POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIoT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS -1-
Open the catalog to page 1POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS FEATURES • Measurement of 54 power network parameters, including current and voltage harmonics up to 63rd in 1-phase 2-wire or 3-phase 3 or 4-wire balanced and unbalanced systems. • Ethernet Daisy Chain Topology. • Programmable choice of communication protocols: MQTT, BACnet / IP lub MODBUS TCP/IP. • Modern and user-friendly BACnet/IP interface. • High accuracy class (0.2S for active energy). • Graphical color display: LCD 3.5’’ typu TFT, 640 x 480 pixels, fully configurable by a user. • 14 predefined...
Open the catalog to page 2POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS MEASUREMENT AND VISUALIZATION OF POWER NETWORK PARAMETERS • • • • • • • • • • • • phase voltages: U1, U2, U3 phase-to-phase voltages: U12, U23, U31 phase currents I1, I2, I3 active phase powers: P1, P2, P3 reactive phase powers: Q1, Q2, Q3 apparent phase powers: S1, S2, S3 active power factors: PF1, PF2, PF3 reactive/active power factors: tgj1, tgj2, tgj3 active, reactive and apparent 3-phase power: P, Q, S mean 3-phase power factors: PF, tgj frequency f mean 3-phase voltage: US mean phase-to-phase...
Open the catalog to page 3POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS MEASURING RANGE Measured value tr_I - Current transformer ratio = Transformer primary current / Current transformer secondary current tr_U - Voltage transformer ratio = Transformer primary voltage / Voltage transformer secondary voltage
Open the catalog to page 4POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS EXTERNAL FEATURES Readout field graphic color display LCD TFT 3,5’’ , 640 x 480 pixels Overall dimensions Protection grade from frontal side: IP65 from terminal side: IP20 Input signal 0...0.1...1.2 In; 0.1…0.2...1.2 Un for current, voltage, PFi, tgji Power factor Preheating time Ambient temperature without condensation Operating position External magnetic field Short-term overload Admissible crest factor RATED OPERATING CONDITIONS Supply voltage Power consumption Additional error (in % of the...
Open the catalog to page 5POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS DISPLAING OF MEASUREMENT PARAMETERS up to 10 programmable screens (8 parameters per page); ability to change color for all screens Available colors for digital indications: two screens dedicated to harmonics; indication of individual harmonic for voltages and currents (up to 51st); bargraph presentation for all harmonics with zoom function presentation in the form of analog meter view with min/max preview for display value and zoom function Contracted power representation (Max Demand) in W, kW...
Open the catalog to page 6POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS easy to use and intuitive menu; information bar with status of: phase sequence, alarm outputs, temperature measurements, archiving and memory, Ethernet and RS-485 interfaces, time and date *- available depending on the ND31PLUS version METER CONFIGURATION WITH FREE eCON SOFTWARE ability to configure and update ND31 with free eCon software (via RS-485 or Ethernet interface) REMOTE READOUT OF PARAMETERS THROUG ETHERNET: WWW SERVER, FTP WEB server for remote reading of current measurement data; FTP...
Open the catalog to page 7POWER NETWORK METER WITH ETHERNET DAISY CHAIN AND MQTT (IIOT), BACNET/IP OR MODBUS TCP/IP PROTOCOLS ORDERING CODE Meter ND31PLUS 2 relays, 1 analog output (0–20 mA), 2 Pt100 inputs, RS485, dual-port Ethernet, internal file system memory. Input voltage (phase/phase-to-phase) Un: 3 x 57.7/100 V, 3 x 230/400 V Language Polish/English Acceptance tests without additional quality requirements with an extra quality inspection certificate with an extra calibration certificate acc.to customer’s request* Version standard custom-made* * only after agreeing with the manufacturer ORDERING EXAMPLE, the code...