1. Catalogs
  2. SIGMA ELEKTRIK
  3. RCCB RESIDUAL CURRENT CIRCUIT BREAKERS

RCCB RESIDUAL CURRENT CIRCUIT BREAKERS
1 /14Pages

RCCB RESIDUAL CURRENT CIRCUIT BREAKERS

RCCB RESIDUAL CURRENT CIRCUIT BREAKERS
1 /14Pages

Catalog excerpts

RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-2

RCCB Residual Current Circuit Breakers General Information Sigma RCCB’s are designed to protect equipment and people from low level ground faults. Typical applications include resistance and impedance heating systems; submersible pumps; semiconductor process equipment and wet location equipment. The RCCBs use the residual current sensing method to detect ground faults. The units monitor the load currents and will trip immediately should they detect any imbalance greater than the rated trip level. Sigma RCCB’s derive the energy required to trip from the ground fault current alone. They will operate...

 Open the catalog to page 2
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-3

Residual Current Circuit Breakers RCCB principle, the residual current behaviour and frequency show an effect upon tripping. When using a device designed for 50/60 Hz in a network with a different frequency, the user must count on a change of the tripping threshold i.e. a change of IΔn Rated conditional short-circuit current Inc – short-circuit strength. The function and design principle does not allow for the residual current circuit breaker use for protection against short-circuit. For circuit protection it is necessary to use a circuit breaker or a fuse. These elements cut the shortcircuited...

 Open the catalog to page 3
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-4

CIRCUIT BREAKERS RESIDUAL CURRENT

 Open the catalog to page 4
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-5

RESIDUAL CURRENT CIRCUIT BREAKERS Working Principle RCCB works on the principle that in an electrical circuit the incoming current is the same as out going current as shown in the diagram. RCCB incorpo- rates a core balance transformer having primary and secondary windings and a sensitive relay for instantaneous detection of fault signal. The primary winding lies in series with the supply mains and load. Secondary winding is connected to a very sensitive relay. In a faultless situtation, the magnetized effects of the current carrying conductors cancel each other out. There is no residual magnetic...

 Open the catalog to page 5
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-6

RCCB Residual Current Circuit Breakers Protective Action While RCCBs for rated fault current I∆n > 30 mA provide protection against indirect contact, the installation of RCCBs with I∆n ≤ 30 mA provides a high level of additional protection against unintentional direct contact with live parts. The above diagram shows the physiological responses in the human body when current flows through it, classified into current ranges. Current/time values in range 4 are dangerous, as they can initiate heart fibrillation which can result in death. The tripping range for RCCBs with rated fault currents of 10...

 Open the catalog to page 6
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-7

RESIDUAL CURRENT CIRCUIT BREAKERS RCCBs may be used in all three distribution network types (DIN VDE 0100 Part 410) and in an IT network system provided that the capacity of the net- work to ground is sufficient to allow a fault current to flow which has the same level as the rated fault current. The IT network can still be monitored using an insulation monitor. Both protective systems do not mutually interfere with one another. Selective Tripping Residual current operated circuit-breakers normally have an instantaneous release. This means that a series connection of such residual current ope-...

 Open the catalog to page 7
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-9

RESIDUAL CURRENT CIRCUIT BREAKERS • Wiring should be done by a trained & qualified electrician as per the wiring diagram. • All wiring necessary for operation shall be passed through the RCCB. • The neutral conductor must be insulated against earth to the same extent as the live conductors. • All equipments used must be properly earthed. • To ensure correct functioning care must be taken that the neutral conductor on the load side of the RCCB must not be connected to earth, otherwise nuisance tripping may occur or tripping may be impaired. • Suitable device either MCB or HRC fuses shall be used...

 Open the catalog to page 9
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-10

RESIDUAL CURRENT CIRCUIT BREAKERS

 Open the catalog to page 10
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-12

Residual Current Circuit Breakers RCCB 2P 30 mA 10 kA RCCB's Type Code No Of Poles Rated Current Rated Residual Current (In) A IΔn (mA) SGM-2 2 25 30 SGM2025030 SGM-2 2 40 30 SGM2040030 SGM-2 2 63 30 SGM2063030 Order code 2P 300 mA 10 kA RCCB's Type Code No Of Poles Rated Current Rated Residual Current (In) A IΔn (mA) SGM-2 2 25 300 SGM2025300 SGM-2 2 40 300 SGM2040300 SGM-2 2 63 300 SGM2063300 Order code 4P 30 mA 10 kA RCCB's Type Code No Of Poles Rated Current Rated Residual Current ( In) A IΔn (mA) SGM-4 4 25 30 SGM4025030 SGM-4 4 40 30 SGM4040030 SGM-4 4 63 30 SGM4063030 Order code 4P 300...

 Open the catalog to page 12
RCCB RESIDUAL CURRENT CIRCUIT BREAKERS-14

Do not risk your safety! Ekşioğlu Mah. Yeni Şile Cad. No:40 34794 Alemdağ - Çekmeköy / İstanbul / TURKEY Tel: +90 216 429 72 01 (pbx) Fax: +90 216 484 41 01 www.sigmaelektrik.com [email protected]

 Open the catalog to page 14

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.