Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Medium-Voltage Switchgear
Open the catalog to page 1Typical uses Application in public and industrial energy systems Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Open the catalog to page 2Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated Medium-Voltage Switchgear Catalog HA 40.2 ■ 2017 Invalid: Catalog HA 40.2 ■ 2014 siemens.com/medium-voltage-switchgear siemens.com/8DJH The products and systems described in this catalog are manufactured and sold according to a certified management system (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001). Contents Application Page Types, typical uses, ratings, approvals 4 and 5 Features, safety, technology, classification 6 to 8 Technical Data Electrical data of the switchgear 9 Switching capacity and...
Open the catalog to page 3Individual circuit-breaker panel 500 mm 4 Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated · Siemens HA 40.2 · 2017
Open the catalog to page 4Typical uses, ratings, approvals 8DJH switchgear is a factory-assembled, type-tested, 3-pole metal-enclosed single-busbar switchgear for indoor installation. 8DJH switchgear is used in public and industrial energy systems of the secondary distribution level, e.g. in • Local ring-main units, customer transfer substations and switching substations of power supply and public utilities • Wind power and solar plants, hydroelectric power plants • Water and sewage treatment plants • Airports, railway stations, underground railway stations • Open-cast mining facilities • High-rise buildings....
Open the catalog to page 5Requirements Features Environmental independence Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts of the primary circuit under high voltage of 8DJH switchgear • Insensitive to certain aggressive ambient conditions, such as: - Saline air - Air humidity - Dust - Condensation • Tight to ingress of foreign objects, such as: - Dust - Pollution - Small animals - Humidity. Compact design Thanks to the use of SF6 insulation, compact dimensions are possible. Thus: • Existing switchgear rooms and substation rooms can be used...
Open the catalog to page 6General • Three-pole primary enclosure, metal-enclosed • Welded switchgear vessel without seals, made of stainless steel, with welded-in bushings for electrical connections and mechanical components • Insulating gas SF6 (fluorinated greenhouse gas) • Maintenance-free components under normal ambient conditions according to IEC 62271-1 and VDE 0671-1 • Three-position switch-disconnector with load-break function and make-proof earthing function • Vacuum circuit-breaker • Cable connection with outside-cone plug-in system - In ring-main and circuit-breaker feeders with bolted contact (M16) - In...
Open the catalog to page 7Designation of the internal arc classification IAC IAC class for 8DJH Standard and 8DJH Compact design for - Wall-standing arrangement - Free-standing arrangement Additionally only for 8DJH Compact design for - Installation in substations without control aisle 1) 1) Rear space required for pressure relief. Application recommended in prefabricated substations without control aisle, tested according to IEC 62271-202. Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■ 2017
Open the catalog to page 8Technical Data Electrical data of the switchgear Rated voltage Ur Rated short-duration power-frequency withstand voltage Ud – Phase-to-phase, phase-to-earth, open contact gap – Across the isolating distance Rated lightning impulse withstand voltage Up – Phase-to-phase, phase-to-earth, open contact gap – Across the isolating distance or switchgear with t k = 3 s (design option) Rated insulation level Rated normal current Ir 2) for circuit-breaker feeders 50 Hz Rated short-time withstand current Ik for switchgear with t k = 3 s (design option) Rated peak withstand current Ip Rated...
Open the catalog to page 9Three-position switch-disconnector Switching capacity for general-purpose switches according to IEC / EN 62271-103 (former: IEC / EN 60265-1 /VDE 0670-301) 1) Design option 2) Depending on HV HRC fuse-link Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■ 2
Open the catalog to page 10Switching capacity and classification of switching devices Vacuum circuit-breaker Switching capacity according to IEC / EN 62271-100 /VDE 0671-100 Type 1.1 with three-position disconnector Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kV, Gas-Insulated ■ Siemens HA 40.2 ■
Open the catalog to page 11Product Range Individual panels and modules – freely configurable for up to 4 functions in the block Cable feeder Type K(E) 2) 430 mm wide with make-proof earthing switch Vacuum circuit-breaker Three-position switch-disconnector Three-position disconnector Capacitive voltage detecting system Circuit-breaker feeder Type R 310 mm wide Ring-main feeder Cable-type current transformer Cable connection with outside cone (not included in the scope of supply) Surge arrester or limiter Make-proof earthing switch Transformer feeder 1) Only for end panel, on the free connection side of the busbar 2)...
Open the catalog to page 12Product Range Individual panels with switch-fuse combination Type H 1) 430 mm wide with switch-disconnector Vacuum circuit-breaker Three-position switch-disconnector Three-position disconnector Capacitive voltage detecting system Type S(620) (earthing on the left) 620 mm wide Bus sectionalizer panel with switch-disconnector Type S(500) with current transformer 500 mm wide Current transformer Plug-in voltage transformer 4MT3 Type V (with circuitbreaker 1.1 or 2) 500 mm wide 4MT3 Bus sectionalizer panel with circuit-breaker Design option with current transformer 4MT3 1) Also executable as...
Open the catalog to page 13Product Range Individual panels Circuit-breaker feeder Type R(500) 500 mm wide Ring-main feeder Type L(500) with circuitbreaker type 1.1 or 4MT3 type 2) 500 mm wide Three-position switch-disconnector Vacuum circuit-breaker Capacitive voltage detecting system 4MT8 Three-phase current transformer Busbar voltage metering panel, fused on the primary side HA40-2274b eps Busbar voltage metering panel Cable-type current transformer Cable connection with outside cone (not included in the scope of supply) Surge arrester or limiter 4MT3 Plug-in voltage transformer Busbar earthing panel HA40-2138a eps...
Open the catalog to page 14All Siemens Medium-voltage – Power distribution catalogs and technical brochures
-
Outdoor systems
16 Pages
-
8DJH 12 – blue GIS
6 Pages
-
Siemens Vacuum Recloser 3AD
56 Pages
-
3AH4 Vacuum Circuit-Breakers
50 Pages
-
3AH3 Vacuum Circuit-Breakers
58 Pages
-
NXAIR C The Optimum
24 Pages
-
E-House
22 Pages
-
Distributing Power Economically
24 Pages