Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated
48Pages

{{requestButtons}}

Catalog excerpts

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 1

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Medium-Voltage Switchgear

Open the catalog to page 1
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 2

Application Public power supply system Application Industry NXPLUS C switchgear 20 kV (example) R-HA35-365 tif Photo: Harald M. Valderhaug Application Industry and offshore Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated· Siemens HA 35.41 · 2020

Open the catalog to page 2
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 3

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated Medium-Voltage Switchgear Catalog HA 35.41 ■ 2020 siemens.com/nxplusc Contents Page Applications Types, typical uses, ratings 4 and 5 Requirements Features, safety, technology 6 and 7 Technical data Electrical data 8 to 11 Panel dimensions Single busbar 16 to 25 Product range Single-busbar panels 29 to 35 Components Panel connection 38 to 40 Standards Standards, specifications, guidelines 41 to 44 The products and systems described in this catalog are manufactured and sold according to a certified management...

Open the catalog to page 3
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 4

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated· Siemens HA 35.41 · 2020

Open the catalog to page 4
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 5

Typical uses, ratings Typical uses Fixed-mounted circuit-breaker switchgear NXPLUS C is a factory-assembled, type-tested, metal-enclosed, SF6-insulated switchgear with metallic partitions 3) for single-busbar and double-busbar applications for indoor installation. It is used in transformer and switching substations, e.g., in: • Power supply companies • Power stations • Cement industry • Automobile industry • Iron and steel works • Rolling mills • Mining industry • Textile, paper and food industries • Chemical industry • Petroleum industry • Pipeline installations • Offshore installations •...

Open the catalog to page 5
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 6

Features Safety Environmental independence Hermetically tight, welded switchgear vessels made of stainless steel as well as single-pole solid insulation make the parts of the primary circuit under high voltage of NXPLUS C switchgear • nsensitive to certain aggressive ambient conditions, I such as saline air, air humidity, dust and condensation • Tight to ingress of foreign objects, such as dust, p ollution, small animals, humidity • Independent of the site altitude. This high degree of environmental independence cannot be achieved for the air-insulated metering panel due to the partial air...

Open the catalog to page 6
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 7

Requirements Technology General • -pole enclosure of the primary part consisting of a 3 switchgear vessel made of stainless steel • Insulating gas SF6 (fluorinated greenhouse gas) • hree-position switch as busbar disconnector and T feeder earthing switch • ake-proof earthing by means of the vacuum circuit- M breaker • Compact dimensions due to SF6 insulation • ermetically tight, welded switchgear vessel made of H stainless steel • -pole, solid-insulated, screened busbars, plug-in type 1 • able connection with outside-cone plug-in system, or C for connection of solid-insulated bars •...

Open the catalog to page 7
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 8

Technical data Electrical data, filling pressure, temperature for single-busbar switchgear Common Rated insulation level electrical data, filling pressure and temperature Rated voltage Ur Rated short-duration power-frequency withstand voltage Ud – hase-to-phase, phase-top earth, open contact gap – across the isolating distance Rated lightning impulse withstand voltage Up – hase-to-phase, phase-top earth, open contact gap – across the isolating distance Rated frequency fr Rated normal current 3) Ir Rated filling level (absolute) pre Minimum functional level (absolute) pme Ambient air...

Open the catalog to page 8
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 9

Technical data Electrical data, filling pressure, temperature for single-busbar switchgear Rated voltage Ur Disconnector panel 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A Rated short-time withstand current Ik Rated peak withstand current Ip Endurance classes according to IEC 62271‑102 Threeposition switchdisconnector/ fuse combination Rated normal current 3) 4) Iload Rated short-time withstand current Ik Auxiliary trans former panel (with HV HRC fuses) Rated short-circuit making current 4) Ima Rated peak withstand current 4) Ip Rated transfer current TDItransfer, TDIto Rated take-over...

Open the catalog to page 9
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 10

Technical data Electrical data, filling pressure, temperature for single-busbar switchgear Rated voltage Ur Ringmain panel Rated normal current 3) Iload Rated short-time withstand current Ik Rated peak withstand current Ip Rated short-circuit making current Ima Rated normal current 3) 4) Ir Rated short-time withstand current Ik Rated peak withstand current 4) Ip Rated short-circuit making current 4) Ima Endurance class according to IEC 62271‑103 Vacuum contactor panel with HV HRC fuses Electrical endurance of the vacuum contactor panel (with HV HRC fuses) Endurance class DISCONNECTING M0...

Open the catalog to page 10
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 11

Electrical data, filling pressure, temperature for double-busbar switchgear Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated • Siemens HA 35.41 • 2020

Open the catalog to page 11
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 12

Technical data Room planning Switchgear installation • For single-busbar applications: – Wall-standing arrangement or – Free-standing arrangement – Face-to-face arrangement accordingly • For double-busbar applications: – Back-to-back arrangement (free-standing arrangement). Switchgear fixing • For floor openings and fixing points of the switchgear, see pages16 to 28 • Foundations: – Steel girder construction – Steel-reinforced concrete with foundation rails, welded or bolted on. Room dimensions See imension drawings below. d Panel dimensions See pages 16 to 28. Room height • ≥ 2750 mm N...

Open the catalog to page 12
Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 36 kV, Gas-Insulated - 13

Technical data Room planning Switchgear installation Free-standing arrangement for single-busbar switchgear * Control aisle depending on national specifications; for extension/panel replacement: ≥ 1400 mm recommended (450 mm, 600 mm panels) ≥ 1600 mm recommended (900 mm panels) ** Lateral wall distances on the left or on the right; for installation and maintenance (according to IEC 61936‑1): ≥ 500 mm recommendable ≥ 00 mm required for auxiliary transformer panels 5 with lateral cable connection as end panels *** ≥ 800 mm aisle for operation (according to IEC 62271‑200) All panels with cable...

Open the catalog to page 13

All Siemens Medium-voltage – Power distribution catalogs and technical brochures

  1. E-House

    22 Pages