Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated
92Pages

{{requestButtons}}

Catalog excerpts

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 1

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Medium-Voltage Switchgear

Open the catalog to page 1
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 2

Typical uses Application in public and industrial energy systems Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017

Open the catalog to page 2
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 3

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 ■ 2017 Invalid: Catalog HA 40.2 ■ 2014 siemens.com/medium-voltage-switchgear siemens.com/8DJH The products and systems described in this catalog are manufactured and sold according to a certified management system (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001). Contents Application Page Types, typical uses, ratings, approvals 4 and 5 Features, safety, technology, classification 6 to 8 Technical Data Electrical data of the switchgear 9 Switching capacity and...

Open the catalog to page 3
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 4

Individual circuit-breaker panel 500 mm 4 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017

Open the catalog to page 4
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 5

Typical uses, ratings, approvals 8DJH switchgear is a factory-assembled, type-tested, 3-pole metal-enclosed single-busbar switchgear for indoor installation. 8DJH switchgear is used in public and industrial energy systems of the secondary distribution level, e.g. in • Local ring-main units, customer transfer substations and switching substations of power supply and public utilities • Wind power and solar plants, hydroelectric power plants • Water and sewage treatment plants • Airports, railway stations, underground railway stations • Open-cast mining facilities • High-rise buildings....

Open the catalog to page 5
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 6

Requirements Features Environmental independence Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts of the primary circuit under high voltage of 8DJH switchgear • Insensitive to certain aggressive ambient conditions, such as: - Saline air - Air humidity - Dust - Condensation • Tight to ingress of foreign objects, such as: - Dust - Pollution - Small animals - Humidity. Compact design Thanks to the use of SF6 insulation, compact dimensions are possible. Thus: • Existing switchgear rooms and substation rooms can be used...

Open the catalog to page 6
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 7

General • Three-pole primary enclosure, metal-enclosed • Welded switchgear vessel without seals, made of stainless steel, with welded-in bushings for electrical connections and mechanical components • Insulating gas SF6 (fluorinated greenhouse gas) • Maintenance-free components under normal ambient conditions according to IEC 62271-1 and VDE 0671-1 • Three-position switch-disconnector with load-break function and make-proof earthing function • Vacuum circuit-breaker • Cable connection with outside-cone plug-in system - In ring-main and circuit-breaker feeders with bolted contact (M16) - In...

Open the catalog to page 7
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 8

Designation of the internal arc classification IAC IAC class for 8DJH Standard and 8DJH Compact design for - Wall-standing arrangement - Free-standing arrangement Additionally only for 8DJH Compact design for - Installation in substations without control aisle 1) 1) Rear space required for pressure relief. Application recommended in prefabricated substations without control aisle, tested according to IEC 62271-202. Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■ 2017

Open the catalog to page 8
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 9

Technical Data Electrical data of the switchgear Rated voltage Ur Rated short-duration power-frequency withstand voltage Ud – Phase-to-phase, phase-to-earth, open contact gap – Across the isolating distance Rated lightning impulse withstand voltage Up – Phase-to-phase, phase-to-earth, open contact gap – Across the isolating distance or switchgear with t k = 3 s (design option) Rated insulation level Rated normal current Ir 2) for circuit-breaker feeders 50 Hz Rated short-time withstand current Ik for switchgear with t k = 3 s (design option) Rated peak withstand current Ip Rated...

Open the catalog to page 9
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 10

Three-position switch-disconnector Switching capacity for general-purpose switches according to IEC / EN 62271-103 (former: IEC / EN 60265-1 /VDE 0670-301) 1) Design option 2) Depending on HV HRC fuse-link Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■ 2

Open the catalog to page 10
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 11

Switching capacity and classification of switching devices Vacuum circuit-breaker Switching capacity according to IEC / EN 62271-100 /VDE 0671-100 Type 1.1 with three-position disconnector Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■

Open the catalog to page 11
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 12

Product Range Individual panels and modules – freely configurable for up to 4 functions in the block Cable feeder Type K(E) 2) 430 mm wide with make-proof earthing switch Vacuum circuit-breaker Three-position switch-disconnector Three-position disconnector Capacitive voltage detecting system Circuit-breaker feeder Type R 310 mm wide Ring-main feeder Cable-type current transformer Cable connection with outside cone (not included in the scope of supply) Surge arrester or limiter Make-proof earthing switch Transformer feeder 1) Only for end panel, on the free connection side of the busbar 2)...

Open the catalog to page 12
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 13

Product Range Individual panels with switch-fuse combination Type H 1) 430 mm wide with switch-disconnector Vacuum circuit-breaker Three-position switch-disconnector Three-position disconnector Capacitive voltage detecting system Type S(620) (earthing on the left) 620 mm wide Bus sectionalizer panel with switch-disconnector Type S(500) with current transformer 500 mm wide Current transformer Plug-in voltage transformer 4MT3 Type V (with circuitbreaker 1.1 or 2) 500 mm wide 4MT3 Bus sectionalizer panel with circuit-breaker Design option with current transformer 4MT3 1) Also executable as...

Open the catalog to page 13
Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated - 14

Product Range Individual panels Circuit-breaker feeder Type R(500) 500 mm wide Ring-main feeder Type L(500) with circuitbreaker type 1.1 or 4MT3 type 2) 500 mm wide Three-position switch-disconnector Vacuum circuit-breaker Capacitive voltage detecting system 4MT8 Three-phase current transformer Busbar voltage metering panel, fused on the primary side HA40-2274b eps Busbar voltage metering panel Cable-type current transformer Cable connection with outside cone (not included in the scope of supply) Surge arrester or limiter 4MT3 Plug-in voltage transformer Busbar earthing panel HA40-2138a eps...

Open the catalog to page 14

All Siemens Medium-voltage – Power distribution catalogs and technical brochures

  1. E-House