  Page

  20. SSI 021

    1  Page

  21. SIB 061

    1  Page

  22. ST 151

    2  Pages

  23. DC 061-1

    2  Pages

  24. Smart Factory

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.