KD6

KD6

KD6

Product catalog summary
Specifications:
The KD6 Screen Recorder supports up to 60 logical channels, with a maximum of 8 analog channels. It features programmable measuring inputs (0, 4, or 8), binary inputs (2 or 6), and digital Modbus RTU master inputs (10 devices up to 10 registers). Outputs include relays (2, 6, or 8), analog outputs (0/4...20mA), a supplying output of 24V DC/30mA, and a digital RS-485 Modbus interface. The device has a graphical color display (LCD TFT 3.5'', 320 x 240 pixels) and an internal memory capacity of 8GB for data archiving.

Data Logging and Presentation:
Data is logged in CSV format and can be presented digitally, as analog indicators, line charts, or bar graphs. The recorder supports independent recording for each group of logical channels and features extensive alarm, math, and scaling functions.

Connectivity:
The KD6 includes a USB Host 2.0 and a modern Ethernet interface (10/100 Base-T) supporting Modbus TCP/IP, HTTP, and FTP protocols. It offers services like a web server, FTP server, and DHCP client. Parameters can be programmed using free eCon software, and the device can synchronize with a time server via NTP.

Technical Data:
The device dimensions are 96 x 96 x 77 mm, with a protection grade of IP65 on the frontal side and IP20 on the terminal side. It supports various sensor types and input signals, including RTD and thermocouples, with specific standard ranges and basic errors.

Safety and Compatibility:
The KD6 complies with electromagnetic compatibility standards (EN 61000-6-2 and EN 61000-6-4) and isolation requirements (EN 61010-1). It is suitable for installation category III and operates at altitudes below 2000 m.

Operating Conditions:
The device operates with a supply voltage of 85...253 V AC or 20...60 V DC, with a power consumption of ≤ 12 VA. It functions within an ambient temperature range of -10 to 55°C and a humidity range of 0 to 95% without condensation.

Configuration and Remote Access:
The KD6 can be configured and updated using eCon software via RS-485 or Ethernet. It supports remote reading of parameters through a web server and downloading archived data via FTP.

Ordering Information:
The KD6 is available with various I/O module configurations, supply voltage options, and acceptance tests. Custom-made versions and language options are also available upon request.
See more

Catalog excerpts

KD6-2

KD6 - SCREEN RECORDERFEATURES iNPUTS OUTPUTS GALVANiC iSQLATiON TECHNICAL DATA 2 or 6 inputs; 0 V d.c. - inactive binary input, 5...24 V d.c. - active binary input Binary inputs

 Open the catalog to page 2
KD6-3

KD6 - screen recorder rated operating conditions Preheating time Supply voltage Ambient temperature Operating position without condensation Additional error (in % of the basic error) from ambient temperature change: < 50% / 10°C Safety and compability requirements Electromagnetic compatibility Isolation between circuits Polution level Installation category Maximal phase-to-earth voltage Altitude a.s.l. noise immunity noise emissions basic 2 III • for supply circuit and relay outputs 300 V • for measuring input 50 V • for circuits of RS-485, Ethernet, analog outputs: 50 V < 2000 m data visualisation...

 Open the catalog to page 3
KD6-4

KD6 - screen recorder recordeR configuration with FREE eCon Software ability to configure and update of KD6 with free eCon software (via RS-485 or Ethernet interface) Saving the configuration to a file and loading to many of the same recorders or creating a backup copy. remote readout of parameters throug Ethernet: WWW server, FTP www server for remote reading of current measurement data; FTP server for downloading archived data in CSV files

 Open the catalog to page 4
KD6-5

ORDERING CODE xx I/O module - slot X*: 4 x programmable measuring inputs without module 6 x relay outputs 4 x relay outputs + 4 x binary inputs separated from each other 4 x analog outputs + 4 x binary inputs with common ground 4 x programmable measuring inputs Supply voltage: Acceptance tests: * all possible variants for slot X are described in the user manual in chapter 11 ** only after agreeing with the manufacturer KD6-19 enSifam Tinsley Instrumentation Ltd 1 Warner Drive, Springwood Industrial Estate, Braintree, Essex CM7 2YW Contact No. : +44 (0) 1376 335271 Email: [email protected]...

 Open the catalog to page 5

All Sifam Tinsley catalogs and technical brochures

  1. PD8W

    2  Pages

  2. INSU 5DX+

    6  Pages

  3. RE11

    2  Pages

  4. AP35-3RJ12

    10  Pages

  5. PD24

    8  Pages

  6. CBCT

    10  Pages

  7. ELPR

    6  Pages

  8. TW-E Series

    3  Pages

  9. Omicron UVR

    4  Pages

  10. UNO NX

    9  Pages

  11. ND31PLUS

    8  Pages

  12. LTRP Series

    12  Pages

  13. Gamma 36

    9  Pages

  14. PD9

    2  Pages

  15. ND31

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.